PORTLAND, OR —
OSHA Inspection: VIGOR MARINE, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of VIGOR MARINE, LLC in 5555 N. CHANNEL AVE, PORTLAND, OR 97217 (NAICS 336611). OSHA activity number 342928439.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VIGOR MARINE, LLC
- Site address
- 5555 N. CHANNEL AVE
- City
- PORTLAND
- State
- OR
- ZIP
- 97217
- Mailing
- 5555 NORTH CHANNEL AVENUE, PORTLAND, OR 97217
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336611
- Employees
- 1800
- Ownership type
- A
Citations
7 citations on file for this inspection.
1915.89 C01
- Issued
- Jul 31, 2018
- Abate by
- Aug 21, 2018
- Penalty
- Initial $129,336 · Current $129,336
General-duty citation text
29 CFR 1915.89(c)(1): The employer did not ensure that, before any authorized employee performs servicing when energization or startup, or the release of hazardous energy, may occur, all energy sources were identified and isolated, and the machinery, equipment, or system was rendered inoperative. (a) M/V Matanuska - Car Deck - On or about February 2nd, 2018 and at times prior thereto, employees were exposed to electrical hazards that would result in cardiac arrest, severe burns and death while connecting or disconnecting wiring in the circuit breakers of the temporary load centers. The employer did not ensure that the energy sources were isolated prior to working in the circuit breaker enclosures (GE TE100R Mod. 8 type 3R), with dead fronts that were intentionally removed.
Recent events (2)
- — I (S) $129336
- — Z (W) $129336
1910.333 A01
- Issued
- Jul 31, 2018
- Abate by
- Aug 21, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not de-energized before the employee worked on or was near to them. (a) M/V Matanuska - Car Deck - On or about February 2nd, 2018 and at times prior thereto, employees were exposed to electrical hazards that would result in cardiac arrest, severe burns and death while connecting or disconnecting wiring in the circuit breakers of the temporary load centers. The employer did not de-energize the circuit breaker enclosures (GE TE100R Mod. 8 type 3R) prior to assigning employees to work within.
Recent events (2)
- — I (S) $0
- — Z (W) $0
1910.335 A02 II
- Issued
- Jul 31, 2018
- Abate by
- Aug 21, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(2)(ii): Protective shields, protective barriers, or insulating materials were not used to protect each employee from shock, burns, or other electrically related injuries while that employee was working near exposed energized parts. (a) M/V Matanuska - Car Deck - On or about February 2nd, 2018 and at times prior thereto, employees were exposed to electrical hazards that would result in cardiac arrest, severe burns and death while connecting or disconnecting wiring in the circuit breakers of the temporary load centers. The employees were working in the GE TE100R Mod. 8 type 3R panel enclosures with energized 100A, 480VAC and 30A, 480VAC circuit breakers without arc flash protective clothing and/or equipment.
Recent events (2)
- — I (S) $0
- — Z (W) $0
1910.303 B02
- Issued
- Jul 31, 2018
- Abate by
- Aug 21, 2018
- Penalty
- Initial $129,336 · Current $129,336
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment were not installed and used in accordance with any instructions included in the listing or labeling. (a) M/V Matanuska - Car Deck - On or about February 2nd, 2018 and at times prior thereto, employees were exposed to electrical hazards that would result in cardiac arrest, severe burns and death while connecting or disconnecting wiring in the circuit breakers of the temporary load centers. The employees were working in energized circuit breaker enclosures (GE TE100R Mod. 8 type 3R) with dead fronts that were intentionally removed and not re-installed per the listing and labeling from Underwriters Laboratories (UL).
Recent events (2)
- — I (S) $129336
- — Z (W) $129336
1910.305 D02
- Issued
- Jul 31, 2018
- Abate by
- Oct 25, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures approved for the purpose and were not dead front. (a) M/V Matanuska - Car Deck - On or about February 2nd, 2018 and at times prior thereto, employees were exposed to electrical hazards that would result in cardiac arrest, severe burns and death while connecting or disconnecting wiring in the circuit breakers of the temporary load centers. The missing dead fronts were located on the 100A, 480VAC and 30A, 480VAC GE TE100R Mod. 8 type 3R circuit breaker enclosures.
Recent events (2)
- — I (S) $0
- — Z (W) $0
1910.305 B01 II
- Issued
- Jul 31, 2018
- Abate by
- Aug 21, 2018
- Penalty
- Initial $64,670 · Current $50,000 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed. (a) M/V Matanuska - Car Deck - On or about February 2nd, 2018 and at times prior thereto, the employees were exposed to electrical hazards that would result in cardiac arrest, severe burns and even death from contact with live conductors through the unused openings on General Electric (GE) circuit breaker enclosures TE 100R MOD 9 Type 3R. Vigor was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.305(b)(1)(ii), which was contained in OSHA inspection number 1138205, citation number 1, item number 4a and was affirmed as a final order on 05/27/2016, with respect to a workplace located at Vigor Alaska, LLC. Mile 7 Nash Rd. Seward, AK. 99664.
Recent events (2)
- — I (R) $50000
- — Z (R) $64670
1915.89 Q01
- Issued
- Jul 31, 2018
- Abate by
- Oct 25, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1915.89(q)(1): The employer did not ensure that the audit was performed by an authorized employee other than the one(s) currently using the energy-control procedure being reviewed. (a) On or about February 2nd, 2018 and at times prior thereto, the employer did not perform an annual audit of their Lock-out Tags-plus program.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Vigor Marine, LLC
View Vigor Marine, LLC's full OSHA safety record →
More inspections in this industry (NAICS 336611)
More inspections in OR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342928439.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.