Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DECOR PRODUCTS, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of DECOR PRODUCTS, INC. in 1201 DECOR DRIVE, WAUSAUKEE, WI 54177 (NAICS 336370). OSHA activity number 343182077.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Decor Products, INC. — free Get an email when a new federal OSHA severe-injury report for Decor Products, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1201 DECOR DRIVE
City
WAUSAUKEE
State
WI
ZIP
54177
Mailing
P.O. BOX 320, WAUSAUKEE, WI 54177
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336370
Employees
88
Ownership type
A

5 citations on file for this inspection.

1910.22 A01

Serious Gravity 5 1 instance 4 exposed
Issued
Nov 2, 2018
Abate by
Dec 4, 2018
Penalty
Initial $6,467 · Current $3,880 Reduced
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, and service rooms shall be kept clean and orderly and in a sanitary condition.  a.  On or about May 24, 2018 in the basement production area of the facility located at 1201 Decor Dr. Wausaukee, WI 54177, employees were exposed to fire hazards created by the buildup of an electrostatic coating on the basement walls, horizontal surfaces, and equipment.
Recent events (2)
  • — I (S) $3880.2
  • — Z (S) $6467

1910.106 E06 I

Serious Gravity 5 1 instance 4 exposed
Issued
Nov 2, 2018
Abate by
Dec 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors:  a.  On or about May 24, 2018 in the basement production area of the facility located at 1201 Decor Dr. Wausaukee, WI 54177, employees were exposed to fire hazards created by the accumulation and use of flammable liquids in the basement in the presence of radiant heat hazards from the oven.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.242 B

Serious Gravity 1 1 instance 4 exposed
Issued
Nov 2, 2018
Abate by
Dec 4, 2018
Penalty
Initial $3,880 · Current $2,328 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning. Compressed air shall not be used for cleaning purposes except where reduced to less than 30 p.s.i. and then only with effective chip guarding and personal protective equipment.  a.  On or about May 24, 2018 in the basement production area of the facility located at 1201 Decor Dr. Wausaukee, WI 54177, employees were exposed to inhalation hazards and struck-by hazards when using compressed air over 30 psi to clean the electrostatic powder from their clothes.
Recent events (2)
  • — I (S) $2328
  • — Z (S) $3880

1910.305 B01 II

Other-than-serious 3 instances 4 exposed
Issued
Nov 2, 2018
Abate by
Dec 4, 2018
Penalty
Initial $5,174 · Current $2,070 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed.    a.  On or about May 24, 2018, at the facility located at 1201 Decor Dr. Wausaukee, WI 54177, the employer had a junction box located on the Northwest area of the basement ceiling that was not effectively closed due to an open knock out.
Recent events (2)
  • — I (O) $2069.6
  • — Z (S) $5174

1910.305 G01 IV A

Other-than-serious 2 instances 4 exposed
Issued
Nov 2, 2018
Abate by
Dec 4, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for permanent building wiring.    a.  On or about May 24, 2018, the employer used an extension cord as a substitute for permanent building wiring.  The extension cord was used to supply power to a light fixture in the basement.    b.  On or about May 24, 2018, the employer used an extension cord as a substitute for permanent building wiring.   The extension cord was used to supply power to a radio in the basement.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0