Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: COVESTRO LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of COVESTRO LLC in 8 FAIRVIEW WAY, DEERFIELD, MA 01342 (NAICS 326113). OSHA activity number 342899606.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Covestro LLC — free Get an email when a new federal OSHA severe-injury report for Covestro LLC is published. One employer, no account, unsubscribe in one click.
Establishment
COVESTRO LLC
Site address
8 FAIRVIEW WAY
City
DEERFIELD
State
MA
ZIP
01342
Mailing
8 FAIRVIEW WAY, DEERFIELD, MA 01342
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326113
Employees
125
Ownership type
A

4 citations on file for this inspection.

1910.147 C04 I

Deleted Serious Gravity 10 2 instances 9 exposed
Issued
May 1, 2018
Abate by
Jun 18, 2018
Penalty
Initial $12,934 · Current $0 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:  Covestro, LLC, 8 Fairview Way, Deerfield, Massachusetts; On and before December 27, 2017 employees were not utilizing the lockout procedures for equipment:  a.  The line 11 and 13 Glouster machines were locked out without using the procedure during shutdown maintenance.  The extruder was locked out, but not the heaters, exposing employees to electric shock hazards from the 480 volt system.  b.  Operation and Maintenance employees lock out machines from memory without reviewing or utilizing the lockout procedures.
Recent events (2)
  • — I (S) $0
  • — Z (S) $12934

1910.147 D06

Serious Gravity 10 1 instance 2 exposed
Issued
May 1, 2018
Penalty
Initial $12,934 · Current $5,934 Reduced
29 CFR 1910.147(d)(6): Prior to starting work on machines or equipment that had been locked out or tagged out, the authorized employee did not verify that isolation and deenergization of the machine or equipment had been accomplished:    Covestro, LLC, 8 FairviewWay, South Deerfield, Massachusetts;  On or before December 27, 2017 employees did not verify that the line 11 heaters were deenergized as part of the energy control procedures, prior to performing work on or near the heaters.
Recent events (2)
  • — I (S) $5934
  • — Z (S) $12934

1910.334 A02 I

Serious Gravity 5 5 instances 100 exposed
Issued
May 1, 2018
Abate by
May 18, 2018
Penalty
Initial $7,391 · Current $4,231 Reduced
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):    Covestro, LLC, 8 Fairview Way, South Deerfield, Massachusetts, On or before January 25, 2018 the employer did not have a program in place to identify damaged cords, plugs, and insulation on cord and plug equipment:    a. Damaged cord with cut in the insulation of greater than an inch in length.  b. Relocatable power taps being supported by the plugs of equipment plugged into them.  c. Minimum bend radii of cords for lights and portable equipment crimping the cords  d. Insulation on portable cords pulled away from the plugs due to insufficient strain relief  e. Crushed plug on a portable tilter
Recent events (2)
  • — I (S) $4231
  • — Z (S) $7391

1910.137 C02 XII

Other-than-serious 1 instance 8 exposed
Issued
May 1, 2018
Abate by
May 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.137(c)(2)(xii): The employer shall certify that equipment has been tested in accordance with the requirements of paragraphs (c)(2)(iv), (c)(2)(vii)(D), (c)(2)(viii), (c)(2)(ix), and (c)(2)(xi) of this section. The certification shall identify the equipment that passed the test and the date it was tested and shall be made available upon request to the Assistant Secretary for Occupational Safety and Health and to employees or their authorized representatives.                                                                                                                                                                 Note to paragraph (c)(2)(xii): Marking equipment with, and entering onto logs, the results of the tests and the dates of testing are two acceptable means of meeting the certification requirement.  Covestro, LLC, 8 Fairview Way, South Deerfield, Massachusetts; On and before January 25, 2018 employees were using electrically rated gloves that did not have the test date marked on the gloves.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Covestro LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342899606.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.