APOLLO BEACH, FL ·
OSHA Inspection: TAMPA ELECTRIC COMPANY
Fatality or catastrophe inspection · Safety discipline
At a glance
On , OSHA opened a fatality or catastrophe safety inspection of TAMPA ELECTRIC COMPANY in 13031 WYANDOTTE RD., APOLLO BEACH, FL 33572 (NAICS 221112). OSHA activity number 342446093.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TAMPA ELECTRIC COMPANY
- Site address
- 13031 WYANDOTTE RD.
- City
- APOLLO BEACH
- State
- FL
- ZIP
- 33572
- Mailing
- 702 N FRANKLIN ST., TAMPA, FL 33602
What kind of inspection was it?
- Inspection type
- Fatality or catastrophe (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221112
- Employees
- 800
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.132 A
- Issued
- Dec 27, 2017
- Abate by
- Jan 12, 2018
- Penalty
- Initial $12,675 · Current $12,675
General-duty citation text
29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered: a) For the work conducted around and on slag tanks, on or about June 29, 2017, appropriate personal protective equipment, such as but not limited to protective equipment for the head, feet, arms and body, was not used to protect employees' skin from thermal burns.
Recent events (2)
- · C (S) $12675
- · Z (S) $12675
1910.133 A01
- Issued
- Dec 27, 2017
- Abate by
- Jan 12, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.133(a)(1): The employer did not ensure that each affected employee uses appropriate eye or face protection when exposed to eye or face hazards from flying particles, molten metal, liquid chemicals, acids or caustic liquids, chemical gases or vapors, or potentially injurious light radiation: a) For the work conducted around and on slag tanks, on or about June 29, 2017, appropriate face protection was not selected to protect employees from thermal burns. Employees were exposed to high temperature slag while working at the bottom of a slag tank.
Recent events (2)
- · C (S) $0
- · Z (S) $0
1910.138 A
- Issued
- Dec 27, 2017
- Abate by
- Jan 12, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.138(a): The employer did not select and require employee(s) to use appropriate hand protection when employees' hands were exposed to hazards such as those from skin absorption of harmful substances; severe cuts or lacerations; severe abrasion; punctures; chemical burns; thermal burns; and harmful temperature extremes: a) For the work conducted around and on slag tanks on or about June 29, 2017, appropriate hand protection was not selected to protect employees from thermal burns. Employees were exposed to high temperature slag while working at the bottom of a slag tank.
Recent events (2)
- · C (S) $0
- · Z (S) $0
5(a)(1)
- Issued
- Dec 27, 2017
- Abate by
- Jan 22, 2018
- Penalty
- Initial $126,749 · Current $126,749
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to burn and/or struck by hazards associated with molten slag being released from the slag tank: a) At the slag tank 2A, on or about June 29, 2017, employees at/near the bottom of slag tank 2A working to clear slag tank clogging during regular operations were exposed to steam and molten slag being released from the slag tank. - The neck/tap hole of the slag tank had been clogged and/or partially clogged for 13 hours. Per the employer's Slag Tank Water Blasting Procedure the unit should have been taken off (shut down) after the last slag tap closed and was unable to be reopened within 6 to 8 hours. - Employer safe work procedures did not address a simultaneous blockage at the neck/tap hole and at the dog house gate at the bottom of the tank. A simultaneous blockage occurred on or about June 29, 2017. - During that time, the operational load in megawatts was run at full load/power and not reduced as per the employer's Slag Tank Water Blasting Procedure.
Recent events (2)
- · C (W) $126749
- · Z (W) $126749
1910.269 D02 III
- Issued
- Dec 27, 2017
- Abate by
- Jan 31, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(d)(2)(iii): Procedures were not developed, documented, and used for the control of potentially hazardous energy covered by paragraph (d) of this section: a) The employer did not develop, document, and implement specific LOTO procedures for shutting down the furnace and clearing clogs in the slag tanks, on or about June 29, 2017.
Recent events (2)
- · C (W) $0
- · Z (W) $0
More inspections at Tampa Electric Company
View Tampa Electric Company's full OSHA safety record →
More inspections in this industry (NAICS 221112)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 342446093.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.