VINELAND, NJ —
OSHA Inspection: BRIDOR USA, INC.
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of BRIDOR USA, INC. in 2260 INDUSTRIAL WAY, VINELAND, NJ 08360 (NAICS 311812). OSHA activity number 342691144.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BRIDOR USA, INC.
- Site address
- 2260 INDUSTRIAL WAY
- City
- VINELAND
- State
- NJ
- ZIP
- 08360
- Mailing
- 2260 INDUSTRIAL WAY, VINELAND, NJ 08360
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311812
- Employees
- 320
- Ownership type
- A
Citations
30 citations on file for this inspection.
1910.36 D01
- Issued
- Apr 6, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $9,239 · Current $6,566 Reduced
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: a) GEA/FES engine room, Bay Door #13: The exit leading to the outside of the facility contained a pad lock, door latch and a folding security gate with a lock and key, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (2)
- — I (S) $6566
- — Z (S) $9239
1910.37 A03
- Issued
- Apr 6, 2018
- Abate by
- Aug 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit routes must be free and unobstructed. No materials or equipment may be placed, either permanently or temporarily, within the exit route. The exit access must not go through a room that can be locked, such as a bathroom, to reach an exit or exit discharge, nor may it lead into a dead-end corridor. Stairs or a ramp must be provided where the exit route is not substantially level. a) GEA/FES engine room, Bay Door #13, Door Labeled as an Exit: The exit leading to the outside of the facility contained a locked folding security gate which blocked the egress from the facility, on or about 10/10/2017. b) Roof: Exit routes were obstructed by pipe chases located in the attic. Employees had to travel under pipe chases and crossbeams which were located in the path of travel to the exit. There was no clear path of travel to the exit door, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (3)
- — P (S) $0
- — I (S) $0
- — Z (S) $0
1910.36 E02
- Issued
- Apr 6, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $9,239 · Current $6,562 Reduced
General-duty citation text
29 CFR 1910.36(e)(2): The door(s) that connected any room to an exit route did not swing out in the direction of exit travel when the room was designed to be occupied by more than 50 people or when the room was a high hazard area. b) GEA/FES ammonia refrigeration engine room: The exit doors leading from the engine room to the boiler room did not open toward the direction of exit travel, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (5)
- — P (S) $6562
- — P (S) $6562
- — P (S) $6562
1910.119 D03 II
- Issued
- Apr 6, 2018
- Abate by
- Oct 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complied with recognized and generally accepted good engineering practices: a) Boiler room next to ammonia refrigeration engine rooms: The employer failed to document that the rooms immediately outside of the engine room complied with RAGAGEP, such as, but not limited to, IIAR 2 2014 section 6.7. An eyewash station capable of providing 15 minutes of continuous flushing and a safety shower were not provided in the boiler room outside of the GEA/FES ammonia refrigeration room, on or about 10/10/17. b) GEA/FES ammonia refrigeration engine room: The employer failed to document that the exit doors leading from the engine room to the maintenance shop complied with RAGAGEP, such as, but not limited to, IIAR 2 2014 section 6.10.2. The doors were not equipped with panic bar hardware and did not open in the direction of travel, on or about 10/10/17. c) GEA/FES ammonia refrigeration engine room: The employer failed to document that the exit doors leading from the engine room to the boiler room complied with RAGAGEP, such as, but not limited to, IIAR 2 2014 section 6.10.2. The doors were not equipped with panic bar hardware and did not open in the direction of travel, on or about 10/10/17. d) GEA/FES ammonia refrigeration engine room: The employer failed to document that the exit doors leading from the control room to the emergency exits complied with RAGAGEP, such as, but not limited to, IIAR 2 2014 section 6.10.2. The doors were not equipped with panic bar hardware and did not open in the direction of travel, on or about 10/10/17. f) Access platform for the VK-1 Evaporative Condenser: The employer failed to document that the configuration of the discharge header located next to the access platform complied with RAGAGEP such as, but not limited to IIAR-2 2014 15.5.1.5. The termination of the discharge was t-shaped and in the event of a release from the pressure relief discharge, ammonia would be directed horizontally rather than vertically above the access platform potentially exposing employees, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (4)
- — P (S) $0
- — P (S) $0
- — I (S) $0
