AUSTIN, TX —
OSHA Inspection: SAMSUNG AUSTIN SEMICONDUCTOR LLC
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of SAMSUNG AUSTIN SEMICONDUCTOR LLC in 12100 SAMSUNG BLVD., AUSTIN, TX 78754 (NAICS 334413). OSHA activity number 343190955.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SAMSUNG AUSTIN SEMICONDUCTOR LLC
- Site address
- 12100 SAMSUNG BLVD.
- City
- AUSTIN
- State
- TX
- ZIP
- 78754
- Mailing
- 12100 SAMSUNG BLVD., AUSTIN, TX 78754
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 334413
- Employees
- 3529
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.305 B03 I
- Issued
- Jun 15, 2018
- Abate by
- Jun 21, 2018
- Penalty
- Initial $12,934 · Current $7,760 Reduced
General-duty citation text
29 CFR 1910.305(b)(3)(i): Pull and junction boxes used on systems rated over 600 volts, nominal, did not provide a complete enclosure for the contained conductors or cables: On or about February 15, 2018, and in times prior thereto, the side panel covers were missing from adjoining Ampgard, 4160 Volt electrical starter cabinets, exposing workers to the hazard of an arc flash, located in the Cub 2 Building.
Recent events (2)
- — I (S) $7760.4
- — Z (S) $12934
1910.335 A02 II
- Issued
- Jun 15, 2018
- Abate by
- Jun 21, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(2)(ii): Protective shields, protective barriers, or insulating materials were not used to protect each employee from shock, burns, or other electrically related injuries while that employee is working near exposed energized parts which might be accidentally contacted or where dangerous electric heating or arcing might occur. On or about February 15, 2018, and in times prior thereto, where the side panel covers were missing from adjoining Ampgard, 4160 Volt electrical starter cabinets, shields or barriers were not used to isolate the live parts of the adjoining panels while employees performed work near them, exposing workers to the hazard of an arc flash, located in the Cub 2 Building.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Jun 15, 2018
- Abate by
- Jun 21, 2018
- Penalty
- Initial $12,934 · Current $7,760 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: On or about February 15, 2018, and in times prior thereto, electricians were working next to 4160 volt live parts that were not deenergized or insulated without using electrical arc flash protective equipment for face, hands and body. The close proximity to live buss bars exposed the electricians to an arc flash hazard, located in the Cub 2 Building.
Recent events (2)
- — I (S) $7760.4
- — Z (S) $12934
1910.335 A02 I
- Issued
- Jun 15, 2018
- Abate by
- Jun 21, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts: On or about February 15, 2018, and in times prior thereto, electricians were using a 16 inch torque wrench that was not insulated within one inch of 4160 volts of electricity. The close proximity of this wrench to live buss bars exposed the electricians to an arc flash hazard, located in the Cub 2 Building.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Samsung Austin Semiconductor LLC
View Samsung Austin Semiconductor LLC's full OSHA safety record →
More inspections in this industry (NAICS 334413)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343190955.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.