Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: B & I CONTRACTORS, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of B & I CONTRACTORS, INC. in CAMPO FELICE 2500 EDWARDS DRIVE, FORT MYERS, FL 33901 (NAICS 238220). OSHA activity number 342381613.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch B & I Contractors, INC. — free Get an email when a new federal OSHA severe-injury report for B & I Contractors, INC. is published. One employer, no account, unsubscribe in one click.
Site address
CAMPO FELICE 2500 EDWARDS DRIVE
City
FORT MYERS
State
FL
ZIP
33901
Mailing
2701 PRINCE ST., FORT MYERS, FL 33916
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238220
Employees
450
Ownership type
A

2 citations on file for this inspection.

1926.501 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 27, 2017
Abate by
Oct 10, 2017
Penalty
Initial $9,054 · Current $4,527 Reduced
29 CFR 1926.501(b)(1): Each employee on a walking/working surface with an unprotected side or edge which was 6 feet (1.8 m) or more above a lower level was not protected from falling by the use of guardrail systems, safety net systems, or personal fall arrest systems.    a) For employees working at 2500 Edwards Drive in Bradenton, as observed on or about June 2, 2017. Employees were installing feeder wires into a switchgear assembly. One of the employees was on top of the panel working without the use of a fall protection system exposing the eemployee to a 8 feet fall.
Recent events (2)
  • — I (S) $4527
  • — Z (S) $9054

1926.416 A03

Serious Gravity 10 1 instance 3 exposed
Issued
Sep 27, 2017
Abate by
Oct 10, 2017
Penalty
Initial $12,675 · Current $6,338 Reduced
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into physical or electrical contact with the electric power circuit.    a) For employees working at 2500 Edwards Drive in Bradenton, as observed on or about June 2, 2017. Employees were installing feeder wires into a switchgear assembly when an arc flash occurred as one of the ground wires contacted an energized feeder bus bar in the adjacent panel. The insulated barrier between the panels was cut out previously by employees installing the connecting bus bar.
Recent events (2)
  • — I (S) $6337.5
  • — Z (S) $12675

View B & I Contractors, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342381613.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.