BLAKESLEE, PA —
OSHA Inspection: TEKRINS, INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of TEKRINS, INC. in 291 COMMERCE BLVD, BLAKESLEE, PA 18610 (NAICS 238210). OSHA activity number 343399242.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TEKRINS, INC.
- Site address
- 291 COMMERCE BLVD
- City
- BLAKESLEE
- State
- PA
- ZIP
- 18610
- Mailing
- 11 E TROUT RUN ROAD, EPHRATA, PA 17522
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 6
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.152 C04 I
- Issued
- Sep 20, 2018
- Abate by
- Nov 7, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.152(c)(4)(i): Portable outdoor storage tanks for flammable or combustible liquids were nearer than 20 feet from the building(s): a) Blakeslee, PA: A 500-gallon diesel fuel storage tank was placed about 2 feet from a structure used as a workplace for employees, on or about August 16, 2018. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (O) $0
1926.152 D02
- Issued
- Sep 20, 2018
- Abate by
- Nov 7, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.152(d)(2): A portable fire extinguisher having a rating of not less than 20-B was not located between 25 feet and 75 feet from flammable liquid storage area(s) located outside: a) Blakeslee, PA: A portable fire extinguisher was not available in the area where a 500-gallon diesel storage tank was used for refueling equipment, on or about August 16, 2018. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (O) $0
1926.152 G09
- Issued
- Sep 20, 2018
- Abate by
- Nov 7, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.152(g)(9): Conspicuous and legible signs prohibiting smoking were not posted in service and refueling areas: a) Blakeslee, PA: A sign prohibiting smoking was not posted where a 500-gallon diesel storage tank was used for refueling equipment, on or about August 16, 2018. ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (O) $0
More inspections at Tekrins, INC.
View Tekrins, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343399242.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.