Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WARREN DESIGN & BUILD, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of WARREN DESIGN & BUILD, LLC in 2401 PARKMAN RD. NW, WARREN, OH 44485 (NAICS 541330). OSHA activity number 342635091.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Warren Design & Build, LLC — free Get an email when a new federal OSHA severe-injury report for Warren Design & Build, LLC is published. One employer, no account, unsubscribe in one click.
Site address
2401 PARKMAN RD. NW
City
WARREN
State
OH
ZIP
44485
Mailing
2401 PARKMAN RD. NW, WARREN, OH 44485
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541330
Employees
14
Ownership type
A

16 citations on file for this inspection.

1910.36 D01

Serious Gravity 1 1 instance 14 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $2,173 · Current $869 Reduced
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:    On or about September 13, 2017, on the north side of the milling department there was a north exit discharge door that was locked and could not be opened from the inside without a key.
Recent events (3)
  • — F (S) $869.2
  • — C (S) $2173
  • — Z (S) $2173

1910.37 B02

Serious Gravity 1 1 instance 14 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $2,173 · Current $869 Reduced
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":    On or about September 13, 2017, the milling department north exit discharge door was not marked as an exit.
Recent events (3)
  • — F (S) $869.2
  • — C (S) $2173
  • — Z (S) $2173

1910.37 B05

Serious Gravity 1 1 instance 4 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):    On or about September 13, 2017, in the milling department there was a closed door to the compressor room that was not marked as "not an exit".
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.147 C01

Serious Gravity 5 1 instance 6 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $3,622 · Current $1,449 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:     On or about September 13, 2017, the employer did not have a lockout/tagout program for servicing and maintaining machinery such as but not limited to vertical milling machines and horizontal lathes.
Recent events (3)
  • — F (S) $1448.8
  • — C (S) $3622
  • — Z (S) $3622

1910.157 E02

Serious Gravity 5 1 instance 14 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $2,897 · Current $1,159 Reduced
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:    On or about September 13, 2017, the employer did not ensure portable fire extinguishers were being visually inspected monthly.
Recent events (3)
  • — F (S) $1158.8
  • — C (S) $2897
  • — Z (S) $2897

1910.157 E03

Serious Gravity 5 2 instances 14 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): The date of the annual maintenance check of portable fire extinguishers was not recorded:    On or about September 13, 2017, the employer did not ensure portable fire extinguishers received an annual maintenance check.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.157 G01

Serious Gravity 5 1 instance 14 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting:     On or about September 13, 2017, the employer did not provide employees with portable fire extinguisher training.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.178 L01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $2,897 · Current $1,159 Reduced
29 CFR 1910.178(l)(1)(i): The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l):    On or about September 13, 2017, the employer did not ensure that employees who operate forklifts receive information training and skill evaluation.
Recent events (3)
  • — F (S) $1158.8
  • — C (S) $2897
  • — Z (S) $2897

1910.212 A01

Serious Gravity 5 17 instances 7 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $3,622 · Current $1,449 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    On or about September 13, 2017, the following machinery was not safe guarded for rotating parts, flying chips and sparks, and/or point of operation.    a. There were three drill presses (Tristar, Industrial and Delta) that were not guarded at the rotating chucks.    b. There were two lathes (Harrison and Tarnow) that were not guarded at the rotating chucks.     c. There was a Dake horizontal bandsaw that had 13 inches of the unused portion of the blade that was not guarded.    d. There was a DoAll vertical bandsaw that had 3 inches of the unused portion of the saw blade that was not  guarded above and below the work table.    e. There were eight Bridgeport milling machines that were not guarded at the rotating chucks.    f. There was an Accugrid surface grinder with the guard displaced.    g. There was an Allsteel press brake that was not guarded at the point of operation of the dies.
Recent events (3)
  • — F (S) $1448.8
  • — C (S) $3622
  • — Z (S) $3622

1910.215 A04

Serious Gravity 5 1 instance 7 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $2,897 · Current $1,159 Reduced
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:     On or about September 13, 2017, the Baldor abrasion wheel pedestal grinder had a 5/16 inch opening at the work rest.
Recent events (3)
  • — F (S) $1158.8
  • — C (S) $2897
  • — Z (S) $2897

1910.215 B09

Serious Gravity 5 2 instances 7 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:     On or about September 13, 2017, the Baldor abrasive wheel pedestal grinder periphery guards were open 3/4 and 1 inch.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.242 B

Serious Gravity 5 3 instances 7 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $2,897 · Current $1,159 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:     On or about September 13, 2017, employees were using compressed air for cleaning that was at 70psi.
Recent events (3)
  • — F (S) $1158.8
  • — C (S) $2897
  • — Z (S) $2897

1910.303 B02

Serious Gravity 5 3 instances 4 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $2,897 · Current $1,159 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:     On or about September 13, 2017, the following electrical equipment was not used in accordance with instructions included in the listing or labeling.    a. There was a commercial grade multi-tap strip attached to an industrial fan at the paint booth.    b. There were flexible cords attached to two separate electrical junction knockout boxes used for receptacles that were not secured.     NOTE: Knockout boxes were designed to be secured to a fixed/permanent structure. When knockout boxes are used on the ends of flexible cords, employees gripping the box to attach or disconnect a plug may dislodge the circular scored metal portion in the box wall causing it to come in contact with the hot terminal. The result may lead to an electric shock.
Recent events (3)
  • — F (S) $1158.8
  • — C (S) $2897
  • — Z (S) $2897

1910.303 G02 I

Serious Gravity 5 2 instances 7 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $2,897 · Current $1,159 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures:     On or about September 13, 2017, the following electrical wiring was live and not encased in an approved enclosure.     a. There was live 480 volt flexible cord/electrical wiring taped to a cylindrical structural column near the grinding station.    b. There was live 480 volt flexible cord/electrical wiring hanging at the front side of the metal paint booth.
Recent events (3)
  • — F (S) $1158.8
  • — C (S) $2897
  • — Z (S) $2897

1910.305 B01 I

Serious Gravity 1 2 instances 7 exposed
Issued
Oct 30, 2017
Abate by
May 2, 2018
Penalty
Initial $2,173 · Current $869 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:    On or about September 13, 2017, the following flexible cord/electrical wiring conductors were not protected from abrasion.    a. In the electrical assembly area there was an unprotected flexible cord/electrical wire feed fitting at the side of the 480 volt disconnect switch.     b. In the welding/grinding area there was an unprotected flexible cord/electrical wire feed at the top of the 480 volt disconnect switch.
Recent events (3)
  • — F (S) $869.2
  • — C (S) $2173
  • — Z (S) $2173

1910.305 B02 I

Serious Gravity 5 1 instance 6 exposed
Issued
Oct 30, 2017
Penalty
Initial $3,622 · Current $1,449 Reduced
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:     On or about September 13, 2017, on the north wall in the milling department there was an electrical disconnect switch above the workbench by the compressor room door. The disconnect switch cover was open and the internal conductors were exposed.
Recent events (3)
  • — F (S) $1448.8
  • — C (S) $3622
  • — Z (S) $3622

View Warren Design & Build, LLC's full OSHA safety record →