OSHA Inspection: MAR-JAC POULTRY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MAR-JAC POULTRY in 1301 JAMES STREET, HATTIESBURG, MS 39401 (NAICS 311615). OSHA activity number 342540663.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mar-Jac Poultry — free Get an email when a new federal OSHA severe-injury report for Mar-Jac Poultry is published. One employer, no account, unsubscribe in one click.
Establishment
MAR-JAC POULTRY
Site address
1301 JAMES STREET
City
HATTIESBURG
State
MS
ZIP
39401
Mailing
P. O. BOX 991, HATTIESBURG, MS 39403
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311615
Employees
1093
Ownership type
A

4 citations on file for this inspection.

1910.119 D03 II

Deleted Serious Gravity 5 1 instance 1093 exposed
Issued
Jan 18, 2018
Abate by
Feb 9, 2018
Penalty
Initial $11,086 · Current $0 Reduced
29 CFR 1910.119(d)(3)(ii): The employer shall document that equipment complies with recognized and generally accepted good engineering practices.  a) On or about August 9, 2017 the Red Water Chiller unit was not provided with a safety system or alarm to detect the release of ammonia. The employer failed to use recognized and generally accepted good engineering practice (RAGAGEP) such as IIAR.  A leak detection sensor, or the inlet of a sampling tube that draws air to a leak detection sensor, shall be mounted in a position where ammonia from a leak is expected to accumulate.
Recent events (2)
  • — I (S) $0
  • — Z (S) $11086

1910.120 Q02 VI

Serious Gravity 5 1 instance 40 exposed
Issued
Jan 18, 2018
Abate by
Jan 22, 2018
Penalty
Initial $11,086 · Current $7,000 Reduced
29 CFR 1910.120(q)(2)(vi): Evacuation routes and procedures.      a) On or about August 9, 2017 the employees turn stile gate was not free of obstructions and failure to have a plan that included evacuation routes and procedures that prevented a turn stile in the evacuation route from being locked.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $11086

1910.119 J04 II

Deleted Serious Gravity 5 1 instance 40 exposed
Issued
Jan 18, 2018
Abate by
Feb 9, 2018
Penalty
Initial $11,086 · Current $0 Reduced
29 CFR 1910.119(j)(4)(ii): Inspection and testing procedures shall follow recognized and generally accepted good engineering practices.  a) On or about August 9, 2017 employer did not inspect the back pressure regulator valve rated at 150 psi to be functional due to an electrical problem in which the valve was not connected resulting into the release of ammonia at the water chiller unit.    .
Recent events (2)
  • — I (S) $0
  • — Z (S) $11086

1910.119 J04 IV

Deleted Serious Gravity 5 1 instance 40 exposed
Issued
Jan 18, 2018
Abate by
Feb 9, 2018
Penalty
Initial $11,086 · Current $0 Reduced
29 CFR 1910.119(j)(4)(iv): The employer shall document each inspection and test that has been performed on process equipment. The documentation shall identify the date of the inspection or test, the name of the person who performed the inspection or test, the serial number or other identifier of the equipment on which the inspection or test was performed, a description of the inspection or test performed, and the results of the inspection or test.   a) On or about August 9, 2017 the back pressure regulator valve rated at 150 psi was not inspected or tested to be  functional due to an electrical problem in which the valve was not connected resulting into the release of ammonia at the water chiller unit.
Recent events (2)
  • — I (S) $0
  • — Z (S) $11086

View Mar-Jac Poultry's full OSHA safety record →