DAYTON, OH —
OSHA Inspection: CROWN PACKAGING CORPORATION
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of CROWN PACKAGING CORPORATION in 1885 WOODMAN CENTER DRIVE, DAYTON, OH 45420 (NAICS 424990). OSHA activity number 343057469.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CROWN PACKAGING CORPORATION
- Site address
- 1885 WOODMAN CENTER DRIVE
- City
- DAYTON
- State
- OH
- ZIP
- 45420
- Mailing
- 1885 WOODMAN CENTER DRIVE, DAYTON, OH 45420
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424990
- Employees
- 80
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.303 B07 IV
- Issued
- Apr 30, 2018
- Abate by
- Jun 4, 2018
- Penalty
- Initial $7,775 · Current $3,296 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Mechanical execution of work. Electric equipment shall be installed in a neat and workmanlike manner. There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. a) A GFCI outlet on the northwest side of the warehouse near Location Z10 was damaged in that it appeared bent and had exposed wiring. b) The base of the breaker box near Doors 23 and 24 was damaged in that the base was partially removed to allow access for a flexible cable.
Recent events (2)
- — I (S) $3296
- — Z (S) $7775
1910.303 F02
- Issued
- Apr 30, 2018
- Abate by
- Jun 4, 2018
- Penalty
- Initial $6,220 · Current $3,251 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Breakers in the breaker box in the Dunnage Hold Area were not labeled. b) Breakers in the breaker box near Door 14 and Door 15 were not labeled.
Recent events (2)
- — I (S) $3251
- — Z (S) $6220
1910.303 G01 II
- Issued
- Apr 30, 2018
- Abate by
- Jun 15, 2018
- Penalty
- Initial $6,220 · Current $3,251 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) On or about 4/2/2018, access to the Dunnage Hold Area breaker box was obstructed in that forklifts are parked in front of the breaker box and a forklift charger was positioned on the north side of the breaker box. b) On or about 4/24/2018, access to the Dunnage Hold Area breaker box was obstructed in that dunnage was positioned in front of the breaker box and a forklift charger was positioned on the north side of the breaker box. c) On or about 4/24/2018, access to the breaker box near Door 23 and 24 was obstructed in that boxes of merchandise were positioned in front of the breaker box.
Recent events (2)
- — I (S) $3251
- — Z (S) $6220
1910.304 F01 VIII
- Issued
- Apr 30, 2018
- Abate by
- Jun 4, 2018
- Penalty
- Initial $6,220 · Current $3,251 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." The employer did not ensure that circuit breakers near Doors 15 and 16 which are used as switches for fluorescent lighting in the Production Area were listed and marked "SWD".
Recent events (2)
- — I (S) $3251
- — Z (S) $6220
1910.304 G05
- Issued
- Apr 30, 2018
- Penalty
- Initial $6,220 · Current $0 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: The Sealer Machine located at station K-1 lacked a grounding connection in that the grounding prong on the plug was missing.
Recent events (2)
- — I (S) $0
- — Z (S) $6220
1910.334 A02 I
- Issued
- Apr 30, 2018
- Abate by
- Jun 4, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): The employer did not ensure that portable cord and plug connected equipment such as sealer machines were visually inspected before use.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 I
- Issued
- Apr 30, 2018
- Abate by
- Jun 4, 2018
- Penalty
- Initial $7,775 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering boxes, cabinets, or fittings were not protected from abrasions: Flexible cable feeding a forklift charger was wired into a breaker box near Doors 23 and 24 without protection from abrasion.
Recent events (2)
- — I (S) $0
- — Z (S) $7775
1910.305 G02 III
- Issued
- Apr 30, 2018
- Abate by
- Jun 4, 2018
- Penalty
- Initial $7,775 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) The breaker box near Door 23 and Door 24 did not have strain relief for cords entering the breaker box. b) The breaker box near Door 14 and Door 15 did not have strain relief for cords entering the breaker box.
Recent events (2)
- — I (S) $0
- — Z (S) $7775
1910.332 B01
- Issued
- Apr 30, 2018
- Abate by
- Jun 4, 2018
- Penalty
- Initial $6,220 · Current $3,251 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: The employer did not ensure that maintenance employees and shift supervisors received training in electrical safety-related work practices.
Recent events (2)
- — I (S) $3251
- — Z (S) $6220
1910.303 B07 I
- Issued
- Apr 30, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment. Two unused openings in the base of the breaker box in the Dunnage Hold Area were not effectively closed.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Crown Packaging Corporation
View Crown Packaging Corporation's full OSHA safety record →
More inspections in this industry (NAICS 424990)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343057469.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.