1910.151 C
- Issued
- Apr 6, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) Boiler Room: An eye wash/drenching station providing at least 15 minutes of a continuous flow was not provided where employees handle corrosive products including but not limited to Polyplex 205-F and Formula 2206-A, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 A02
- Issued
- Apr 6, 2018
- Abate by
- Aug 30, 2018
- Penalty
- Initial $9,239 · Current $6,562 Reduced
General-duty citation text
29 CFR 1910.37(a)(2): Exit routes were not arranged so that employees would not have to travel toward a high hazard area, nor was the hazard effectively shielded by suitable partitions or barriers: a) Roof: The exit routes from the roof lead back into the building. There was no way to exit the roof except to go back into the facility, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (3)
- — P (S) $6562
- — I (S) $6562
- — Z (S) $9239
1910.119 E03 V
- Issued
- Apr 6, 2018
- Abate by
- May 2, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(e)(3)(v): The PHA did not address facility siting: a) GEA/FES and Frick ammonia refrigeration systems: The PHA was inadequate in addressing facility siting hazards. The PHA did not address a means of egress from the roof for employees conducting maintenance. In the event of an emergency, employees would have to re-enter the building, potentially through a hazardous area, in order to evacuate from the roof, on or about 10/11/2016. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 D03 I D
- Issued
- Apr 6, 2018
- Abate by
- Oct 30, 2018
- Penalty
- Initial $9,239 · Current $6,562 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(D): Information pertaining to equipment in the process did not include relief system design and design basis: a) GEA/FES ammonia refrigeration system: The employer's process safety information did not include the design basis for relief systems, such as, but not limited to, PRV-W1-21, on the high pressure receiver VV1, on or about 10/11/16. b) GEA/FES ammonia refrigeration system: The employer's process safety information did not include the design basis for relief systems, such as, but not limited to, PRV-W1-22, on the high pressure receiver VV1, on or about 10/11/16. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (4)
- — P (S) $6562
- — P (S) $6562
- — I (S) $6562
1910.119 D03 I H
- Issued
- Apr 6, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $9,239 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(H): Process safety information pertaining to the equipment in the process did not include the safety systems (e.g., interlocks, detection or suppression systems): a) GEA/FES ammonia refrigeration system: The employer's process safety information did not include the design information for the hot gas defrost interlocks on equipment such as, but not limited to, spiral air unit coolers LK-18 and LK-19, on or about 10/10/17. b) GEA/FES and Frick ammonia refrigeration systems: The employer's process safety information did not include the design information for the emergency stop buttons, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (5)
- — P (S) $0
- — P (S) $0
- — P (S) $0
1910.119 E03 III
- Issued
- Apr 6, 2018
- Abate by
- May 2, 2018
- Penalty
- Initial $9,239 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(e)(3)(iii) The process hazard analysis did not address engineering and administrative controls applicable to the hazards: a) GEA/FES and Frick ammonia refrigeration systems: The process hazard analysis failed to address how operators working on the roof will be notified of an emergency condition when there was inadequate reception for the wireless phones provided for communication and no alarm system on the roof, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $0
- — Z (S) $9239
1910.120 Q02 IX
- Issued
- Apr 6, 2018
- Abate by
- Aug 30, 2018
- Penalty
- Initial $0 · Current $6,562
General-duty citation text
29 CFR 1910.120(q)(2)(ix): The emergency response plan did not address, to the extent not addressed elsewhere, emergency alerting and response procedures: a) GEA/FES and Frick ammonia refrigeration systems: Employees working as ammonia refrigeration system operators are required to respond to ammonia releases at the facility. The employers emergency response plan did not address response procedures such as, but not limited to, the required action needed based on the extent and location of a release, on or about 10/10/2017. b) GEA/FES and Frick ammonia refrigeration systems: The employer's emergency response plan failed to address how operators working on the roof would be alerted to an emergency condition. The employer relied on a WIFI phones to alert employees of an emergency situation, however, a WIFI signal was not available at all locations where employees would be working, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
