Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TRICON ENTERPRISES INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TRICON ENTERPRISES INC. in 64 PEARL HARBOR AVE FORT MONMOUTH RESEARCH BUILDING, TINTON FALLS, NJ 07724 (NAICS 238910). OSHA activity number 343381109.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tricon Enterprises INC. — free Get an email when a new federal OSHA severe-injury report for Tricon Enterprises INC. is published. One employer, no account, unsubscribe in one click.
Site address
64 PEARL HARBOR AVE FORT MONMOUTH RESEARCH BUILDING
City
TINTON FALLS
State
NJ
ZIP
07724
Mailing
322 BEERS ST, KEYPORT, NJ 07735
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238910
Employees
10
Ownership type
A

5 citations on file for this inspection.

1926.403 B02

Other-than-serious Gravity 5 1 instance 30 exposed
Issued
Jan 22, 2019
Abate by
Jun 4, 2019
Penalty
Initial $2,772 · Current $2,500 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  a)Demolition project at Old Fort Monmouth at 64 Pearl Harbor Way in Tinton Falls, NJ, 07703- Quadrant 3:  Employees operated electrical equipment which was not installed according to the listing and labeling in that hardware including but not limited to screws and other securing hardware and latches from the front panels were missing, additionally electrical equipment boxes were not permanently mounted and were instead attached to hand trucks which were not secured, observed on or about 8/9/18.  NOTE:  THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (3)
  • — J (O) $2500
  • — C (S) $2772
  • — Z (S) $2772

1926.403 H

Other-than-serious Gravity 5 1 instance 30 exposed
Issued
Jan 22, 2019
Abate by
Jun 4, 2019
Penalty
Initial $2,217 · Current $2,500
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident: a)Demolition project at Old Fort Monmouth at 64 Pearl Harbor Way in Tinton Falls, NJ, 07703- Quadrant 3:  Employees operated electrical equipment which was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, observed on or about 8/9/18.    NOTE:  THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (3)
  • — J (O) $2500
  • — C (S) $2217
  • — Z (S) $2217

1926.405 A02 II I

Other-than-serious Gravity 10 1 instance 30 exposed
Issued
Jan 22, 2019
Abate by
Jun 14, 2019
Penalty
Initial $3,880 · Current $2,500 Reduced
29 CFR 1926.405(a)(2)(ii)(I): Protection was not provided to avoid damage to flexible cords and cables used for temporary wiring which passed through doorways or other pinch points: a)Demolition project at Old Fort Monmouth at 64 Pearl Harbor Way in Tinton Falls, NJ, 07703- Quadrant 3:  Employees operated electrical equipment where protection was not provided to avoid damage to flexible cords and cables used for temporary wiring which passed through doorways or other pinch points, observed on or about 8/9/18.    NOTE:  THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (3)
  • — J (O) $2500
  • — C (S) $3880
  • — Z (S) $3880

1926.405 B01

Deleted Serious Gravity 5 1 instance 30 exposed
Issued
Jan 22, 2019
Abate by
Feb 15, 2019
Penalty
Initial $2,772 · Current $0 Reduced
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed: a)Demolition project at Old Fort Monmouth at 64 Pearl Harbor Way in Tinton Falls, NJ, 07703- Quadrant 3:  Employees operated electrical equipment which had unused openings which were not effectively closed including but not limited to knockouts in electrical panel boxes and circuit breaker opening without a blank, observed on or about 8/9/18.      NOTE:  THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (3)
  • — J (S) $0
  • — C (S) $2772
  • — Z (S) $2772

1926.405 F

Other-than-serious Gravity 5 1 instance 30 exposed
Issued
Jan 22, 2019
Abate by
Jun 14, 2019
Penalty
Initial $2,772 · Current $2,500 Reduced
29 CFR 1926.405(f): All conductors used for general wiring were not insulated: a)Demolition project at Old Fort Monmouth at 64 Pearl Harbor Way in Tinton Falls, NJ, 07703- Quadrant 3:  Employees operated electrical equipment where conductors used for general wiring were not insulated, including but not limited to exit sign lighting wiring, observed on or about 8/9/18.     NOTE:  THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.