Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ARI INDUSTRIES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ARI INDUSTRIES, INC. in 381 ARI COURT, ADDISON, IL 60101 (NAICS 334513). OSHA activity number 342888518.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ARI Industries, INC. — free Get an email when a new federal OSHA severe-injury report for ARI Industries, INC. is published. One employer, no account, unsubscribe in one click.
Site address
381 ARI COURT
City
ADDISON
State
IL
ZIP
60101
Mailing
381 ARI COURT, ADDISON, IL 60101
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
334513
Employees
65
Ownership type
A

2 citations on file for this inspection.

1910.335 A01 I

Serious Gravity 1 1 instance 5 exposed
Issued
Mar 6, 2018
Abate by
Apr 3, 2018
Penalty
Initial $3,297 · Current $1,649 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:     Inspection Department D32.  On or about January 19, 2018 employees performed hipot (high potential) testing on mineral-insulated cable utilizing two Hipot Tester machines (Slaughter Co., Model No. 2965, Capacity 5000 VAC).  Employees performed testing at voltages ranging from approx. 750 to 2500 VAC and were not provided with and did not wear voltage-rated gloves, to prevent contact with energized components during testing.  Employees were exposed to electrical shock and burn hazards to the hands.    Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).    Note:  For abatement assistance, refer to OSHA's Electrical Protective Equipment Standard, 29 CFR 1910.137
Recent events (2)
  • — I (S) $1649
  • — Z (S) $3297

1910.332 B01

Other-than-serious 1 instance 5 exposed
Issued
Mar 6, 2018
Abate by
Apr 3, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  Inspection Department D32.  On or about January 19, 2018 employees performed hipot (high potential) testing on mineral-insulated cable utilizing Hipot Tester machines. Employees were not trained in and familiar with safety-related work practices, including the use of special precautionary techniques, personal protective equipment (PPE) and insulating and shielding materials.  Employees were exposed to electrical shock and burn hazards to the hands.  Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).