Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CROWN PACKAGING CORPORATION

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of CROWN PACKAGING CORPORATION in 1885 WOODMAN CENTER DRIVE, DAYTON, OH 45420 (NAICS 424990). OSHA activity number 343057469.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Crown Packaging Corporation — free Get an email when a new federal OSHA severe-injury report for Crown Packaging Corporation is published. One employer, no account, unsubscribe in one click.
Site address
1885 WOODMAN CENTER DRIVE
City
DAYTON
State
OH
ZIP
45420
Mailing
1885 WOODMAN CENTER DRIVE, DAYTON, OH 45420
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424990
Employees
80
Ownership type
A

10 citations on file for this inspection.

1910.303 B07 IV

Serious Gravity 5 2 instances 2 exposed
Issued
Apr 30, 2018
Abate by
Jun 4, 2018
Penalty
Initial $7,775 · Current $3,296 Reduced
29 CFR 1910.303(b)(7)(iv): Mechanical execution of work. Electric equipment shall be installed in a neat and workmanlike manner.  There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.    a) A GFCI outlet on the northwest side of the warehouse near Location Z10 was damaged in that it appeared bent and had exposed wiring.     b) The base of the breaker box near Doors 23 and 24 was damaged in that the base was partially removed to allow access for a flexible cable.
Recent events (2)
  • — I (S) $3296
  • — Z (S) $7775

1910.303 F02

Serious Gravity 5 2 instances 2 exposed
Issued
Apr 30, 2018
Abate by
Jun 4, 2018
Penalty
Initial $6,220 · Current $3,251 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    a) Breakers in the breaker box in the Dunnage Hold Area were not labeled.     b) Breakers in the breaker box near Door 14 and Door 15 were not labeled.
Recent events (2)
  • — I (S) $3251
  • — Z (S) $6220

1910.303 G01 II

Serious Gravity 5 3 instances 2 exposed
Issued
Apr 30, 2018
Abate by
Jun 15, 2018
Penalty
Initial $6,220 · Current $3,251 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:    a) On or about 4/2/2018, access to the Dunnage Hold Area breaker box was obstructed in that forklifts are parked in front of the breaker box and a forklift charger was positioned on the north side of the breaker box.    b) On or about 4/24/2018, access to the Dunnage Hold Area breaker box was obstructed in that dunnage was positioned in front of the breaker box and a forklift charger was positioned on the north side of the breaker box.    c) On or about 4/24/2018, access to the breaker box near Door 23 and 24 was obstructed in that boxes of merchandise were positioned in front of the breaker box.
Recent events (2)
  • — I (S) $3251
  • — Z (S) $6220

1910.304 F01 VIII

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 30, 2018
Abate by
Jun 4, 2018
Penalty
Initial $6,220 · Current $3,251 Reduced
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD."    The employer did not ensure that circuit breakers near Doors 15 and 16 which are used as switches for fluorescent lighting in the Production Area were listed and marked "SWD".
Recent events (2)
  • — I (S) $3251
  • — Z (S) $6220

1910.304 G05

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Apr 30, 2018
Penalty
Initial $6,220 · Current $0 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    The Sealer Machine located at station K-1 lacked a grounding connection in that the grounding prong on the plug was missing.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6220

1910.334 A02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 30, 2018
Abate by
Jun 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):    The employer did not ensure that portable cord and plug connected equipment such as sealer machines were visually inspected before use.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 I

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 30, 2018
Abate by
Jun 4, 2018
Penalty
Initial $7,775 · Current $0 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering boxes, cabinets, or fittings were not protected from abrasions:    Flexible cable feeding a forklift charger was wired into a breaker box near Doors 23 and 24 without protection from abrasion.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7775

1910.305 G02 III

Serious Gravity 5 2 instances 4 exposed
Issued
Apr 30, 2018
Abate by
Jun 4, 2018
Penalty
Initial $7,775 · Current $0 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:    a) The breaker box near Door 23 and Door 24 did not have strain relief for cords entering the breaker box.     b) The breaker box near Door 14 and Door 15 did not have strain relief for cords entering the breaker box.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7775

1910.332 B01

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 30, 2018
Abate by
Jun 4, 2018
Penalty
Initial $6,220 · Current $3,251 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    The employer did not ensure that maintenance employees and shift supervisors received training in electrical safety-related work practices.
Recent events (2)
  • — I (S) $3251
  • — Z (S) $6220

1910.303 B07 I

Other-than-serious 1 instance 4 exposed
Issued
Apr 30, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment.    Two unused openings in the base of the breaker box in the Dunnage Hold Area were not effectively closed.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Crown Packaging Corporation's full OSHA safety record →