PORTSMOUTH, VA ·
OSHA Inspection: NORFOLK NAVAL SHIPYARD
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of NORFOLK NAVAL SHIPYARD in CODE 106, PORTSMOUTH, VA 23709 (NAICS 336611). OSHA activity number 342547445.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NORFOLK NAVAL SHIPYARD
- Site address
- CODE 106
- City
- PORTSMOUTH
- State
- VA
- ZIP
- 23709
- Mailing
- CODE 106, PORTSMOUTH, VA 23709
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336611
- Employees
- 100
- Ownership type
- Federal government (D)
Citations
7 citations on file for this inspection.
1910.101 B
- Issued
- Oct 27, 2017
- Abate by
- Nov 24, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): Section 3.2.1, Compressed Gas Association pamphlet P-1-1965, as adopted by 29 CFR 1910.101(b): Where removable caps are provided for valve protection, such caps were not kept on cylinders in storage: a) Building 1575, Warehouse section: On or about 08/10/2017, nitrogen gas cylinders not in use were stored without valve protection caps. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
- · Z (S) $0
1910.303 B02
- Issued
- Oct 27, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Building 276: On or about 08/09/2017, the yellow extension cords used to supply power to various appliances and a chop saw were not used in accordance with the listing and labeling in that one extension cord was plugged into another, thus exposing an employee to possible injuries. No abatement certification or documentation required.
Recent events (1)
- · Z (S) $0
1910.304 B03 II A
- Issued
- Oct 27, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(3)(ii)(A): All 125-volt, single-phase, 15, 20 and 30-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and that are in use by personnel did not have ground-fault circuit-interrupter protection for personnel. a) Building 276: On or about 08/09/2017, an employee was not provided with a ground fault interrupter device for the two yellow 25-foot extension cords connected together and used to supply temporary power to various appliances and a chop saw. No abatement certification or documentation required.
Recent events (1)
- · Z (S) $0
1910.305 A02 II
- Issued
- Oct 27, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(ii): Temporary wiring was not removed immediately upon completion of the project or purpose for which the wiring was installed: a) Building 276: On or about 08/09/2017, the yellow extension cord used to supply temporary power to various appliances and a chop saw was not immediately removed upon completion of use. No abatement certification or documentation required.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV B
- Issued
- Oct 27, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors: a) Building 276, Code 308: On or about 08/09/2017, a yellow extension cord used to supply temporary power to appliances in the shop was run through a hole made in the wall. No abatement certification or documentation required.
Recent events (1)
- · Z (S) $0
1910.157 E02
- Issued
- Oct 27, 2017
- Abate by
- Nov 24, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: a) Building 276, Code 2380: On or about 08/09/2017, a monthly inspection was not provided for the ABC type fire extinguisher mounted outside of the space. The last inspection according to the tag was in year 2011. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
- · Z (O) $0
1910.303 B07
- Issued
- Oct 27, 2017
- Abate by
- Nov 24, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7): Electric equipment was not installed in a neat and workmanlike manner: a) Building 1575, Workbench: On or about 08/11/2017, the duplex receptacle was not installed in a neat and workmanlike manner in that the wrong screw was used to secure the receptacle to the cover plate and caused the receptacle to push away from the cover. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
- · Z (O) $0
More inspections at Norfolk Naval Shipyard
View Norfolk Naval Shipyard's full OSHA safety record →
More inspections in this industry (NAICS 336611)
More inspections in VA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 342547445.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.