PECOS, TX ·
OSHA Inspection: STALLION OIL FIELD SERVICES, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of STALLION OIL FIELD SERVICES, INC. in LEASE GRIZZLY WEST 77B-4-419 WELL NO. 1H 5.1 MILES WEST DIRECTION FROM PECOS, PECOS, TX 79772 (NAICS 213112). OSHA activity number 342250099.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STALLION OIL FIELD SERVICES, INC.
- Site address
- LEASE GRIZZLY WEST 77B-4-419 WELL NO. 1H 5.1 MILES WEST DIRECTION FROM PECOS
- City
- PECOS
- State
- TX
- ZIP
- 79772
- Mailing
- 950 CORBINDALE, SUITE 300, HOUSTON, TX 77024
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213112
- Employees
- 11
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.305 G02 III
- Issued
- Jun 14, 2017
- Abate by
- Jun 26, 2017
- Penalty
- Initial $1,006 · Current $604 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about April 06, 2017, electric power cords entering the electrical control panel of Stallion skid mobile home trailer No. 23243 and 36883 were not provided with a strain relief as to prevent pulling the cord directly from terminal screws. These conditions exposed employees to electrical shock hazards.
Recent events (2)
- · I (O) $603.6
- · Z (O) $1006
1910.305 J01 I
- Issued
- Jun 14, 2017
- Abate by
- Jun 26, 2017
- Penalty
- Initial $1,006 · Current $604 Reduced
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact: On or about April 06, 2017, employees were exposed to live parts from a single gang receptacle installed on the backside of a leased Stallion skid mobile home trailer no. 36883. This condition exposed employees to electrical shock hazards.
Recent events (2)
- · I (O) $603.6
- · Z (O) $1006
1910.303 B07 I
- Issued
- Jun 14, 2017
- Abate by
- Jun 26, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment. On or about April 06, 2017, the unused knock-out of the electrical control box located on skid mobile home trailer no. 23243 was not closed. This condition exposed employees to electrical shock hazards.
Recent events (2)
- · I (O) $0
- · Z (O) $0
1910.305 E01
- Issued
- Jun 14, 2017
- Abate by
- Jun 26, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures were not weatherproof in wet locations: On or about April 06, 2017, a receptacle installed outdoors did not have a weatherproof cover. This condition exposed employees to electrical shock hazards.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections at Stallion OIL Field Services, INC.
View Stallion OIL Field Services, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 213112)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 342250099.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.