Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: GRANDLAND GROUP (CNMI) LTD.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of GRANDLAND GROUP (CNMI) LTD. in IMPERIAL PACIFIC RESORT HOTEL SAIPAN, SAIPAN, MP 96950 (NAICS 236220). OSHA activity number 342534880.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Grandland Group (Cnmi) LTD. for free Get an email when a new federal OSHA severe-injury report for Grandland Group (Cnmi) LTD. is published. One employer, no account, unsubscribe in one click.
Site address
IMPERIAL PACIFIC RESORT HOTEL SAIPAN
City
SAIPAN
State
MP
ZIP
96950
Mailing
PMB 705 P.O. BOX 10000, SAIPAN, MP 96950
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
110
Ownership type
A

6 citations on file for this inspection.

1926.25 A

Serious Gravity 1 1 instance 6 exposed
Issued
Jan 3, 2018
Abate by
Jan 11, 2018
Penalty
Initial $4,155 · Current $2,909 Reduced
29 CFR 1926.25(a): During the course of construction, alteration, or repairs, form and scrap lumber with protruding nails, and all other debris, were not kept cleared from work areas, passageways, and stairs, in and around buildings or other structures.  At the loading dock area, lumber with nails sticking out and other debris was in the walkway. Employees were exposed to puncture tripping hazards.
Recent events (2)
  • · I (S) $2908.5
  • · Z (S) $4155

1926.701 B

Serious Gravity 1 1 instance 6 exposed
Issued
Jan 3, 2018
Abate by
Jan 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.701(b): Protruding reinforcing steel, onto and into which employees could fall was not guarded to eliminate the hazard of impalement.   Outside the hotel near the walkways, reinforcing steel rebar was not covered.  Employees were exposed to impalement hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1926.350 A10

Serious Gravity 1 1 instance 6 exposed
Issued
Jan 3, 2018
Abate by
Jan 11, 2018
Penalty
Initial $4,155 · Current $2,909 Reduced
29 CFR 1926.350(a)(10): Oxygen cylinders in storage were not separated from fuel-gas cylinder or combustible materials (especially oil or grease), a minimum distance of 20 feet or by a noncombustible barrier at least 5 feet high having a fire-resistance rating of at least one-half hour.  Next to the blue shipping container, unsecured oxygen and acetylene gas cylinders were stored together. Employees were exposed to fire and struck-by hazards.
Recent events (2)
  • · I (S) $2908.5
  • · Z (S) $4155

1926.350 A11

Serious Gravity 5 1 instance 6 exposed
Issued
Jan 3, 2018
Abate by
Jan 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.350(a)(11): Cylinders were not stored in definitely assigned storage places where  the cylinders would not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons.  Next to the blue shipping container, oxygen and acetylene gas cylinders were not secured to prevent from being knocked over. Employees were exposed to struck-by hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1926.405 G02 IV

Other-than-serious 1 instance 6 exposed
Issued
Jan 3, 2018
Abate by
Jan 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws.  At the temporary power panel, flexible cords with the plugs separating from the outer insulation were powering electrical equipment.  Employees were exposed to electrical and fire hazards.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1926.416 E01

Other-than-serious 1 instance 6 exposed
Issued
Jan 3, 2018
Abate by
Jan 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables were used.  Outside the hotel, a flexible cord with torn outer insulation was used to power a pipe cutter.  Employees were exposed to electrical and fire hazards.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342534880.