FREEPORT, IL —
OSHA Inspection: SNAK-KING CORP.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of SNAK-KING CORP. in 3133 INDUSTRIAL DRIVE, FREEPORT, IL 61032 (NAICS 311919). OSHA activity number 343387221.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SNAK-KING CORP.
- Site address
- 3133 INDUSTRIAL DRIVE
- City
- FREEPORT
- State
- IL
- ZIP
- 61032
- Mailing
- 3133 INDUSTRIAL DRIVE, FREEPORT, IL 61032
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311919
- Employees
- 390
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.36 G04
- Issued
- Feb 13, 2019
- Abate by
- Mar 25, 2019
- Penalty
- Initial $12,503 · Current $0 Reduced
General-duty citation text
29 CFR 1910.36(g)(4): Objects that projected into the exit route reduced the width of the exit route to less than the minimum width requirements of exit routes: Wastewater Treatment Plant, DAF Unit Side. Objects such as permanent piping, ladders, pallets and chemical totes projected into the exit route, reducing the width to less than 28 inches. Employees were exposed to smoke inhalation and burn hazards from delayed egress in the event of a fire, or other emergency. Abatement documentation is required for this item in accordance with 29 CFR 1904.19(d).
Recent events (2)
- — I (S) $0
- — Z (S) $12503
1910.212 A01
- Issued
- Feb 13, 2019
- Abate by
- Mar 25, 2019
- Penalty
- Initial $8,335 · Current $8,000 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: On or about August 15, 2018 through December 18, 2018, the following machines were not adequately guarded, exposing employees to lacerations, fractures and contusions. b) Potato Peeling Line, Potato Transfer Conveyor. The ingoing nip point on the underside of the conveyor between the idle roller and the belt was not guarded. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $8000
- — Z (S) $8335
1910.303 G01 I B
- Issued
- Feb 13, 2019
- Penalty
- Initial $6,251 · Current $8,000
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the working space did not permit at least a 90-degree opening of equipment doors or hinged panels: On or about August 15, 2018, electrical panels in areas listed below did not have doors that would open to at least 90 degrees, exposing maintenance employees to electrical shock hazards as the clear work space was reduced while performing voltage testing/troubleshooting: a) Potato Peeling Line, 480v panel, in front of potato conveyor. b) Corn Kitchen, Corn Chip Seasoner, 480v panel across from Fastback accumulater machine. There is no abatement documentation or certification required for this item.
Recent events (2)
- — I (S) $8000
- — Z (S) $6251
1910.332 B01
- Issued
- Feb 13, 2019
- Abate by
- Mar 25, 2019
- Penalty
- Initial $13,260 · Current $8,000 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees shall be trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments: On or about August 15, 2018 through December 18, 2018, maintenance employees performed troubleshooting and servicing tasks on or near energized electrical components, including voltage testing from 120v to 480v. Employees were not trained in and familiarized with safety-related work practices such as the use of special precautionary techniques, personal protective equipment (PPE), insulated tools and insulating and shielding materials necessary to safely accomplish such tasks. Employees were exposed to the hazards of shock, electrocution and arc flash/blast injuries. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $8000
- — Z (S) $13260
1910.333 C02
- Issued
- Feb 13, 2019
- Abate by
- Mar 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(c)(2): Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools: On or about August 15, 2018 through December 18, 2018, maintenance employees performed troubleshooting and servicing tasks on energized electrical components, including voltage testing. The employer did not ensure that such employees were qualified, capable of working safely through familiarity with special precautionary techniques, personal protective equipment, insulating and shielding materials and insulated tools necessary to safety accomplish such tasks. Employees were exposed to the hazards of shock, electrocution and arc flash/blast injuries. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 C01
- Issued
- Feb 13, 2019
- Abate by
- Mar 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(c)(1): Only qualified persons may perform testing work on electric circuits or equipment: On or about August 15, 2018 through December 18, 2018, maintenance employees who were not qualified persons were assigned and permitted to perform voltage testing on energized components such as but not limited to control panels for fryers, extruders, corn chip seasoners, corn kettles, and packaging machinery conveyors. Employees were exposed to the hazards of shock, electrocution and arc flash/blast injuries. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Feb 13, 2019
- Abate by
- Mar 25, 2019
- Penalty
- Initial $13,260 · Current $8,000 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards did not use or were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: On or about August 15, 2018 through December 18, 2018, all maintenance employees who performed work on or around energized electrical components (480v) were not provided with or did not wear electrical protective equipment appropriate for the level of exposure, to protect against shock, electrocution and arc flash/blast injuries, including: 1) Hand protection: Rubber insulating gloves with leather protectors or arc-rated gloves 2) Apparel: Arc-rated clothing such as arc-rated long-sleeve shirt and pants or arc-rated coverall 3) Head and face protection: Arc-rated face shield, arc-rated hard hat, arc-rated flash suit hood and/or balaclava. 4) Hearing protection: Hearing protectors (canal inserts). Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d). Abatement Note: For compliance assistance, refer to NFPA 70E national consensus standard, Standard for Electrical Safety in the Workplace, 2017 Edition, www.NFPA.org.
