MORRIS, CT —
OSHA Inspection: INTEGRATED ILLUMINATION SYSTEMS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of INTEGRATED ILLUMINATION SYSTEMS, INC. in 355 BANTAM LAKE ROAD, MORRIS, CT 06763 (NAICS 335122). OSHA activity number 343324133.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INTEGRATED ILLUMINATION SYSTEMS, INC.
- Site address
- 355 BANTAM LAKE ROAD
- City
- MORRIS
- State
- CT
- ZIP
- 06763
- Mailing
- 355 BANTAM LAKE ROAD, MORRIS, CT 06763
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 335122
- Employees
- 134
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.147 C01
- Issued
- Sep 25, 2018
- Abate by
- Nov 13, 2018
- Penalty
- Initial $6,652 · Current $4,656 Reduced
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative: Facility: On, or about, July 20, 2018, the company had not developed and implemented a written lockout/tagout program that consisted of specific lockout procedures, lockout hardware and employee training.
Recent events (2)
- — I (S) $4656.4
- — Z (S) $6652
1910.212 A03 II
- Issued
- Sep 25, 2018
- Penalty
- Initial $8,315 · Current $5,821 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s): On, or about, July 20, 2018, hazards created by machinery had not been adequately safeguarded: A. TM5Assembly Area: Pinch point created at insertion area. B. Machine Shop: Point of operation on Kobalt sliding miter saw.
Recent events (2)
- — I (S) $5820.5
- — Z (S) $8315
1910.303 B02
- Issued
- Sep 25, 2018
- Penalty
- Initial $4,240 · Current $2,968 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: SMT: On, or about, July 20, 2018, three relocatable power taps were not used in accordance with listing/labeling contained in the UL Whitebook in that they were used series to provide power to a computer workstation. Also, the relocatable power taps were energized through a green extension cord instead of being energized directly by permanently installed receptacles.
Recent events (2)
- — I (S) $2968
- — Z (S) $4240
1910.305 G01 IV A
- Issued
- Sep 25, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: SMT: On, or about, July 20, 2018, a green extension cord was used to provide power to a computer workstation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 A
- Issued
- Sep 25, 2018
- Penalty
- Initial $8,315 · Current $5,821 Reduced
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized: Final Assembly: On, or about, July 20, 2018, employees were using Hi-Pot testing equipment to verify correct wiring and insulation on lighting components. The testing was done on metal work tables with static dissipating mats. Electrical Safety Related Work Practices had not been developed and implemented in accordance with industry guidelines to reduce/eliminate the risk of electric shock to employees.
Recent events (2)
- — I (S) $5820.5
- — Z (S) $8315
1910.242 B
- Issued
- Sep 25, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: On, or about, July 20, 2018, in the following locations, compressed air nozzles used for cleaning were measured to be greater than 30 p.s.i., dead-ended: A. TM5 Assembly Area. B. Machine Shop: Bridgeport milling machine J256982.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Integrated Illumination Systems, INC.
View Integrated Illumination Systems, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 335122)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343324133.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.