Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: BRIDGEWATER RESOURCES, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BRIDGEWATER RESOURCES, INC. in 15 POLHEMUS LANE, BRIDGEWATER, NJ 08807 (NAICS 562219). OSHA activity number 343215018.

Watch Bridgewater Resources, INC. — free Get an email when a new federal OSHA severe-injury report for Bridgewater Resources, INC. is published. One employer, no account, unsubscribe in one click.
Site address
15 POLHEMUS LANE
City
BRIDGEWATER
State
NJ
ZIP
08807
Mailing
15 POLHEMUS LANE, BRIDGEWATER, NJ 08807
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
562219
Employees
14
Ownership type
A

8 citations on file for this inspection.

1910.22 A01

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2217.00 · Current $1117.00 Reduced
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition:    a) 15 Polhemus Ln, Bridgewater, NJ site - Maintenance shop:    Garbage from adjacent room falls through the opening in the wall into the maintenance work area.      Condition noted on or about 6/8/2018.
Recent events (2)
  • — I (S) $1117
  • — Z (S) $2217

1910.141 A04 II

Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.141(a)(4)(ii): All sweepings, solid or liquid wastes, refuse and garbage was not removed in such a manner as to avoid creating a menace to health and as often as necessary or appropriate to maintain the place of employment in a sanitary condition.    a) 15 Polhemus Ln,  Bridgewater, NJ Site - Maintenance Shop: All sweepings, solid or liquid wastes, refuse and garbage were not removed from employees' break area.    Condition noted on or about  6/8/2018.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.28 B01 I

Serious Gravity 5 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $4434.00 · Current $2234.00 Reduced
29 CFR 1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that was 4 feet (1.2 m) or more above a lower level was protected from falling by one or more of the following:  Guardrail systems, safety net systems, or personal fall arrest systems:    a) 15 Polhemus Ln, Bridgewater, NJ site - Outside maintenance shop:    Guardrails were not provided  on the ramp located outside the maintenance repair shop. The ramp is 54 inches above the adjacent ground. Equipment that is stored on the ground can cause impalement.     Condition noted on or about 6/8/2018.
Recent events (2)
  • — I (S) $2234
  • — Z (S) $4434

1910.253 B04 III

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $2956.00 · Current $1746.00 Reduced
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least.     a) 15 Polhemus Ln, Bridgewater, NJ site - Maintenance shop/ Parts Room:    Three (3) Oxygen gas cylinders were stored next to an acetylene compressed gas cylinder.    Conditions noted on or about 6/8/2018.
Recent events (2)
  • — I (S) $1746
  • — Z (S) $2956

1910.303 B02

Serious Gravity 5 3 instances 8 exposed
Issued
Abate by
Penalty
Initial $3696.00 · Current $3566.00 Reduced
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.     Electrical equipment including but not limited to a water cooler, computer(s), were supplied power via an electrical power supply (re-locatable power tap).  Re-locatable power taps are not intended to be used as a substitute for fixed wiring.    a) 15 Polhemus Ln, Bridgewater, NJ site - Maintenance shop: Water Cooler, microwave(s)    b) 15 Polhemus Ln, Bridgewater, NJ site - Operations Manager's Office: Computer(s)    Condition noted on or about 6/8/2018.
Recent events (2)
  • — I (S) $3566
  • — Z (S) $3696

1910.303 B07 IV

Serious Gravity 5 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $3696.00 · Current $2912.00 Reduced
29 CFR 1910.303(b)(7)(iv): Equipment with damaged parts that may adversely affect its safe operation or its mechanical strength, such as broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating parts shall not be used:     a) 15 Polhemus Ln, Bridgewater, NJ site - Maintenance Shop: Electrical outlet(s) that were providing power to a welding machine and other hand tools were damaged which could severely affect the safe operation of the equipment.    b) 15 Polhemus Ln, Bridgewater, NJ site - Maintenance Office: Electrical outlet(s) that were providing power to hand tools were damaged which could severely affect the safe operation of the equipment.    Condition noted on or about 6/8/2018.
Recent events (2)
  • — I (S) $2911.75
  • — Z (S) $3696

1910.304 G05

Serious Gravity 5 1 instance 4 exposed
Issued
Penalty
Initial $3696.00 · Current $2912.00 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:      a) 15 Polhemus Ln, Bridgewater, NJ site - Operation Manager's Office: The extension cord that supplied power to the window air conditioner was not continuous, in that, the grounding pin was missing.    Condition noted on or about 6/8/2018.
Recent events (2)
  • — I (S) $2911.75
  • — Z (S) $3696

1910.305 G01 IV

Serious Gravity 5 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv):  a) 15 Polhemus Ln, Bridgewater, NJ site - Operation Manager's Office:  A flexible cord (extension cord) was used as a substitute for fixed wiring to supply power to the window air conditioner located in the main office.    Condition noted on or about 6/8/2018.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View BRIDGEWATER RESOURCES, INC.'s full OSHA safety record →