OSHA Inspection: CAMGER COATINGS SYSTEMS, INCORPORATED

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CAMGER COATINGS SYSTEMS, INCORPORATED in 364 MAIN STREET, NORFOLK, MA 02056 (NAICS 325510). OSHA activity number 343370557.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Camger Coatings Systems, Incorporated — free Get an email when a new federal OSHA severe-injury report for Camger Coatings Systems, Incorporated is published. One employer, no account, unsubscribe in one click.
Site address
364 MAIN STREET
City
NORFOLK
State
MA
ZIP
02056
Mailing
364 MAIN STREET, NORFOLK, MA 02056
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325510
Employees
35
Ownership type
A

8 citations on file for this inspection.

1910.36 D01

Serious Gravity 5 2 instances 3 exposed
Issued
Oct 23, 2018
Abate by
Feb 13, 2019
Penalty
Initial $5,498 · Current $3,849 Reduced
29 CFR 1910.36(d)(1): Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge. A device such as a panic bar that locks only from the outside is permitted on exit discharge doors.    a) Location - Lacquer room:  On 07/27/18, the double exit doors to the outside were difficult to open as they are held secured with a wooden bar across, and did not have panic bar hardware.    b) Location - Boathouse storage building (detached from main building):  On 07/27/18, Both single side hinged doors to the outside flammable liquids storage room did not have any hardware.
Recent events (2)
  • — I (S) $3848.5
  • — Z (S) $5498

1910.36 E01

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 23, 2018
Abate by
Dec 13, 2018
Penalty
Initial $5,498 · Current $0 Reduced
29 CFR 1910.36(e)(1): 29 CFR 1910.36(e)(1): A side-hinged door was not used to connected rooms to an exit route:    a) Location - Lower level Clear Mixing Wing;  On 08/08/18, the door within the exit route through the Clear Mixing Wing from a high hazard area was a rollup overhead door.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5498

1910.36 E02

Deleted Serious Gravity 5 2 instances 3 exposed
Issued
Oct 23, 2018
Abate by
Dec 13, 2018
Penalty
Initial $5,498 · Current $0 Reduced
29 CFR 1910.36(e)(2): The door that connects any room to an exit route did not swing out in the direction of exit travel when the room is designed to be occupied by more than 50 people or if the room is a high hazard area:  a) Location - Upper level Staging / Shipping area: On 07/27/18, the door connecting the exit route through the lunch room in the egress from the staging / shipping area  did not swing out in the direction of exit travel.   b) Location - Upper level lunch room On 07/27/18, two sets of exit doors connecting the exit route through the lunch room from a high hazard area to the main entry way did not swing out in the direction of exit travel.   c) Location - Main entryway and exit to street On 07/27/18 the main exit door to the exit from a high hazard area did not swing out in the direction of exit travel.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5498

1910.37 A03

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 23, 2018
Penalty
Initial $4,673 · Current $3,271 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    Location - Lower Level Flammable liquids warehouse   On 08/08/18, materials were stored within the exit route, partially obstructing egress.
Recent events (2)
  • — I (S) $3271
  • — Z (S) $4673

1910.106 E02 II B 2

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
Oct 23, 2018
Abate by
Dec 13, 2018
Penalty
Initial $5,498 · Current $0 Reduced
29 CFR 1910.106(e)(2)(ii)(b)(2): More than 120 gallons of Category 2, 3, or 4 flammable or combustible liquids in containers were located outside of inside storage room(s) or storage cabinet(s):  Location - Shipping / Staging area: On 07/27/18, the amount of flammable liquids being stored in the loading dock staging area exceeded allowable amounts by 1910.106 and NFPA standards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5498

1910.106 E03 III

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 23, 2018
Abate by
Dec 13, 2018
Penalty
Initial $5,498 · Current $3,849 Reduced
29 CFR 1910.106(e)(3)(iii): "Chemical processes." Areas where unstable liquids are handled or small scale unit chemical processes are carried on was not separated from the remainder of the plant by a fire wall of 2-hour minimum fire resistance rating.    (a) Location -  Upper Level; Small Batch Color Lab:  On 07/27/18, the lab was not separated from the remainder of the plant by a fire wall of 2-hour minimum fire resistance rating as required.    (b) Location - Lower Level; Packaging area:  The packaging area where flammable liquids are being poured into smaller containers was not separated by room with fire walls of 2-hour minimum fire resistance.
Recent events (2)
  • — I (S) $3848.5
  • — Z (S) $5498

1910.106 E03 IV A

Serious Gravity 5 4 instances 8 exposed
Issued
Oct 23, 2018
Abate by
Mar 23, 2022
Penalty
Initial $5,498 · Current $3,849 Reduced
29 CFR 1910.106(e)(3)(iv)(a): Emergency drainage systems were not provided to direct flammable liquid leakage and fire protection water to a safe location. This may require curbs, scuppers, or special drainage systems to control the spread of fire; see paragraph (b)(2)(vii)(b) of this section.    a) Location - Upper level; Lacquer Production Room:  On 07/27/18, the lacquer production room did not have an emergency drainage system as required by standards.     b) Location - Boat house liquid warehouse:  On 07/27/18, the boat house storage area did not have an emergency drainage system as required by standards.     c) Location - Lower level; Area 2 Production Room:  On 08/08/18, The Area 2 production room did not have an emergency drainage system as required by standards.    d) Location - Lower Level Loading Dock 2; flammable liquid storage warehouse:  On 08/08/18, The flammable liquids storage warehouse did not have an emergency drainage system as required by standards.    e) Location - Lower Level Packaging Area:  On 08/08/18, Where batches are poured into smaller container in the packaging area, the floor did not have an emergency drainage system as required by standards where batches are poured into smaller containers.
Recent events (3)
  • — P (S) $3848.5
  • — I (S) $3848.5
  • — Z (S) $5498

1910.307 C02 I

Serious Gravity 5 2 instances 3 exposed
Issued
Oct 23, 2018
Abate by
Feb 13, 2019
Penalty
Initial $5,498 · Current $3,849 Reduced
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present:    a) Location - Lower Level Packaging Area:  On 08/18/18, the electric hoist used to lift up mixing vessels with pour spouts for gravity pouring finished product into shipping containers was not intrinsically safe in this area of operations.    b) Location - Lower Level Packaging Area:  On 08/18/18, the electrical outlet supplying power to the electric hoist flexible cord was not intrinsically safe in this area of operations.
Recent events (2)
  • — I (S) $3848.5
  • — Z (S) $5498

View Camger Coatings Systems, Incorporated's full OSHA safety record →