- — P (S) $6562
- — I (S) $6562
- — Z (S) $0
1910.165 B02
- Issued
- Apr 6, 2018
- Abate by
- Oct 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.165(b)(2): The employee alarm could not be perceived above ambient noise or light levels by all employees in the affected portions of the workplace: a) Roof: The employer failed to provide a means to alert employees, working on the roof of the facility, of an ammonia release or a fire within the facility. The alarms within the facility cannot be heard by employees working on the roof. Employees were provided with WIFI phones but there was limited WIFI signal on the roof, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (4)
- — P (S) $0
- — P (S) $0
- — I (S) $0
1910.119 E03 VI
- Issued
- Apr 6, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $9,239 · Current $6,562 Reduced
General-duty citation text
29 CFR 1910.119(e)(3)(vi) The process hazard analysis did not address human factors: a) GEA/FES and Frick ammonia refrigeration systems: The employer's PHA failed to address human factors such as, but not limited to, use of an inadequate standard operating procedure when using a propane torch or kerosene heater to melt ice. The standard operating procedure, Ice Melting With A Propane Presto Lite Torch or Turbo Heater, did not include instructions to prevent hydrostatic expansion, on or about 10/10/17. b) Frick ammonia refrigeration system: The employer's PHA failed to address human factors such as the use of inadequate standard operating procedures (SOPs). RESOP-28 Operation of Air Unit EV3 Yeast Cooler did not list the consequences of deviation and the steps to avoid deviation, on or about 10/10/17. d) GEA/FES ammonia refrigeration system: The employer's PHA failed to address human factors such as the use of inadequate standard operating procedures (SOPs). OPS-01 Operation of C1, C2 or C3 FES Ammonia Compressors did not include the personal protective equipment required when conducting certain tasks and the properties and hazards of ammonia, on or about 10/10/17. e) GEA/FES ammonia refrigeration system: The employer's PHA failed to address human factors such as the use of inadequate standard operating procedures (SOPs). OPS-10A Startup, Shutdown and Operation of Spiral Air Units LK 18 and LK 19 did not include when emergency shutdown was required, personnel authorized to conduct emergency shutdowns, the consequences of deviation and the steps to avoid deviation, personal protective equipment required for certain tasks, safety systems and their functions and the properties and hazards of ammonia, on or about 10/10/17. f) GEA/FES ammonia refrigeration system: The employer's PHA failed to address human factors such as the use of inadequate standard operating procedures (SOPs). OPS-04 Operation of Low Pressure Receives VA1 and VA2 did not include when emergency shutdown was required, personnel authorized to conduct emergency shutdowns, personal protective equipment required for certain tasks and the properties and hazards of ammonia, on or about 10/10/17. g) Frick ammonia refrigeration system: The employer's PHA failed to address human factors such as, but not limited to, an evaluation of the access control procedures for the line 5 spiral freezer computer. In November 2017 a production supervisor was able to access the computer and initiate the hot gas defrost cycle for one of the four evaporators while another unit was in already in a defrost cycle resulting in a surge of ammonia back to the LTPR-2 that caused the compressors to freeze, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (5)
- — P (S) $6562
- — P (S) $6562
- — P (S) $6562
1910.119 F01
- Issued
- Apr 6, 2018
- Abate by
- Oct 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(f)(1): The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information and addressing at least steps for each operating phase, safe operating limits, safety and health considerations, and safety systems and their functions as outlined by this paragraph: a) Frick ammonia refrigeration system: The employer failed to develop a written operating procedure for the operation of the intercooler, IC-1, that included information such as, but not limited to, safe operating limits, initial start up, normal operations and shutdown, temporary operations, emergency operations and shutdown, oil pot draining, consequences of deviation, steps to avoid deviation and safety and health considerations, on or about 10/10/17. b) Frick ammonia refrigeration system: The employer failed to develop a written operating procedure for the operation of the -45F low temperature pump recirculator, LTPR-2, that included information such as, but not limited to, safe operating limits, initial start up, normal operations and shutdown, temporary operations, emergency operations and shutdown, oil pot draining, consequences of deviation, steps to avoid deviation and safety and health considerations, on or about 10/10/17. c) Frick ammonia refrigeration system: The employer failed to develop a written operating procedure for the operation of the -20F low temperature pump recirculator, LTPR-1, that included information such as, but not limited to, safe operating limits, initial start up, normal operations and shutdown, temporary operations, emergency operations and shutdown, oil pot draining, consequences of deviation, steps to avoid deviation and safety and health considerations, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (4)
