Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NATURAL POLYMER INTERNATIONAL CORPORATION

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NATURAL POLYMER INTERNATIONAL CORPORATION in 3601 EAST PLANO PARKWAY SUITE 150, PLANO, TX 75074 (NAICS 311111). OSHA activity number 342861846.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Natural Polymer International Corporation — free Get an email when a new federal OSHA severe-injury report for Natural Polymer International Corporation is published. One employer, no account, unsubscribe in one click.
Site address
3601 EAST PLANO PARKWAY SUITE 150
City
PLANO
State
TX
ZIP
75074
Mailing
3601 EAST PLANO PARKWAY SUITE 150, PLANO, TX 75074
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311111
Employees
160
Ownership type
A

5 citations on file for this inspection.

1910.212 A01

Serious Gravity 10 1 instance 13 exposed
Issued
Apr 6, 2018
Abate by
May 2, 2018
Penalty
Initial $12,805 · Current $6,500 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    (a) On or about December 29, 2017 employees cleaning augers were exposed to amputation hazards from an unguarded screw auger;    (b) On or about February 2, 2018 maintenance employees cleaning augers were exposed to amputation hazards from an unguarded screw auger.
Recent events (2)
  • — I (S) $6500
  • — Z (S) $12805

1910.332 B01

Serious Gravity 5 1 instance 6 exposed
Issued
Apr 6, 2018
Abate by
May 2, 2018
Penalty
Initial $9,147 · Current $6,500 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    (a) On or about February 14, 2018, and at times prior thereto throughout the facility, employees opened a live 480 volt panel to reset the thermal overloads for the motors on the mixers, bins, and augers without training in electrical safe work practices, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $6500
  • — Z (S) $9147

1910.335 A01 I

Serious Gravity 5 1 instance 6 exposed
Issued
Apr 6, 2018
Abate by
May 2, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  (a) On or about February 14, 2018, and at times prior thereto throughout the facility, maintenance employees were exposed to electrical hazards from opening a live 480 volt panel to reset the thermal overloads for motors, mixers, bins and augers in the facility.  Employees were not provided arc-rated personal protective equipment including: arc-rated long-sleeved shirt, pants or coveralls; arc-rated jacket, parka, rainwear, or hard hat liner (AN); hard hat; hearing protection (ear canal inserts); heavy-duty leather gloves; leather footwear.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 V

Serious Gravity 5 1 instance 6 exposed
Issued
Apr 6, 2018
Abate by
May 2, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face:  (a) On or about February 14, 2018, and at times prior thereto throughout the facility, maintenance employees were exposed to electrical hazards from opening a live 480 volt panel to reset the thermal overloads for motors, mixers, bins and augers in the facility.  Employees were not provided arc-rated personal protective equipment including: arc-rated flash suite hood or arc-related face shield and arc-rated balaclava; safety glasses or safety goggles (SR).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1904.32 B02 I

Other-than-serious 2 instances 161 exposed
Issued
Apr 6, 2018
Abate by
May 2, 2018
Penalty
Initial $1,830 · Current $1,000 Reduced
29 CFR 1904.32(b)(2)(i): Columns on OSHA 300 Logs, or equivalent form, were not totaled:    (a) On or about January 26, 2018 the columns in the number of cases (G - total number of deaths, H - total number of cases with days away from work, I - total number of cases with job transfer or restriction, J - total number of other recordable cases) on the annual summary for the year 2017 were not total;    (b) On or about January 26, 2018 the columns in the injury and illness types (M1 - injury, M2 - skin disorder, M3 - respiratory condition, M4 - poisoning, M5 - hearing loss, M6 - all other illnesses) on the annual summary for the year 2017 were not total.
Recent events (2)
  • — I (O) $1000
  • — Z (O) $1830

View Natural Polymer International Corporation's full OSHA safety record →