Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SAMSUNG AUSTIN SEMICONDUCTOR LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of SAMSUNG AUSTIN SEMICONDUCTOR LLC in 12100 SAMSUNG BLVD., AUSTIN, TX 78754 (NAICS 334413). OSHA activity number 343190955.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Samsung Austin Semiconductor LLC — free Get an email when a new federal OSHA severe-injury report for Samsung Austin Semiconductor LLC is published. One employer, no account, unsubscribe in one click.
Site address
12100 SAMSUNG BLVD.
City
AUSTIN
State
TX
ZIP
78754
Mailing
12100 SAMSUNG BLVD., AUSTIN, TX 78754
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
334413
Employees
3529
Ownership type
A

4 citations on file for this inspection.

1910.305 B03 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 15, 2018
Abate by
Jun 21, 2018
Penalty
Initial $12,934 · Current $7,760 Reduced
29 CFR 1910.305(b)(3)(i): Pull and junction boxes used on systems rated over 600 volts, nominal, did not provide a complete enclosure for the contained conductors or cables:  On or about February 15, 2018, and in times prior thereto, the side panel covers were missing from adjoining Ampgard, 4160 Volt electrical starter cabinets, exposing workers to the hazard of an arc flash, located in the Cub 2 Building.
Recent events (2)
  • — I (S) $7760.4
  • — Z (S) $12934

1910.335 A02 II

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 15, 2018
Abate by
Jun 21, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(2)(ii): Protective shields, protective barriers, or insulating materials were not used to protect each employee from shock, burns, or other electrically related injuries while that employee is working near exposed energized parts which might be accidentally contacted or where dangerous electric heating or arcing might occur.   On or about February 15, 2018, and in times prior thereto, where the side panel covers were missing from adjoining Ampgard, 4160 Volt electrical starter cabinets, shields or barriers were not used to isolate the live parts of the adjoining panels while employees performed work near them, exposing workers to the hazard of an arc flash, located in the Cub 2 Building.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 15, 2018
Abate by
Jun 21, 2018
Penalty
Initial $12,934 · Current $7,760 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  On or about February 15, 2018, and in times prior thereto, electricians were working next to 4160 volt live parts that were not deenergized or insulated without using electrical arc flash protective equipment for face, hands and body.  The close proximity to live buss bars exposed the electricians to an arc flash hazard, located in the Cub 2 Building.
Recent events (2)
  • — I (S) $7760.4
  • — Z (S) $12934

1910.335 A02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 15, 2018
Abate by
Jun 21, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts:  On or about February 15, 2018, and in times prior thereto, electricians were using a 16 inch torque wrench that was not insulated within one inch of 4160 volts of electricity.  The close proximity of this wrench to live buss bars exposed the electricians to an arc flash hazard, located in the Cub 2 Building.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Samsung Austin Semiconductor LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343190955.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.