- — P (S) $0
- — P (S) $0
- — I (S) $0
1910.119 F01 I C
- Issued
- Apr 6, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CR 1910.119(f)(1)(i)(C) The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information and did not address temporary operations: a) Frick ammonia refrigeration system: The employer failed to develop and implement temporary operating procedures within RESOP 17-20 on how to safely place the evaporators in the spiral freezer into hot gas defrost, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 F01 I D
- Issued
- Apr 6, 2018
- Abate by
- Oct 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(f)(1)(i)(D): The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information that addressed emergency shutdown including the conditions under which emergency shutdown was required, and the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown was executed in a safe and timely manner: a) GEA/FES ammonia refrigeration system: The SOP for LK 18 and LK19 spiral air units, OPS-10A, did not list the conditions requiring emergency shutdown and the identity of the operating engineers to execute the shutdown, on or about 10/10/17. b) GEA/FES ammonia refrigeration system: The SOP for Receivers VA1 and VA2, OPS-04, did not list the conditions requiring emergency shutdown and the identity of the operating engineers to execute the shutdown, on or about 10/10/17. c) GEA/FES ammonia refrigeration system: The SOP for compressor C1, OPS-01, did not identify the operating engineers to execute emergency shutdown, on or about 10/10/17 NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (4)
- — P (S) $0
- — P (S) $0
- — I (S) $0
1910.119 F01 II A
- Issued
- Apr 6, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CR 1910.119(f)(1)(ii)(A) The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information that addressed consequences of deviation: a) Frick ammonia refrigeration system: The SOPs for the spiral freezer (SP-1) coils, RESOP 17-20, did not discuss the consequences of deviation for the hot gas defrost cycle, such as, but not limited to, initiating the hot gas defrost cycle on a spiral freezer coil while another was already in a defrost cycle, on or about 10/10/2017. b) GEA/FES ammonia refrigeration system: The SOP for LK 18 and LK19 spiral air units, OPS-10A, did not discuss the consequences of deviation, such as, but not limited to, insufficient removal of ammonia from the coils when removing the units from service and removal of air from the units when returning to service after being opened to atmosphere, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (5)
- — P (S) $0
- — P (S) $0
- — P (S) $0
1910.119 F01 II B
- Issued
- Apr 6, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(f)(1)(ii)(B): The employer's written operating procedures covering operating limits did not address the steps required to correct or avoid deviation: a) Frick ammonia refrigeration system: The SOPs for the spiral freezer (SP-1) coils, RESOP 17-20, did not discuss the steps to correct or avoid the consequences of deviation for the hot gas defrost cycle, overpressurization of the refrigeration system or high condensing pressures, on or about 10/10/2017. b) GEA/FES ammonia refrigeration system: The SOP for LK 18 and LK19 spiral air units, OPS-10A, did not discuss the steps to correct or avoid the consequences of deviation, such as, but not limited to, insufficient removal of ammonia from the coils when removing the units from service and removal of air from the units when returning to service after being opened to atmosphere, on or about 10/10/17. c) Frick ammonia refrigeration system: The SOP for Air Unit EV-3 Yeast Cooler, RESOP 28, did not discuss the steps to correct or avoid the consequences of deviation, such as, but not limited to, overpressurization of the refrigeration system or high condensing pressures, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (5)
- — P (S) $0
- — P (S) $0
- — P (S) $0
1910.119 F01 III A
- Issued