Recent events (2)
- — I (S) $8000
- — Z (S) $13260
1910.137 C02 VIII
- Issued
- Feb 13, 2019
- Abate by
- Mar 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and/or the maximum intervals between tests were not conducted in accordance with Table I-4 and Table I-5. On or about August 15, 2018, rubber insulating gloves utilized by maintenance employees had not been electrically tested (or replaced) at six month intervals to ensure that the dielectric properties of the gloves were adequate to protect from contact with energized parts while performing energized tasks, including voltage testing. Abatement certification is required for this item in accordance with 29 CFR 1903.19(c).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.28 B03 I
- Issued
- Feb 13, 2019
- Penalty
- Initial $41,674 · Current $8,065 Reduced
General-duty citation text
29 CFR 1910.28(b)(3)(i): The employer did not ensure each employee was protected from falling through any hole (including skylights) that was 4 feet (1.2 m) or more above a lower level by one or more of the following: A. Guardrail systems; B. Safety net systems or C. Personal fall protection systems, such as personal fall arrest, travel restraint, or positioning systems: North Corn Cook Mezzanine - On or about August 15, 2018, employees working in the area of the corn kettles were exposed to falls greater than 4 feet to the floor below. Floor holes around the bottom of the following corn cook kettles were not guarded, nor was another means of employee protection utilized: a) Corn cook kettle #1 b) Corn cook kettle #2 There is no abatement documentation or certification required for this item. Snak-King Corp. was previously cited for a violation of this occupational safety and health standard or its equivalent standard which was contained in OSHA Inspection Number 1114452, Citation Number 1, Item Number 1 and was affirmed as a final order on June 8, 2016 with respect to a workplace located at 3133 Industrial Drive, Freeport, IL 61032.
Recent events (2)
- — I (S) $8064.5
- — Z (R) $41674
1910.36 G02
- Issued
- Feb 13, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points: Corn Kitchen, Fries Extruder Machines - On or about August 15, 2018, employees worked between extruder machines where the exit access width was less than 28". This condition was likely to delay egress and expose employees to injury in the event of an emergency: a) The exit access from the work area between Fries Extruder machines #4 and #5 was only 24" wide. b) The exit access from the work area between Fries Extruder machines #5 and #6 was only 24" wide. There is no abatement documentation or certification required for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.132 D01
- Issued
- Feb 13, 2019
- Abate by
- Mar 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards were present, or were likely to be present, which necessitated the use of personal protective equipment: On or about August 15, 2018 through December 18, 2018, the employer's personal protective equipment (PPE) hazard assessment was not adequate in that: a) Packaging Dept. Mezzanine. Employees were not required to wear head protection when stooping to walk beneath moving overhead conveyors and standing/working next to reciprocating conveyor ends that were near head height. Employees' heads were exposed to lacerations and contusions. b) Employees working in Maintenance were required to wear hard hats. This was not reflected in the employer's written PPE hazard assessment document. c) Employees working in the JFC Corn Cook and North Corn Cook Areas were required to wear eye/face protection and rubber boots. This was not reflected in the employer's written PPE hazard assessment document.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Snak-King Corp.
View Snak-King Corp.'s full OSHA safety record →
More inspections in this industry (NAICS 311919)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343387221.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.