Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,473Inspections Most recent open 2026-07-28 Last loaded 2026-07-31

OSHA Inspection: DEPT OF AGRICULTURE-NRCS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPT OF AGRICULTURE-NRCS in 2710 HWY 127, LOGAN, IA 51546 (NAICS 924120). OSHA activity number 342519758.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Dept of Agriculture-Nrcs — free Get an email when a new federal OSHA severe-injury report for Dept of Agriculture-Nrcs is published. One employer, no account, unsubscribe in one click.
Site address
2710 HWY 127
City
LOGAN
State
IA
ZIP
51546
Mailing
2710 HWY 127, LOGAN, IA 51546
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
4
Ownership type
D

6 citations on file for this inspection.

1910.157 G01

Serious Gravity 5 1 instance 4 exposed
Issued
Sep 8, 2017
Abate by
Sep 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting:  At the Logan NRCS employees are instructed via the Emergency Preparedness plan to evacuate if a fire cannot be easily extinguished.
Recent events (1)
  • — Z (S) $0

1910.303 G01

Serious Gravity 5 2 instances 4 exposed
Issued
Sep 8, 2017
Abate by
Sep 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment operating at 600 volts, nominal, or less to ground to permit ready and safe operation and maintenance of such equipment:    (a)  In the common store room/mapping room  a shredder and chairs were stored immediately in front of the 220 volt Cutler Hammer breaker panel where a minimum clearance of 3 feet should have been maintained.  (b) In the West rear storage room multiple items to include but not limited to ladders, buckets, table, water containers, and ice melt blocked access to the 220 volt Cutler Hammer breaker panel where a minimum clearance of 3 feet should have been maintained.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Repeat Gravity 5 1 instance 4 exposed
Issued
Sep 8, 2017
Abate by
Sep 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  In the break room the door leading to the rear exit was not labeled with a sign reading EXIT  The Department of Agriculture-NRCS was previously cited for a violation of this occupational safety and health standard or similar standard 29CFR 1910.37(b)(2) which was contained in OSHA inspection number 1147124 Notice 1, Item 1 and was affirmed as a final order on 8/4/2016 with respect to a workplace located at 709 Furnas Dr., Osceola, IA 50213
Recent events (1)
  • — Z (R) $0

1910.157 C01

Repeat Gravity 5 1 instance 4 exposed
Issued
Sep 8, 2017
Abate by
Sep 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  (a)  In the mail room the General TGP10E fire extinguisher was located on the floor and was not mounted  (b)  In the breakroom the Genersl Halon 1211 fire extinguisher was  located on the floor and was not mounted.    The Department of Agriculture-NRCS was previously cited for a violation of this occupational safety and health standard or similar standard 29CFR 1910.157(c)(1) which was contained in OSHA inspection number 962806 Notice 1, Item 2 and was affirmed as a final order on 4/30/2014 with respect to a workplace located at 815 E Highway 92, Winterset, IA 502723
Recent events (1)
  • — Z (R) $0

1910.157 E03

Repeat Gravity 5 6 instances 4 exposed
Issued
Sep 8, 2017
Abate by
Sep 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check  (a)  In the mail room the un-mounted General TGP10E fire extinguisher was last noted as inspected in 2002 indicating it had not been inspected in 15 years and beyond the 12 year hydrostatic testing requirement.    (b) In the breakroom the un-mounted General  HALON 1211 fire extinguisher was last noted as inspected September of 1991 beyond the 12 year hydrostatic testing requirement.  (c) In the Chevrolet Silverado license A373158 the  Badger 250MB fire extinguisher had not been inspected since 2004  and beyond the 12 year hydrostatic testing requirement  (d) In the Dodge Pickup license A344401 the Amerex B417 fire extinguisher had not been inspected since 2008  (e) In the Chevrolet Silverado license A373158 the  Badger 250MB fire extinguisher had not been inspected since 2004  and beyond the 12 year hydrostatic testing requirement  (f In the Chevrolet Silverado license A375973 the Badger 250MB fire extinguisher had not been inspected since 2006.  (f) In the Dodge Dakotalicense A357608 the fire extinguisher had not been inspected since 2010  The USDA-NRCS was previously cited for a violation of this Occupational Safety and Health standard or its equivalent standard 29CFR 1910.157(e)(3) which was contained in OSHA inspection number 1182315 Notice 1, Item 3 and was affirmed as a final order on 11/17/2016 with respect to a workplace located at 1918 Greene St., Adel, IA 5003
Recent events (1)
  • — Z (R) $0

1910.157 F02

Repeat Gravity 5 3 instances 4 exposed
Issued
Sep 8, 2017
Abate by
Sep 29, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.157(f)(2): Portable fire extinguishers were not hydrostatically tested within the intervals specified in Table L1:  (a) In the mail room the un-mounted General TGP10E fire extinguisher was last noted as inspected in 2002.  Hydrostatic testing or replacement  was therefore not performed in 2015 or sooner.  (b) In the breakroom the un-mounted General Halon 1211 fire extinguisher was last noted as inspected in 1991.  Hydrostatic testing or replacement was therefore not performed in 2003 or sooner.  (c) In the Chevrolet Silverado license A373158 the Badger fire extinguisher had not been tested since 2004.  Hydrostatic testing or replacement was therefore not performed in 2016 or sooner.   The Department of Agriculture-NRCS was previously cited for a violation of this occupational safety and health standard or similar standard 29CFR 1910.157(f)(2) which was contained in OSHA inspection number 1182315 Notice 1, Item 4 and was affirmed as a final order on 11/17/2016 with respect to a workplace located at 1918 Greene St., Suite 2, Adel, IA
Recent events (1)
  • — Z (R) $0

View Dept of Agriculture-Nrcs's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342519758.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.