- Apr 6, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119 (f)(1)(iii)(A) The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information including the properties of, and hazards presented by, the chemicals used in the process: a) GEA/FES ammonia refrigeration systems: The SOP OPS-04, Operation of Low Pressure Receivers VA1 and VA2, did not list the properties and hazards of ammonia, on or about 10/10/17. b) GEA/FES ammonia refrigeration system: The SOP OPS-10A LK 18 and LK19 spiral air units, did not list the properties and hazards of ammonia, on or about 10/10/17. c) GEA/FES ammonia refrigeration systems: The SOP OPS-01, Operation of C1, C2 or C3 FES Ammonia Compressors, did not list the properties and hazards of ammonia, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 F01 III B
- Issued
- Apr 6, 2018
- Abate by
- Oct 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119 (f)(1)(iii)(B) The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information that addressed health and safety considerations, such as precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment. a) GEA/FES and Frick ammonia refrigeration systems: The SOP, Ice Melting With A Propane Presto Lite Torch or Turbo Heater did not list the precautions necessary to prevent exposure to ammonia due to hydrostatic expansion, on or about 10/10/17. b) GEA/FES ammonia refrigeration systems: The SOP OPS-04, Operation of Low Pressure Receivers VA1 and VA2, did not list the specific type of personal protective equipment required when draining or transferring ammonia from the vessels or servicing the float column, on or about 10/10/17. c) GEA/FES ammonia refrigeration systems: The SOP OPS-01, Operation of C1, C2 or C3 FES Ammonia Compressors, did not list the specific type of personal protective equipment required when draining or transferring ammonia from the vessels or conducting line breaks, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (4)
- — P (S) $0
- — P (S) $0
- — I (S) $0
1910.119 F01 III C
- Issued
- Apr 6, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119 (f)(1)(iii)(C) The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information including control measures to be taken if physical contact or airborne exposure occured: a) GEA/FES ammonia refrigeration systems: The SOP OPS-04, Operation of Low Pressure Receivers VA1 and VA2, did not list the steps to be taken for physical contact or airborne exposure to ammonia, on or about 10/10/17. b) GEA/FES ammonia refrigeration system: The SOP for LK 18 and LK19 spiral air units, OPS-10A, did not list the steps to be taken for physical contact or airborne exposure to ammonia, on or about 10/10/17. c) GEA/FES ammonia refrigeration systems: The SOP OPS-01, Operation of C1, C2 or C3 FES Ammonia Compressors, did not list the steps to be taken for physical contact or airborne exposure to ammonia, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 F01 IV
- Issued
- Apr 6, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CR 1910.119(f)(1)(iv) The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information that addressed safety systems and their functions: a) GEA/FES ammonia refrigeration system: The SOP OPS-10A for LK 18 and LK19 spiral air units, did not discuss the safety systems, such as, but not limited to, temperature and pressure alarms and the hot gas interlocks, on or about 10/10/17. b) Frick ammonia refrigeration system: The SOPs RESOP 17-20 SP1 C1-4 Spiral Freezer Coils, did not discuss the safety systems, such as, but not limited to, the hot gas interlocks, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (5)
- — P (S) $0
- — P (S) $0
- — P (S) $0
1910.119 J02
- Issued
- Apr 6, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $9,239 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish written procedures to maintain the on-going integrity of process equipment: a) GEA/FES ammonia refrigeration system: The employer did not establish written procedures to maintain the on-going integrity of the safety interlocks for the hot gas defrost cycle on Spiral Air Unit Coolers LK 18 and LK 19, on or about 10/10/2017. b) Frick ammonia refrigeration system: The employer did not establish written procedures to maintain the on-going integrity of the safety interlocks for the hot gas defrost cycle on Spiral Freezer Coils SP1 C1-C4, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (5)
- — P (S) $0
- — P (S) $0
- — P (S) $0
1910.119 J04 I
- Issued
- Apr 6, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment a) GEA/FES ammonia refrigeration system: The employer did not perform inspections and tests on the safety interlocks for the hot gas defrost cycle on Spiral Air Unit Coolers LK 18 and LK 19, on or about 10/10/2017. b) Frick ammonia refrigeration system: The employer did not perform inspections and tests for the safety interlocks for the hot gas defrost cycle on Spiral Freezer Coils SP1 C1-C4, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (5)
- — P (S) $0
- — P (S) $0
- — P (S) $0
1910.120 F03 I B
- Issued
- Apr 6, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $9,239 · Current $6,562 Reduced
