Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: J M & R ELECTRICAL CO, INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of J M & R ELECTRICAL CO, INC in 3048 SHERIDAN DRIVE, AMHERST, NY 14226 (NAICS 238210). OSHA activity number 342406493.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch J M & R Electrical CO, INC — free Get an email when a new federal OSHA severe-injury report for J M & R Electrical CO, INC is published. One employer, no account, unsubscribe in one click.
Site address
3048 SHERIDAN DRIVE
City
AMHERST
State
NY
ZIP
14226
Mailing
19 VERMONT STREET, HOLLAND, NY 14080
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
6
Ownership type
A

2 citations on file for this inspection.

1926.403 I02 I

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 8, 2017
Penalty
Initial $1,570 · Current $800 Reduced
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph:     a) On or about 6/16/17, at the electrical room area of the site, Amherst, NY. The main distribution panel, 120/208 Volts; 600 Amps, lacked the cover plate to prevent accidental contact.     NO ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
  • — J (S) $800
  • — C (S) $1570
  • — Z (S) $1570

1926.403 H

Deleted Other-than-serious 1 instance 1 exposed
Issued
Sep 8, 2017
Penalty
Initial $0 · Current $0
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident:   a) On or about 6/16/17, at the electrical room area of the site, Amherst, NY. The panel PP-4, 120/208 Volts; 200 Amps, lacked the directory to indicate the purpose of overcurrent devices.   NO ABATEMENT CERTIFICATION REQUIRED