Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: INVISTA S.A.R.L

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of INVISTA S.A.R.L in 12455 STRANG ROAD, LA PORTE, TX 77571 (NAICS 325110). OSHA activity number 342793064.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Invista S.A.R.L — free Get an email when a new federal OSHA severe-injury report for Invista S.A.R.L is published. One employer, no account, unsubscribe in one click.
Establishment
INVISTA S.A.R.L
Site address
12455 STRANG ROAD
City
LA PORTE
State
TX
ZIP
77571
Mailing
4123 E 37TH STREET NORTH, WICHITA, KS 67220
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325110
Employees
100
Ownership type
A

5 citations on file for this inspection.

1910.119 F04

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Apr 4, 2018
Abate by
May 21, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.119(f)(4): The employer did not  implement safe work practices to provide for the control of hazards during operations. These safe work practices shall apply to employees and contractor employees.  On or about November 22, 2017, at Invista Plant in La Porte, Texas; the employer did not implement the Safe Work Permits procedure to issue and/or retain the work permit, including but not limited to the Blanking Lists, Job Safety Analysis (JSA) for the maintenance activities on Step II C Reactor.
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1910.119 F04

Serious Gravity 10 1 instance 4 exposed
Issued
Apr 4, 2018
Abate by
Oct 1, 2018
Penalty
Initial $12,934 · Current $12,934
29 CFR 1910.119(f)(4): The employer did not ensure that safe work practices to provide for the control of hazards were communicated during shift change operations.    On or about November 22, 2017, at the A&AT, LLC plant in La Porte, Texas, the employer did not ensure the MOC-LP-17-0198 to permit the Step 2 "C" Reactor to operate without the Feed Heater/Cooler (5007-7011-3100) was communicated between shifts.
Recent events (3)
  • — F (S) $12934
  • — C (S) $12934
  • — Z (S) $12934

1910.119 L03

Serious Gravity 10 1 instance 4 exposed
Issued
Apr 4, 2018
Abate by
May 21, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.119(l)(3): The employer did not ensure that maintenance employees were informed of and trained in a change prior to implementation.    On or about November 22, 2017, at A&AT, LLC Plant in La Porte, Texas; the employer did not ensure that maintenance personnel were informed of the changes brought about by MOC-LP-17-0198 to permit the Step 2 "C" Reactor to operate without the Feed Heater/Cooler (5007-7011-3100).
Recent events (3)
  • — F (S) $0
  • — C (S) $12934
  • — Z (S) $12934

1910.147 F04

Serious Gravity 10 1 instance 5 exposed
Issued
Apr 4, 2018
Abate by
Oct 1, 2018
Penalty
Initial $12,934 · Current $12,934
29 CFR 1910.147(f)(4): The employer did not ensure that the continuity of lockout or tagout protection, including provisions for the orderly transfer of lockout and tagout device protection between off-going and oncoming employees, to minimize exposure to the hazards of unexpected energization or start-up or the equipment or release of stored energy.    On or about November 22, 2017, at the A&AT, LLC plant in La Porte, Texas, the employer did not ensure employees followed shift change procedures and communicated the status of energy control protections, specifically that the lockout protections on "C" Reactor had been modified.
Recent events (3)
  • — F (S) $12934
  • — C (S) $12934
  • — Z (S) $12934

1910.147 D06

Serious Gravity 10 1 instance 4 exposed
Issued
Apr 4, 2018
Abate by
Oct 1, 2018
Penalty
Initial $12,934 · Current $12,934
29 CFR 1910.147(d)(6): Prior to starting work on machines or equipment that have been locked out or tagged out, the employer did not ensure that the authorized employee verified that isolation and deenergization of the machine or equipment had been accomplished.    On or about November 22, 2017, at the A&AT, LLC plant in La Porte, Texas, the employer failed to ensure employees followed energy control procedures to verify the Step 2 "C" Reactor isolation valve remained locked out/ tagged out and the isolation was validated prior to taking the blind off the piping connected to the reactor.
Recent events (3)
  • — F (S) $12934
  • — C (S) $12934
  • — Z (S) $12934

View Invista S.A.R.L's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342793064.