OSHA Inspection: PREFERRED MEAL SYSTEMS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PREFERRED MEAL SYSTEMS, INC. in 4135 BIRNEY AVENUE, SCRANTON, PA 18507 (NAICS 311412). OSHA activity number 343318986.

Watch Preferred Meal Systems, INC. — free Get an email when a new federal OSHA severe-injury report for Preferred Meal Systems, INC. is published. One employer, no account, unsubscribe in one click.
Site address
4135 BIRNEY AVENUE
City
SCRANTON
State
PA
ZIP
18507
Mailing
4135 BIRNEY AVENUE, SCRANTON, PA 18507
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311412
Employees
255
Ownership type
A

5 citations on file for this inspection.

1910.219 F03

Serious Gravity 5 2 instances 20 exposed
Issued
Abate by
Penalty
Initial $9239.00 · Current $6468.00 Reduced
29 CFR 1910.219(f)(3): Sprocket wheels and chains which were seven (7) feet or less above floors or platforms were not enclosed:    a) CoPk-1, Clarity Room, 4135 Birney Avenue, Moosic, PA  On a daily basis, employees filled trays on the conveyor section of an Ameripak Model 245 Tray Sealer (Serial No. 234) driven by a chain and sprocket system thirty-four (34) inches above the floor that was not fully enclosed on the left side of the machine (facing feed end to discharge end) exposing employees to an in-running nip point and caught-in hazard, as observed on or about July 19, 2018.    b) CoPk-2, Clarity Room, 4135 Birney Avenue, Moosic, PA  On at least a weekly basis, employees filled trays on the conveyor section of a DAK Corporation Model 954123 Packaging Machine (Serial No. 175200) driven by a chain and sprocket system thirty-four (34) inches above the floor that was not enclosed on the right or left side of the machine exposing employees to in-running nip points and caught-in hazard, on or about July 19, 2018.    In accordance with 29 CFR 1903.19, abatement certification is required for this violation.
Recent events (2)
  • — I (S) $6468
  • — Z (S) $9239

1910.303 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $7391.00 · Current $5174.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.    a) Basement, 4135 Birney Avenue, Moosic, PA - Employees used a 100-amp service rated Federal Pacific Electric Company Panelboard (No. AF-761304) with circuit breakers that totaled 385 amps which was not in accordance with the listing and labeling instructions exposing employees to the arc flash and contact with electrical current hazards, on or about July 19, 2018.    In accordance with 29 CFR 1903.19, abatement certification is required for this violation.
Recent events (2)
  • — I (S) $5174
  • — Z (S) $7391

1910.303 F02

Other-than-serious 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.    a) Basement, 4135 Birney Avenue, Moosic, PA - Circuit breakers in a 100A, 120/208V, 3-Phase, 4-Wire Federal Pacific Electric Company Panelboard (No. AF-761304) were not legibly and/or correctly marked to indicate their purpose exposing employees to electrical hazards in the event of an electrical incident, on or about July 19, 2018.    In accordance with 29 CFR 1903.19, abatement certification is required for this violation.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 B01 II

Other-than-serious 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.    a) Basement, 4135 Birney Avenue, Moosic, PA - Employees used a 100A, 120/208V, 3-Phase, 4-Wire Federal Pacific Electric Company Panelboard (No. AF-761304) with three (3) unused circuit breaker openings which bared an energized busbar exposing employees to a contact with electrical current hazard, on or about July 19, 2018.    In accordance with 29 CFR 1903.19, abatement certification is required for this violation.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 B02 I

Deleted Serious Gravity 5 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose.  a) Basement, 4135 Birney Avenue, Moosic, PA - Employees operated a washer and dryer adjacent to energized (208V) conductors in an uncovered junction box on on the south side of the Encon 3200-A Energy Management System control panel exposing employees to a contact with electrical current hazard, on or about July 19, 2018.  In accordance with 29 CFR 1903.19, abatement certification is not required for this violation as the hazardous condition was corrected during the inspection.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View PREFERRED MEAL SYSTEMS, INC.'s full OSHA safety record →

CTI FOODS

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343318986.