NASHUA, NH —
OSHA Inspection: AFP 105 CORPORATION
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of AFP 105 CORPORATION in 11 TARA BLVD, NASHUA, NH 03062 (NAICS 721110). OSHA activity number 343182994.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AFP 105 CORPORATION
- Site address
- 11 TARA BLVD
- City
- NASHUA
- State
- NH
- ZIP
- 03062
- Mailing
- 11 TARA BLVD, NASHUA, NH 03062
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 100
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.147 C04 I
- Issued
- Aug 30, 2018
- Abate by
- Oct 18, 2018
- Penalty
- Initial $6,467 · Current $3,230 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: The employer did not establish procedures for employees required to lock out and/or tag out equipment for maintenance, repair or replacement including but not limited to the domestic hot water system.
Recent events (2)
- — I (S) $3230
- — Z (S) $6467
1910.147 C05 II
- Issued
- Aug 30, 2018
- Abate by
- Oct 18, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(5)(ii): Devices other than lockout devices and tag out devices were used for controlling energy: In the boiler room, masking tape was used to cover circuit breakers controlling energy to equipment which was removed for repair.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C06 I
- Issued
- Aug 30, 2018
- Abate by
- Oct 18, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: Location: site Annual inspections of the energy control program had not been conducted
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B01 VIII
- Issued
- Aug 30, 2018
- Abate by
- Dec 3, 2018
- Penalty
- Initial $9,054 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(1)(viii): Electrical equipment was not free from recognized hazards based on other factors that contribute to the practical safeguarding of persons using or likely to come in contact with the equipment: Location: electrical room Employees were exposed to electrical hazards while standing/walking through water to empty a barrel used to catch water and vacuuming water from the floor from water leaking into a 480 volt main electrical panel.
Recent events (2)
- — I (S) $0
- — Z (S) $9054
1910.303 G02 I B
- Issued
- Aug 30, 2018
- Abate by
- Sep 26, 2018
- Penalty
- Initial $6,467 · Current $3,230 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i)(B): Except as elsewhere required or permitted by this standard, live parts of electrical equipment operating at 50 volts or more was not guarded by suitable permanent, substantial partitions or screens so arranged so that only qualified persons would have access to the space within reach of the live parts. Any openings in such partitions or screens were not so sized and located that persons were not likely to come into accidental contact with the live parts or to bring conducting objects into contact with them: Location: main electrical room Employees were exposed to electrical shock and burns while working in close proximity of live parts on a 480 volt electrical panel partially covered only by a piece of rubber.
Recent events (2)
- — I (S) $3230
- — Z (S) $6467
1910.303 B07 I
- Issued
- Aug 30, 2018
- Abate by
- Oct 18, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment. Location: electrical room Instance 1; two circuit breakers were missing and the openings not covered in a 208 volt electrical panel. Instance 2; an electrical box that's purpose was not known had an uncovered opening on the front of the box.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 E01 II
- Issued
- Aug 30, 2018
- Abate by
- Oct 18, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Electrical equipment in use was not marked giving voltage, current, wattage or other ratings. Location: electrical room The employer did not ensure the main electrical panel and circuit breaker panels were marked to indicate their voltage.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 F02
- Issued
- Aug 30, 2018
- Abate by
- Oct 18, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Location: throughout the facility Circuit breaker panels in the boiler room, main electrical room and pool area had one or more circuit breakers either not marked or not legibly marked to indicate its purpose and one of the disconnects on the main electrical panel in the electrical room was not marked to identify its purpose.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at AFP 105 Corporation
View AFP 105 Corporation's full OSHA safety record →
More inspections in this industry (NAICS 721110)
More inspections in NH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343182994.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.