Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PGA, INC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of PGA, INC in 185 SOUTH ST, FREELAND, PA 18224 (NAICS 326199). OSHA activity number 342246675.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch PGA, INC — free Get an email when a new federal OSHA severe-injury report for PGA, INC is published. One employer, no account, unsubscribe in one click.
Establishment
PGA, INC
Site address
185 SOUTH ST
City
FREELAND
State
PA
ZIP
18224
Mailing
PO BOX 7, FREELAND, PA 18224
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
18
Ownership type
A

2 citations on file for this inspection.

1910.303 G01 I A

Serious Gravity 1 3 instances 6 exposed
Issued
May 18, 2017
Abate by
Jun 7, 2017
Penalty
Initial $1,847 · Current $1,847
29 CFR 1910.303(g)(1)(i)(A): The depth of the working space in the direction of access to live parts may not be less than indicated in Table S-1. Distances shall be measured from the live parts if they are exposed or from the enclosure front or opening if they are enclosed;  a) Outside wall of label printing office: The access to a single pole breaker box was completely blocked by boxes and the installation did not have a clear space of at least 3 feet in front of its face, on or about, April 14, 2017.  b) Stephanie grinder area: The access to several breaker and switch boxes was impeded by stored materials including a table saw and miscellaneous containers of materials and the installations did not have clear spaces of at least 3 feet in front of their faces, on or about, April 14, 2017.  c) Liz grinder area: The access to several breaker and switch boxes was impeded by a wooden platform used for temporary feeding of the grinder and the installations did not have clear spaces of at least 3 feet in front of their faces, on or about, April 17, 2017.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $1847

1910.305 C04

Serious Gravity 1 1 instance 6 exposed
Issued
May 18, 2017
Abate by
Jun 7, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(c)(4): Faceplates for flush-mounted snap switches. Snap switches mounted in boxes shall have faceplates installed so as to completely cover the opening and seat against the finished surface.  a) Men's bathroom: A live light toggle switch was missing the cover, on or about, April 14, 2017.  ABATEMENT CERTIFICATION REQUIRED