ADDISON, IL —
OSHA Inspection: SPROVIERI'S CUSTOM COUNTERS INC.
Unprogrammed Related inspection · Health discipline
At a glance
On , OSHA opened an unprogrammed Related health inspection of SPROVIERI'S CUSTOM COUNTERS INC. in 55 LAURA DR., ADDISON, IL 60101 (NAICS 327991). OSHA activity number 342132537.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SPROVIERI'S CUSTOM COUNTERS INC.
- Site address
- 55 LAURA DR.
- City
- ADDISON
- State
- IL
- ZIP
- 60101
- Mailing
- 55 LAURA DR., ADDISON, IL 60101
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327991
- Employees
- 135
- Ownership type
- A
Citations
3 citations on file for this inspection.
5(a)(1)
- Issued
- Aug 24, 2017
- Abate by
- Apr 30, 2018
- Penalty
- Initial $6,926 · Current $6,926
General-duty citation text
OSH Act of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees inside and outside of the facility were exposed to the combustible dust explosion, deflagration, and other fire hazards resulting from an internal dust collector deflagration or fire event within one of two outdoor unprotected filter media dust collectors. On or about February 27, 2017, the outdoor Murphy-Rogers model WBS 94D (S/N 1005) and Murphy-Rogers model MRM 124D (S/N 1173) filter media dust collectors collecting a mixture of combustible DuPont Corian Solid Surface Material were located in near proximity to a means of egress (building entry/exit), a break area, and a yard area containing stored process materials. The two dust collectors lacked means of (1) explosion protection, (2) deflagration propagation protection (isolation), and (3) fire protection. The outdoor dust collectors flanked a means of egress (access door), were located in immediate proximity to a break area, and were located near materials in storage. The outdoor dust collectors returned exhaust air directly into the occupied building. In the event of an internal deflagration, any employees outside of the building and in proximity to the dust collector may be exposed to explosion hazards resulting from vessel failure from over pressurization such as a resulting pressure wave, expanding flame front (fire ball), and missile fragments. In the event of an internal deflagration, employees both inside and outside of the building may be exposed to propagating flame front hazards due to unprotected vessel connections such as the dirty air inlet, dirty air return outlet, and the vessels material discharge outlet. Finally, in the event of an internal fire, employees inside of the building may be exposed to the hazardous byproducts of an internal fire such as smoke, toxic gases, embers, and flames. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
- — I (O) $6926
- — Z (S) $6926
1910.22 A01
- Issued
- Aug 24, 2017
- Abate by
- Sep 22, 2017
- Penalty
- Initial $6,926 · Current $0 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): (1) All places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition. On or about February 27, 2017, employees working in the solid surface shop were exposed to fire and explosion hazards due to an excessive accumulation of dust on surfaces throughout the shop. The employer failed to ensure that the solid surface shop was kept in a clean condition through adequate housekeeping methods and schedules. Abatement certification is required for this item in accordance with 1903.19(c).
Recent events (2)
- — I (O) $0
- — Z (S) $6926
1910.305 B01 II
- Issued
- Aug 24, 2017
- Penalty
- Initial $5,541 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. On or about February 27, 2017, employees in the Solid Surface Shop were exposed to electrical shock and fire hazards due to an uncovered opening on an electric shutoff box that exposed the wires inside. The employer failed to ensure that unused openings on the box were effectively closed. No abatement documentation or certification required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $5541
More inspections at Sprovieri'S Custom Counters INC.
View Sprovieri'S Custom Counters INC.'s full OSHA safety record →
More inspections in this industry (NAICS 327991)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342132537.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.