OSHA Inspection: NATIONAL PARK SERVICE, LAKE MEAD NATIONAL RECREATION AREA - RESOURCE MANAGEMENT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE, LAKE MEAD NATIONAL RECREATION AREA - RESOURCE MANAGEMENT in 601A NEVADA WAY, BOULDER CITY, NV 89005 (NAICS 712190). OSHA activity number 342214046.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Park Service, Lake Mead National Recreation Area - Resource Management — free Get an email when a new federal OSHA severe-injury report for National Park Service, Lake Mead National Recreation Area - Resource Management is published. One employer, no account, unsubscribe in one click.
Site address
601A NEVADA WAY
City
BOULDER CITY
State
NV
ZIP
89005
Mailing
601 NEVADA WAY, BOULDER CITY, NV 89005
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
712190
Employees
25
Ownership type
D

6 citations on file for this inspection.

1910.36 D01

Repeat Gravity 10 3 instances 25 exposed
Issued
Aug 30, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.36(d)(1): Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge. A device such as a panic bar that locks only from the outside is permitted on exit discharge doors:  (a) Northeast Conference Room Door: Employees are exposed to becoming entrapped in the event of a fire due to the Northeast designated exit door had a dead bolt lock on the door leading to exit discharge.  (b) North Central Entrance Door: Employees are exposed to becoming entrapped in the event of a fire due to the Northeast designated exit door had a dead bolt lock on the door leading to exit discharge.  (c) Northwest GIS Room Door: Employees are exposed to becoming entrapped in the event of a fire due to the Northeast designated exit door had a dead bolt lock on the door leading to exit discharge.  THE U.S. DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 913208, CITATION 01, ITEM NUMBER 001 AND WAS AFFIRMED AS A FINAL ORDER ON NOVEMBER 12, 2013, WITH RESPECT TO A WORKPLACE LOCATED AT U.S. DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, ASH MOUNTAIN NATIONAL PARK, 47050 GENERALS HIGHWAY, THREE RIVERS, CALIFORNIA 93271.
Recent events (1)
  • — Z (R) $0

1910.37 B01

Repeat Gravity 10 2 instances 25 exposed
Issued
Aug 30, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that an employee with normal vision can see along the exit route:  (a) Break Room: Employees were exposed to entrapment hazards in the event of a fire due to the Lithonia Emergency lights being inoperable.  (b) Northwest Hallway: Employees are exposed to becoming entrapped in the event of a fire due to the Lithonia Emergency Unit lights being inoperable.  THE U.S. DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 1056682, CITATION 01, ITEM NUMBER 001 AND WAS AFFIRMED AS A FINAL ORDER ON SEPTEMBER 1, 2015, WITH RESPECT TO A WORKPLACE LOCATED AT U.S. DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, GREAT BASIN NATIONAL PARK, LEHMAN CAVES VISITOR CENTER, 100 GREAT BASIN NATIONAL PARK, BAKER, NEVADA 89311.
Recent events (1)
  • — Z (R) $0

1910.37 B02

Repeat Gravity 10 1 instance 12 exposed
Issued
Aug 30, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  Northwest GIS Room Door: Employees are exposed to becoming entrapped in the event of a fire due to the Northeast designated exit door not being marked an "EXIT".  THE U.S. DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 913225, CITATION 01, ITEM NUMBER 003 AND WAS AFFIRMED AS A FINAL ORDER ON NOVEMBER 6, 2016, WITH RESPECT TO A WORKPLACE LOCATED AT U.S. DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, SEQUOIA AND KINGS CANYON, ASH MOUNTAIN MAINTENANCE FACILITIES, 47050 GENERALS HIGHWAY, THREE RIVERS, CALIFORNIA 93271.
Recent events (1)
  • — Z (R) $0

1910.303 B02

Repeat Gravity 5 2 instances 12 exposed
Issued
Aug 30, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) Copier Room: Employees are exposed to electric shock/fire by using a Relocatable Power Tap attached to an unsecured 2-plex box.  (b) Budget Analyst Office: Employees are exposed to electric shock/fire by using a Flexible Cord attached to Relocatable Power Tap, Model 7-Outlet Surgemaster Protector.  THE U.S. DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 992665, CITATION 01, ITEM NUMBER 005 AND WAS AFFIRMED AS A FINAL ORDER ON FEBRUARY 2, 2015, WITH RESPECT TO A WORKPLACE LOCATED AT U.S. DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, GRAND CANYON, VISITOR AND RESOURCE PROTECTION STATION, ONE THREE CLINIC ROAD, GRAND CANYON, ARIZONA 86023.
Recent events (1)
  • — Z (R) $0

1910.305 B02

Repeat Gravity 5 1 instance 12 exposed
Issued
Aug 30, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:   AIS Education Coordinator Office: Employees are exposed to electric shock/fire by the energized two receptacle wall outlet with a missing cover.  THE U.S. DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 1050143, CITATION 01, ITEM NUMBER 002 AND WAS AFFIRMED AS A FINAL ORDER ON JULY 29, 2015, WITH RESPECT TO A WORKPLACE LOCATED AT U.S. DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, JOSHUA TREE NATIONAL PARK, BLACK ROCK INTERAGENCY FIRE CENTER, 9800 BLACK ROCK CANYON ROAD, YUCCA VALLEY, CALIFORNIA 92284.
Recent events (1)
  • — Z (R) $0

1910.305 G01 IV A

Repeat Gravity 5 1 instance 10 exposed
Issued
Aug 30, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   GIS Office: Employees were exposed to electric shock/fire by using a Dell Computer attached to a Flexible Cord.  THE DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, GRAND CANYON, VISITOR AND RESOURCE PROTECTION STATION 1 WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 992665, CITATION 01, ITEM NUMBER 007 AND WAS AFFIRMED AS A FINAL ORDER ON FEBRUARY 2, 2015, WITH RESPECT TO A WORKPLACE LOCATED AT 3 CLINIC ROAD, GRAND CANYON, ARIZONA 86023.
Recent events (1)
  • — Z (R) $0

View National Park Service, Lake Mead National Recreation Area - Resource Management's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342214046.