General-duty citation text
29 CFR 1910.120(f)(3)(i)(B): Medical examinations and consultations were not made available by the employer to each employee covered under 29 CFR 1910.120(f)(2)(i), (ii), and (iv) at least once every 12 months unless the attending physician believed a longer interval (not greater than biennially) was appropriate: a) GEA/FES and Frick ammonia refrigeration systems: Employees designated as hazardous material technicians were not provided medical exams at least once every 12 months, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $6562
- — Z (S) $9239
1910.120 Q02 XI
- Issued
- Apr 6, 2018
- Abate by
- Aug 30, 2018
- Penalty
- Initial $9,239 · Current $6,562 Reduced
General-duty citation text
29 CFR 1910.120(q)(2)(xi): The emergency response plan did not address, to the extent not addressed elsewhere, personal protective equipment and emergency equipment: a) GEA/FES and Frick ammonia refrigeration systems: The employer's emergency response plan did not address the required personal protective equipment when responding to an ammonia leak, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
- — P (S) $6562
- — I (S) $6562
- — Z (S) $9239
1910.120 Q08 I
- Issued
- Apr 6, 2018
- Abate by
- May 2, 2018
- Penalty
- Initial $9,239 · Current $0 Reduced
General-duty citation text
29 CFR 1910.120(q)(8)(i): Employees who were trained in accordance with 29 CFR 1910.120(q)(6) did not receive annual refresher training of sufficient content and duration to maintain their competencies or did not demonstrate competency in those areas at least yearly: a) GEA/FES and Frick ammonia refrigeration system: Ammonia mechanics designated as Hazardous Materials Technicians and required to respond, investigate and potentially stop ammonia leaks as much as feasibly possible, had not received the annual refresher training as required by the standard, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (S) $0
- — Z (S) $9239
1910.119 F03
- Issued
- Apr 6, 2018
- Abate by
- Oct 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(f)(3): The operating procedures were not reviewed as often as necessary to assure that they reflected current operating practice, including changes that resulted from changes in process chemicals, technology, and equipment, and changes to facilities: Operating procedures for the GEA/FES and Frick ammonia refrigeration systems, such as, but not limited to those listed below, were not reviewed and updated as necessary to reflect current operating conditions. a) GEA/FES ammonia refrigeration system: Operating procedure OPS-04 Operation of Low Pressure Receivers VA1 and VA2 incorrectly listed the operating pressure for VA1 as 0.5 to 5 PSIG, on or about 10/10/17. b) GEA/FES ammonia refrigeration system: Operating procedure OPS-04 Operation of Low Pressure Receivers VA1 and VA2 incorrectly listed the high liquid level operating limits for VA2 as 30% of the vessel diameter, on or about 10/10/17. d) GEA/FES ammonia refrigeration system: Operating procedure OPS-01 Operation of C1, C2 or C3 FES Ammonia Compressors incorrectly listed the minimum slide valve position for C1 as 10%, on or about 10/10/17. e) GEA/FES ammonia refrigeration system: Operating procedure OPS-01 Operation of C1, C2 or C3 FES Ammonia Compressors incorrectly listed the low suction temperature alarm for C1 as -28 F and the shutdown at -30F, on or about 10/10/17. f) GEA/FES ammonia refrigeration system: Operating procedure OPS-01 Operation of C1, C2 or C3 FES Ammonia Compressors incorrectly listed the high oil temperature alarm cutout for C1 as 150F, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (4)
- — P (O) $0
- — P (O) $0
- — I (O) $0
1910.119 H02 I
- Issued
- Apr 6, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(h)(2)(i) The employer, when selecting a contractor, did not obtain and evaluate information regarding the contract employer's safety performance and programs: a) GEA/FES and Frick ammonia refrigeration systems: The employer did not obtain injury and illness rates and safety programs for contractors conducting work on the ammonia refrigeration systems, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.119 H02 VI
- Issued
- Apr 6, 2018
- Abate by
- Jun 29, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(h)(2)(iv) The employer did not maintain a contract employee injury and illness log related to the contractor's work in process areas: a) GEA/FES and Frick ammonia refrigeration systems: The employer did not maintain a contractor employee injury and illness log for contractors on site performing work on the ammonia refrigeration systems, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Bridor USA, INC.
View Bridor USA, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 311812)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342691144.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.