Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AFP 105 CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of AFP 105 CORPORATION in 11 TARA BLVD, NASHUA, NH 03062 (NAICS 721110). OSHA activity number 343681870.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch AFP 105 Corporation — free Get an email when a new federal OSHA severe-injury report for AFP 105 Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
AFP 105 CORPORATION
Site address
11 TARA BLVD
City
NASHUA
State
NH
ZIP
03062
Mailing
11 TARA BLVD, NASHUA, NH 03062
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
100
Ownership type
A

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 28, 2019
Penalty
Initial $5,304 · Current $3,000 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    Location: main electrical room  On or about 12/13/18, a relocatable power tap (surge protector) was used with two water pumps plugged into it and also was not plugged directly into a receptacle but had an extension cord run to it from a receptacle.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5304

1910.305 J02 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 28, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:  Location: Main electrical room On or about 12/17/19 a receptacle (relocatable power tap) used in close proximity to two water pumps was not GFCI protected.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 28, 2019
Abate by
May 14, 2019
Penalty
Initial $13,261 · Current $0 Reduced
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided:    Location: main electrical room  On or about 12/17/19, Employees were exposed to electrical hazards when emptying a barrel filled with water draining from a leaking conduit containing 480 volt conductors . The employer had a drain hole drilled into the conduit to drain the water to keep it from entering the main electrical switch gear.    AFP 105 Corporation, dba Radisson Hotel Nashua was previously cited for a violation of this occupational safety and health standard or its equivalent standard (name previously cited standard), which was contained in OSHA inspection number 1318299, citation number 1, item number 1d and was affirmed as a final order on 9/18/2018, with respect to a workplace located at 11 Tara Blvd., Nashua, NH.
Recent events (2)
  • — I (S) $0
  • — Z (R) $13261

View AFP 105 Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343681870.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.