Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NEHEMIAH HOLDINGS LLC

Monitoring inspection · Health discipline

On , OSHA opened a monitoring health inspection of NEHEMIAH HOLDINGS LLC in 105 HEATHER CT, BALL GROUND, GA 30107 (NAICS 335929). OSHA activity number 343389425.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Nehemiah Holdings LLC — free Get an email when a new federal OSHA severe-injury report for Nehemiah Holdings LLC is published. One employer, no account, unsubscribe in one click.
Site address
105 HEATHER CT
City
BALL GROUND
State
GA
ZIP
30107
Mailing
105 HEATHER CT, BALL GROUND, GA 30107
Inspection type
Monitoring (D)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
335929
Employees
20
Ownership type
A

3 citations on file for this inspection.

1910.303 B02

Other-than-serious 5 instances 15 exposed
Issued
Dec 14, 2018
Penalty
Initial $1,885 · Current $500 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a.  On or about August 17, 2018 employees were exposed to electrical hazards where a relocatable power tap was attached by cable ties to the work station frame in the custom cable area to supply power to hand tools and an overhead light fixture.    b.  On or about August 17, 2018 employees were exposed to electrical hazards where a relocatable power tap was attached by cable ties to the work station frame in the Wire Prep area to provide power to a cut-strip machine.    c.  On or about August 17, 2018 employees were exposed to electrical hazards where two relocatable power taps were connected in series (daisy chained) at the wire harness table in the Harness Area to provide power to hand tools such as a heat gun.    d.  On or about August 17, 2018 employees were exposed to electrical hazards where a relocatable power tap was attached by screws to the wood frame of a mobile harness easel in the Harness Area to provide power to overhead lighting fixtures.    e.  On or about August 17, 2018 employees were exposed to electrical hazards at complex assembly where a 4 inch by 4 inch pull box intended to be mounted to the building structure was used as a free hanging pendant box in which were installed receptacles for cord and plug connected equipment.
Recent events (2)
  • — I (O) $500
  • — Z (S) $1885

1910.305 G01 IV A

Other-than-serious 1 instance 15 exposed
Issued
Dec 14, 2018
Abate by
Jan 4, 2019
Penalty
Initial $1,885 · Current $500 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    a.  On or about August 17, 2018 employees were exposed to hazards related to electrical installation methods where flexible cable was used to provide power to a 4 inch by 4 inch electrical box mounted above the work station light fixture in the Custom Cable area.  The electrical box and receptacles provided power to the light fixture and to a relocatable power tap.    b.  On or about August 17, 2018 employees were exposed to hazards related to electrical installation methods where flexible cable was used to provide power to a 4 inch by 4 inch electrical box and receptacles attached to a vertical component of the work station frame at the assembly tables in the Wire Prep area.  The box and receptacles were used to provide power via cord and plug to another 4 inch by 4 inch electrical box and receptacles in the Wire Prep area.    c.  On or about August 17, 2018 employees were exposed to hazards related to electrical installation methods where flexible cord and plug were used to provide power to a 4 inch by 4 inch electrical box and receptacles attached to a conduit frame supporting an overhead light fixture in the Wire Prep area.  The receptacles were used to provide power to the overhead light and to a relocatable power tap into which was plugged a cut-strip machine.    d.  On or about August 17, 2018 employees were exposed to hazards related to electrical installation methods where flexible cable was used to provide power to a 4 inch by 4 inch electrical box used as a pendant receptacle at the Complex Assembly station.  Connected to the electrical box was a relocatable power tap, a "Milwaukee" heat gun, and an extension cord connected to a table top light fixture.    e.  On or about August 17, 2018 employees were exposed to hazards related to electrical installation methods where flexible cord and plug were used to provide power from a 4 inch by 4 inch electrical box to a table top light fixture at the Complex Assembly station.
Recent events (2)
  • — I (O) $500
  • — Z (S) $1885

1910.305 G01 IV D

Other-than-serious 1 instance 15 exposed
Issued
Dec 14, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used where attached to building surfaces:    a.  On or about August 17, 2018 employees were exposed to hazards related to electrical installation methods where cable ties were used to attach  the electrical cords of an overhead light fixture and a relocatable power tap to the work station frame in the Custom Cable area.    b.  On or about August 17, 2018 employees were exposed to hazards related to electrical installation methods where cable ties were used to attach  the electrical cord of the light fixture to the work station frame at station AA1 in the Custom Cable assembly area.    c.  On or about August 17, 2018 employees were exposed to hazards related to electrical installation methods where cable ties were used to attach  the electrical cord of the light fixture to the work station frame at station AA3 in the Custom Cable assembly area.    d.  On or about August 17, 2018 employees were exposed to hazards related to electrical installation methods where cable ties were used to attach  a yellow flexible cable to the workstation frame to provide power to a 4 inch by 4 inch electrical box and receptacles at the assembly tables in the Wire Prep area.     e.  On or about August 17, 2018 employees were exposed to hazards related to electrical installation methods where cable ties were used to attach a  flexible cord and plug used to provide power from one 4 inch by 4 inch electrical box and receptacles to another 4 inch by 4 inch electrical box and receptacles attached to a conduit frame supporting an overhead light fixture in the Wire Prep area.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View Nehemiah Holdings LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343389425.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.