GREEN BAY, WI —
OSHA Inspection: OAK RIDGE CUSTOM CABINETS, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of OAK RIDGE CUSTOM CABINETS, INC. in 2660 N. PACKERLAND DR., GREEN BAY, WI 54303 (NAICS 337110). OSHA activity number 342962784.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- OAK RIDGE CUSTOM CABINETS, INC.
- Site address
- 2660 N. PACKERLAND DR.
- City
- GREEN BAY
- State
- WI
- ZIP
- 54303
- Mailing
- 2660 N. PACKERLAND DR., GREEN BAY, WI 54303
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 337110
- Employees
- 14
- Ownership type
- A
Citations
11 citations on file for this inspection.
5(a)(1)
- Issued
- May 16, 2018
- Abate by
- Aug 31, 2018
- Penalty
- Initial $3,696 · Current $1,848 Reduced
E200M110
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees working at or near dry dust collection systems (indoor enclosureless bag separator and upstream ducting) handling combustible wood dust were exposed to wood dust fire hazards during the operation and maintenance of the dust collection system: On or about February 21, 2018, a) An indoor enclosureless bag separator (Extrema DC-240.3 Portable Dust Collector) with positive pressure air-material inlet and two unenclosed dust filter bags was used to collected combustible wood dust fines from an Extrema wide belt sander. Employees were exposed to the hazards of fire and flash fire from working in close proximity to the indoor enclosureless dust collector and upstream ducting and manually emptying the bags of collected combustible wood dust in the event of the presence of an internal fire, ember or spark.
Recent events (2)
- — I (S) $1848
- — Z (S) $3696
1910.106 D04 I
- Issued
- May 16, 2018
- Abate by
- Jun 25, 2018
- Penalty
- Initial $3,696 · Current $1,848 Reduced
General-duty citation text
29 CFR 1910.106(d)(4)(i): "Construction." Inside storage rooms shall be constructed to meet the required fire-resistive rating for their use. Such construction shall comply with the test specifications set forth in Standard Methods of Fire Tests of Building Construction and Materials, NFPA 251-1969. Where an automatic sprinkler system is provided, the system shall be designed and installed in an acceptable manner. Openings to other rooms or buildings shall be provided with noncombustible liquid-tight raised sills or ramps at least 4 inches in height, or the floor in the storage area shall be at least 4 inches below the surrounding floor. Openings shall be provided with approved self-closing fire doors. The room shall be liquid-tight where the walls join the floor. A permissible alternate to the sill or ramp is an open-grated trench inside of the room which drains to a safe location. Where other portions of the building or other properties are exposed, windows shall be protected as set forth in the Standard for Fire Doors and Windows, NFPA No. 80-1968, which is incorporated by reference as specified in Sec. 1910.6, for Class E or F openings. Wood at least 1 inch nominal thickness may be used for shelving, racks, dunnage, scuffboards, floor overlay, and similar installations: On or about February 21, 2018, the construction of the inside storage room used to store flammable containers of paints and stains was insufficient when: a) The opening to the spray booth room was not protected with 4 inch noncombustible liquid-tight raised sills, ramps or other lowered floor. b) The opening between the inside storage room and the spray booth room was not provided with an approved self-closing fire door. c) The inside storage room was not liquid-tight where the walls joined the floor.
Recent events (2)
- — I (S) $1848
- — Z (S) $3696
1910.106 D04 II
- Issued
- May 16, 2018
- Abate by
- Jun 25, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(d)(4)(ii): "Rating and capacity." Storage in inside storage rooms shall comply with Table H-13: On or about February 21, 2018, the storage of flammable liquids inside the inside storage room did not comply with Table H-13. The indoor storage room was approximately 9 feet by 5 feet (45 square feet), was not provided fire protection (sprinkler, water spray, carbon dioxide, or other system) and contained greater than 225 gallons of flammable materials (5 gallons/square feet x 45 square feet).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.106 D04 IV
- Issued
- May 16, 2018
- Abate by
- Jun 25, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(d)(4)(iv): Ventilation. Every inside storage room shall be provided with either a gravity or a mechanical exhaust ventilation system. Such system shall be designed to provide for a complete change of air within the room at least six times per hour. If a mechanical exhaust system is used, it shall be controlled by a switch located outside of the door. The ventilating equipment and any lighting fixtures shall be operated by the same switch. A pilot light shall be installed adjacent to the switch if Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), are dispensed within the room. Where gravity ventilation is provided, the fresh air intake, as well as the exhaust outlet from the room, shall be on the exterior of the building in which the room is located: On or about February 21, 2018, the inside storage room was not provide with either a gravity or mechanical exhaust ventilation system.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.106 D04 V
- Issued
- May 16, 2018
- Abate by
- Jun 25, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(d)(4)(v): "Storage in inside storage rooms." In every inside storage room there shall be maintained one clear aisle at least 3 feet wide. Containers over 30 gallons capacity shall not be stacked one upon the other. Dispensing shall be by approved pump or self-closing faucet only: On or about February 21, 2018, the inside storage room was not provide with either a gravity or mechanical exhaust ventilation system.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 C
- Issued
