Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,201Inspections Most recent open 2026-08-31 Last loaded 2026-09-03

OSHA Inspection: AARGUS PLASTICS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AARGUS PLASTICS, INC. in 540 ALLENDALE DRIVE, WHEELING, IL 60090 (NAICS 326111). OSHA activity number 342348240.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Aargus Plastics, INC. for free Get an email when a new federal OSHA severe-injury report for Aargus Plastics, INC. is published. One employer, no account, unsubscribe in one click.
Site address
540 ALLENDALE DRIVE
City
WHEELING
State
IL
ZIP
60090
Mailing
540 ALLENDALE, WHEELING, IL 60090
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326111
Employees
152
Ownership type
Private (A)

8 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 31, 2017
Abate by
Aug 24, 2017
Penalty
Initial $8,149 · Current $5,500 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to caught in hazards:     a) On or about May 12, 2017, in the Tool Room, the JET horizontal/vertical metal cutting band-saw, model #HVBS-7MW, serial #8059180, used by employees to cut angle iron, was not equipped with a mechanism to prevent the saw from automatically restarting upon restoration of power after a power failure.    Among other methods, one method of feasible abatement would be to follow the guidelines in the American National Standards Institute (ANSI) B11.10  2003, Safety Requirements for Metal Sawing Machines, Section 6.11 Machine Starting.  Incorporate a type of drive motor starter that will disconnect the drive motor to the power source in the event of control voltage or power system failure.
Recent events (2)
  • · I (S) $5500
  • · Z (S) $8149

1910.22 D01

Serious Gravity 1 2 instances 2 exposed
Issued
Jul 31, 2017
Abate by
Aug 24, 2017
Penalty
Initial $4,889 · Current $3,000 Reduced
29 CFR 1910.22(d)(1): Walking-working surfaces were not inspected, regularly and as necessary, and maintained in a safe condition:    a) Production Area - On May 19, 2017, the employer did not ensure that the floor was maintained in a safe condition, as there was an air hose near Machine #B-108 on the floor across the aisle that created a tripping hazard.       b) Production Area - On May 19, 2017, the employer did not ensure that the floor was maintained in a safe condition, as there was an electrical cord powering an extruder machine on the floor across the aisle that created a tripping hazard.
Recent events (2)
  • · I (S) $3000
  • · Z (S) $4889

1910.178 L04 III

Serious Gravity 1 1 instance 3 exposed
Issued
Jul 31, 2017
Penalty
Initial $4,889 · Current $3,000 Reduced
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not conducted at least once every three years:    a) Throughout Plant - On or about May 19, 2017, the employer did not ensure that an evaluation of the powered industrial truck operators' performance was conducted at least once every three years.
Recent events (2)
  • · I (S) $3000
  • · Z (S) $4889

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 31, 2017
Penalty
Initial $6,519 · Current $3,500 Reduced
29 CFR 1910.303(b)(2): Listed or labeled equipment were not used or installed in accordance with any instructions included in the listing or labeling:       a) Near Hopper #26 - On May 19, 2017, the employer did not ensure that the duplex receptacle metal box was installed in accordance with the listing or labeling while being used to provide electricity to a sealer machine.
Recent events (2)
  • · I (S) $3500
  • · Z (S) $6519

1910.305 G02 III

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 31, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws:  a) Near Hopper #26 - On May 19, 2017, the employer did not ensure that the flexible cord on the two outlet electrical box was provided with adequate strain relief.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.178 P01

Other-than-serious 2 instances 3 exposed
Issued
Jul 31, 2017
Abate by
Aug 24, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.178(p)(1): Powered industrial truck found to be in need of repair, defective, or in any way unsafe, were not taken out of service until it has been restored to safe operating condition:       a) Production Area - On or about May 19, 2017, the employer did not ensure that the TCM Forklift, model #FCG15F9, serial #A12R00483, that had broken back light covers, was missing two rubber foot pedal covers, and had bent and damaged back rests, was removed from service until repairs could be made.   b) Production Area - On or about May 19, 2017, the employer did not ensure that the Toyota Forklift, model #7FGCU20, serial #05793, that had broken back light covers, was missing two rubber foot pedal covers, and had bent and damaged back rests, was removed from service until repairs could be made.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.212 A02

Other-than-serious 2 instances 1 exposed
Issued
Jul 31, 2017
Abate by
Aug 24, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(2): The employer did not ensure that guard(s) on machine(s) were affixed to the machine or secured elsewhere when attachment to the machine was not possible:  a) Production Area - On May 19, 2017, the employer did not ensure the door cover to the housing of the power transmission apparatus of machine #B-108, was closed and secured.     b) Production Area - On May 19, 2017, the employer did not ensure the door cover to the housing of the power transmission apparatus of machine #B-113, was closed and secured.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 2 exposed
Issued
Jul 31, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): Working space about electric equipment rated 600 volts, nominal, or less was used for storage   a) Outside Tool Room - On May 19, 2017, the employer did not ensure that a clear area was maintained around the electrical disconnect equipment, such as the electrical switches that powers the west side of the building.  The area in front of the electrical panels was being used to store boxes, packaging, and broken equipment.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Aargus Plastics, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 342348240.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.