METTER, GA —
OSHA Inspection: CPE AMERICA RENTALS, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of CPE AMERICA RENTALS, LLC in 655 WEST LYTELL STREET, METTER, GA 30439 (NAICS 333911). OSHA activity number 343262408.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CPE AMERICA RENTALS, LLC
- Site address
- 655 WEST LYTELL STREET
- City
- METTER
- State
- GA
- ZIP
- 30439
- Mailing
- 655 WEST LYTELL STREET, METTER, GA 30439
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 333911
- Employees
- 23
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.107 C05
- Issued
- Dec 21, 2018
- Abate by
- Jan 18, 2019
- Penalty
- Initial $2,513 · Current $2,010 Reduced
General-duty citation text
29 CFR 1910.107(c)(5): Electrical equipment in any spraying area that contained both deposits of readily ignitable residue and explosive vapors, whereon deposits of combustible residues may readily accumulate, was not approved for the location. A) East end of building, on or about June 27, 2018, the spray area used by the employer to spray flammable paints, contained portable fans with electric motors that were not approved for the location, exposing employees to a fire hazard.
Recent events (2)
- — I (S) $2010.4
- — Z (S) $2513
1910.107 C08
- Issued
- Dec 21, 2018
- Abate by
- Jan 18, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(c)(8): Portable lamp(s) were used in the spraying area(s) during spraying operations: A) East end of building, on or about June 27, 2018, the spray area used by the employer to spray flammable paints, contained portable lamps (fluorescent lights) that were not designed for that location, exposing employees to a fire hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.253 B04 I
- Issued
- Dec 21, 2018
- Abate by
- Jan 18, 2019
- Penalty
- Initial $2,513 · Current $2,010 Reduced
General-duty citation text
29 CFR 1910.253(b)(4)(i): Oxygen cylinders were stored near highly combustible material, especially oil and grease; or near reserve stocks of carbide and acetylene or other fuel-gas cylinders, or near other substance likely to cause or accelerate fire: A) East end of building, on or about June 27, 2018, or prior to, oxygen cylinders were stored inside a spray area where flammable paints are used, exposing employees to a fire hazard.
Recent events (2)
- — I (S) $2010.4
- — Z (S) $2513
1910.134 E01
- Issued
- Dec 21, 2018
- Abate by
- Jan 18, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace: A) Garage area and spray paint area, on or about June 27, 2018, or prior to, employees who used a 3M half mask with 2078 filters or a 3M half mask with SP71 filters were not given a medical evaluation prior to using the respirators.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.134 F01
- Issued
- Dec 21, 2018
- Abate by
- Jan 18, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(f)(1): The employer did not ensure that employee(s) required to use a tight-fitting facepiece respirator passed the appropriate qualitative fit test (QLFT) or quantitative fit test (QNFT): A) Garage area and spray paint area, on or about June 27, 2018, or prior to, employees who used a 3M half mask with 2078 filters or a 3M half mask with SP71 filters were not fitted tested for the respirators prior to using the respirator while working.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at CPE America Rentals, LLC