SMYRNA, GA —
OSHA Inspection: K & H MAINTENANCE, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of K & H MAINTENANCE, INC. in 6000 HIGHLANDS PKWY SE, SMYRNA, GA 30082, SMYRNA, GA 30082 (NAICS 238210). OSHA activity number 342745015.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- K & H MAINTENANCE, INC.
- Site address
- 6000 HIGHLANDS PKWY SE, SMYRNA, GA 30082
- City
- SMYRNA
- State
- GA
- ZIP
- 30082
- Mailing
- 101 INDUSTRIAL DRIVE, ZEBULON, GA 30295
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 20
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.333 A01
- Issued
- Apr 26, 2018
- Penalty
- Initial $5,174 · Current $3,104 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): "Deenergized parts." Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs. a) Site, Switch Gear Trailers; On or about 10/27/2017, the employer exposed employees to shock hazards in that they were allowed to work directly on and within 18 inches of live exposed 480 Volt 2000 Amp bus bars.
Recent events (2)
- — I (S) $3104.4
- — Z (S) $5174
1910.335 A01 I
- Issued
- Apr 26, 2018
- Penalty
- Initial $5,174 · Current $3,104 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed. a) Site, Switch Gear Trailer; On or about 10/27/2017, the employer exposed employees to electric shock and arc blast hazards while working from the point of contact to 18 inches from live 480 volt, 2000 amp bus bars with either no personal protective gear worn or with only safety glasses and rubber boots being worn
Recent events (2)
- — I (S) $3104.4
- — Z (S) $5174
More inspections at K & H Maintenance, INC.
View K & H Maintenance, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in GA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342745015.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.