WESTERN SPRINGS, IL —
OSHA Inspection: LAYNE CHRISTENSEN COMPANY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of LAYNE CHRISTENSEN COMPANY in 740 HILLGROVE AVENUE, WESTERN SPRINGS, IL 60558 (NAICS 237110). OSHA activity number 342259041.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LAYNE CHRISTENSEN COMPANY
- Site address
- 740 HILLGROVE AVENUE
- City
- WESTERN SPRINGS
- State
- IL
- ZIP
- 60558
- Mailing
- 721 W. ILLINOIS AVENUE, AURORA, IL 60506
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237110
- Employees
- 25
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.137 C02 VIII
- Issued
- Aug 29, 2017
- Abate by
- Sep 11, 2017
- Penalty
- Initial $12,675 · Current $12,675
General-duty citation text
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and/or the maximum intervals between tests were not conducted in accordance with Table I-4 and Table I-5. On or about April 17, 2017, employee(s) performing work at various field locations were required to use electrical protective equipment such as rubber insulating gloves during their assigned electrical work. The employees were required to work on or near voltages between 110 VAC - 480 VAC. The rubber insulating gloves were not subjected to periodic electrical tests. Employees were thereby exposed to the hazards associated with live electrical parts.
Recent events (3)
- — F (S) $12675
- — C (S) $12675
- — Z (S) $12675
1910.332 B01
- Issued
- Aug 29, 2017
- Abate by
- Oct 17, 2017
- Penalty
- Initial $12,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: Western Springs, IL. - On or about April 17, 2017, a motor service technician was required to troubleshoot the circuit elements and electrical parts of the 2,300/2,400 V AC well pump located at 740 Hillgrove Avenue, Western Springs, IL., Pump House, Well No. 3. Employee(s) were not adequately trained in and familiar with safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments. The employer's electrical safety-related work practice training did not include the following: 1. Prior to performing troubleshooting work on circuit elements and electrical parts always lockout / tagout all electrical power sources in the area of work. 2. Verify that de-energization conditions are in accordance with 29 CFR 1910.333(b)(2)(iii)(D) and (b)(2)(iv)(B). Employee(s) were thereby exposed to the hazards associated with live electrical parts.
Recent events (3)
- — F (S) $0
- — C (S) $12675
- — Z (S) $12675
1910.333 B02 IV
- Issued
- Aug 29, 2017
- Abate by
- Oct 17, 2017
- Penalty
- Initial $12,675 · Current $12,675
General-duty citation text
29 CFR 1910.333(b)(2)(iv): Verification of deenergized condition. The requirements of this paragraph were not met before any circuits or equipment were considered or worked as deenergized. Western Springs, IL. And other field repair locations - On or about April 17, 2017, a motor technician was required to troubleshoot the circuit elements and electrical parts of a well pump located at 740 Hillgrove Ave. Western Springs, IL., Pump House, Well No. 3. The employer's procedures did not include step corresponding to the requirements of paragraph 29 CFR 1910.333(b)(2)(iv).
Recent events (3)
- — F (S) $12675
- — C (S) $12675
- — Z (S) $12675
1910.335 A01 I
- Issued
- Aug 29, 2017
- Abate by
- Oct 17, 2017
- Penalty
- Initial $12,675 · Current $12,675
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: Western Springs, Illinois - On or about April 17, 2017, a motor service technician was required to troubleshoot the circuit elements and electrical parts of the 2,300 V AC well pump located at 740 Hillgrove Avenue, Western Springs, IL., Pump House, Well No. 3. The technician worked in an area where there were electrical hazards (2,400 V AC) and was not provided with electrical protective equipment including voltage-rated gloves and flame resistant clothing. The employee was thereby exposed to the hazards associated with live electrical parts.
Recent events (3)
- — F (O) $12675
- — C (S) $12675
- — Z (S) $12675
1910.335 A01 IV
- Issued
- Aug 29, 2017
- Abate by
- Oct 17, 2017
- Penalty
- Initial $12,675 · Current $12,675
General-duty citation text
29 CFR 1910.335(a)(1)(iv): Employees exposed to the danger of head injury from electric shock or burns due to contact with exposed energized parts did not were nonconductive head protection: Western Springs, Illinois - On or about April 17, 2017, a motor service technician was required to troubleshoot the circuit elements and electrical parts of the 2, 300 V AC well pump located at 740 Hillgrove Avenue, Western Springs, IL., Pump House, Well No. 3. The technician worked in an area where there were electrical hazards (2,400 V AC). The technician was not provided with nonconductive head protection. The employee(s) was thereby exposed to the hazards associated with live electrical parts.
Recent events (3)
- — F (O) $12675
- — C (S) $12675
- — Z (S) $12675
1910.335 A01 V
- Issued
- Aug 29, 2017
- Abate by
- Oct 17, 2017
- Penalty
- Initial $12,675 · Current $12,675
General-duty citation text
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face: Western Springs, Illinois - On or about April 17, 2017, A motor service technician was required to troubleshoot the circuit elements and electrical parts of the 2,300 V AC well pump located at 740 Hillgrove Avenue, Western Springs, IL., Pump House, Well No. 3. The technician worked in an area where there were electrical hazards (2,400 V AC). The technician was not provided with an arc-rated face shield. The employee(s) was thereby exposed to the hazards associated with live electrical parts.
Recent events (3)
- — F (O) $12675
- — C (S) $12675
- — Z (S) $12675
More inspections at Layne Christensen Company
View Layne Christensen Company's full OSHA safety record →
More inspections in this industry (NAICS 237110)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342259041.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.