Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. DEPARTMENT OF JUSTICE - BUREAU OF PRISON - FEDERAL CORRECTIONAL INSTITUTION - MENDOTA

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of U.S. DEPARTMENT OF JUSTICE - BUREAU OF PRISON - FEDERAL CORRECTIONAL INSTITUTION - MENDOTA in 33500 W. CALIFORNIA AVE, MENDOTA, CA 93640 (NAICS 922140). OSHA activity number 343143749.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of Justice - Bureau of Prison - Federal Correctional Institution - Mendota — free Get an email when a new federal OSHA severe-injury report for U.S. Department of Justice - Bureau of Prison - Federal Correctional Institution - Mendota is published. One employer, no account, unsubscribe in one click.
Site address
33500 W. CALIFORNIA AVE
City
MENDOTA
State
CA
ZIP
93640
Mailing
33500 W. CALIFORNIA AVE, MENDOTA, CA 93640
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922140
Employees
100
Ownership type
D

2 citations on file for this inspection.

1910.22 D02

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 29, 2018
Abate by
Jul 26, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.22(d)(2): Hazardous conditions on walking / working surfaces were not corrected or repaired before an employee uses the walking-working surface again. If the correction or repair cannot be made immediately, the hazard must be guarded to prevent employees from using the walking-working surface until the hazard is corrected or repaired:    Control Center: A sub floor panel (24 X 24 inches) located in front of a bathroom door inside the Control Center Room was removed. An employee stepped out of the bath room and fell 18 inches in the hole. The employee sustained a sprain.
Recent events (1)
  • — Z (S) $0

1910.305 E01

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 29, 2018
Abate by
Jul 26, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panel board enclosures in wet locations were not weatherproof:    Control Center: A junction box with knockouts was fixed to the concrete floor and was not elevated to prevent water from coming inside the box. The junction box contained energized conductors and was placed in a location that had been flooded.  Employees were exposed to electrical shock and burn injuries.
Recent events (1)
  • — Z (S) $0

View U.S. Department of Justice - Bureau of Prison - Federal Correctional Institution - Mendota's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343143749.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.