Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. DEPARTMENT OF THE INTERIOR

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of U.S. DEPARTMENT OF THE INTERIOR in FORT SUMTER CHARLESTON HARBOR, CHARLESTON, SC 29401 (NAICS 712120). OSHA activity number 342685377.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of the Interior — free Get an email when a new federal OSHA severe-injury report for U.S. Department of the Interior is published. One employer, no account, unsubscribe in one click.
Site address
FORT SUMTER CHARLESTON HARBOR
City
CHARLESTON
State
SC
ZIP
29401
Mailing
1214 MIDDLE STREET, SULLIVANS ISLAND, SC 29482
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
712120
Employees
37
Ownership type
D

2 citations on file for this inspection.

1910.303 B07

Serious Gravity 1 1 instance 6 exposed
Issued
Jan 10, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7): 29 CFR 1910.303(b)(7):  Electrical equipment was not installed in a neat and workmanlike manner:  a) Elevated concrete walkway between the docking berth and Fort Sumter: A 240 volt electrical panel box located over land on the Southwest side was not firmly attached to the metal support frame and was dangling from the frame due to being held in place with a plastic tie. It was also listing to the point of making physical contact with an adjacent electrical panel box.
Recent events (1)
  • — Z (S) $0

1910.305 B01

Serious Gravity 1 1 instance 6 exposed
Issued
Jan 10, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1): Openings through which conductors enter boxes, cabinets, or fittings were not effectively closed.  a) Elevated concrete walkway between the docking berth and Fort Sumter: A 240 volt electrical panel box located over land on the Southwest side had a 1 inch opening on the south side of the box in which a "dead" plug and insulated conductors passed through, was not closed allowing the elements to enter the box.