- May 16, 2018
- Abate by
- Jul 26, 2018
- Penalty
- Initial $2,956 · Current $1,478 Reduced
General-duty citation text
29 CFR 1910.134(c): Respiratory protection program. This paragraph requires the employer to develop and implement a written respiratory protection program with required worksite-specific procedures and elements for required respirator use. The program must be administered by a suitably trained program administrator. In addition, certain program elements may be required for voluntary use to prevent potential hazards associated with the use of the respirator: On or about February 21, 2018, the employer did not develop and implement a written respiratory protection program when a Spray Room employee was required to wear a 3M tight-fitting half-face respirator with organic filter cartridges during spray finishing operations to protect against gasses and vapors from wood paints and stains. All provisions of 29 CFR 1910.134(c) through (m) must be covered in a written respiratory protection program. Key elements include, but are not limited to the following: 1) Medical evaluations for respirator use 2) Fit testing 3) Filter change-out schedule 4) Training on use, maintenance and care 5) Recordkeeping
Recent events (2)
- — I (S) $1478
- — Z (S) $2956
1910.134 E01
- Issued
- May 16, 2018
- Abate by
- Jul 26, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(e)(1): The employer shall provide a medical evaluation to determine the employee's ability to use a respirator, before the employee is fit tested or required to use the respirator in the workplace. The employer may discontinue an employee's medical evaluations when the employee is no longer required to use a respirator: On or about February 21, 2018, the employer did not provide a medical evaluation to determine a Spray Room employee's ability to use a respirator before the employee was required to use a 3M tight-fitting half-face respirator with organic filter cartridge during spray finishing operations to protect against gasses and vapors from wood paints and stains.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 F01
- Issued
- May 16, 2018
- Abate by
- Jul 26, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(f)(1): The employer shall ensure that employees using a tight-fitting facepiece respirator pass an appropriate qualitative fit test (QLFT) or quantitative fit test (QNFT) as stated in this paragraph: On or about February 21, 2018, the employer did not ensure that Spray Room employees passed an appropriate QLFT or QNFT when the employee was required to use a 3M tight-fitting half-face respirator with organic filter cartridge during spray finishing operations to protect against gasses and vapors from wood paints and stains.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 G01 I A
- Issued
- May 16, 2018
- Abate by
- Jul 26, 2018
- Penalty
- Initial $2,956 · Current $0 Reduced
General-duty citation text
29 CFR 1910.134(g)(1)(i)(A): The employer shall not permit respirators with tight-fitting facepieces to be worn by employees who have facial hair that comes between the sealing surface of the facepiece and the face or that interferes with valve function: On or about February 21, 2018 the employer permitted a Spray Room employee to wear a 3M tight-fitting half-face respirator when the employee had facial hair that came between the sealing surface of the facepiece of the respirator. The respirator was worn during spray finishing operations to protect against gasses and vapors from wood paints and stains.
Recent events (2)
- — I (S) $0
- — Z (S) $2956
1910.134 H02 I
- Issued
- May 16, 2018
- Abate by
- Jul 26, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(h)(2)(i): All respirators shall be stored to protect them from damage, contamination, dust, sunlight, extreme temperatures, excessive moisture, and damaging chemicals, and they shall be packed or stored to prevent deformation of the facepiece and exhalation valve: On or about February 21, 2018, a Spray Room employee was storing their their 3M tight-fitting half-face respirator by hanging it in the Spray Room area which did not protect it from contamination, dust and damaging chemicals. The respirator was worn during spray finishing operations to protect against gasses and vapors from wood paints and stains.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 K
- Issued
- May 16, 2018
- Abate by
- Jul 26, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(k): Training and information. This paragraph requires the employer to provide effective training to employees who are required to use respirators. The training must be comprehensive, understandable, and recur annually, and more often if necessary. This paragraph also requires the employer to provide the basic information on respirators in Appendix D of this section to employees who wear respirators when not required by this section or by the employer to do so: On or about February 21, 2018, the employer did not provide effective training to a Spray Room employee who was required to wear a 3M tight-fitting half-face respirator. The respirator was worn during spray finishing operations to protect against gasses and vapors from wood paints and stains. All provisions of the training paragraph 29 CFR 1910.95(k) must be provided to affected employees. Key elements include, but are not limited to the following: 1) Purpose, limitations, and uses of respirators 2) Respirator inspection, maintenance and repair/replacement 3) How to recognize medial signs/symptoms the affect respirator use 4) Training conducted annually 5) Appendix D training for voluntary respirator use situations
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at OAK Ridge Custom Cabinets, INC.
View OAK Ridge Custom Cabinets, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 337110)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342962784.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.