Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,473Inspections Most recent open 2026-07-28 Last loaded 2026-07-31

OSHA Inspection: DEPT OF AGRICULTURE - NRCS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of DEPT OF AGRICULTURE - NRCS in 840 BROOKS RD, IOWA FALLS, IA 50126 (NAICS 924120). OSHA activity number 342156957.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Dept of Agriculture - Nrcs — free Get an email when a new federal OSHA severe-injury report for Dept of Agriculture - Nrcs is published. One employer, no account, unsubscribe in one click.
Site address
840 BROOKS RD
City
IOWA FALLS
State
IA
ZIP
50126
Mailing
840 BROOKS RD, IOWA FALLS, IA 50126
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
2
Ownership type
D

2 citations on file for this inspection.

1910.305 G01 IV A

Serious Gravity 5 3 instances 5 exposed
Issued
May 22, 2017
Abate by
Jun 13, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  (a) At a workstation, an APC Surge Arrest Relocatable Power Tap was used as an extension cord to furnish power to a Haier Refrigerator Model BC-111 and HP Printer Unit (Serial JPGFG01023).  (b) At a second workstation, an SnapIt Relocatable Power Tap was used as an extension cord to furnish power to a Hamilton Beach Type K24 Kettle (teapot) Model 40870.  (c) At the Minolta Printer/Copier Model 360, an NOMA LR9309 Relocatable Power Tap was used as an extension cord to furnish power to the printer/copier.
Recent events (1)
  • — Z (S) $0

1910.304 B04 II B

Repeat Gravity 5 1 instance 3 exposed
Issued
May 22, 2017
Abate by
Jun 6, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord- and plug-connected load in excess of the maximum specified in Table S-4:  Overloaded relocatable power taps:    (a) At a workstation, a Hamilton Beach Type K24 Kettle (teapot) Model 40870 operated at 1500 watts (12.5 amps) was plugged into a 15 amp SnapIt Relocatable Power Tap rated for 12 amps of use.  Other low voltage electronic equipment rated between 0.5-1.0 amps was also plugged into the RPT increasing amperage draw and overloading the device.   The Dept. of Agriculture NRCS was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA inspection number 948245, Notice number 1, item number 2, with respect to a workplace located in Newton, IA and became a final order on January 29, 2014.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos, which you believe will be helpful.  The abatement certification sheet is enclosed with the notice(s).
Recent events (1)
  • — Z (R) $0

View Dept of Agriculture - Nrcs's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342156957.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.