Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TEKRINS, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of TEKRINS, INC. in 291 COMMERCE BLVD, BLAKESLEE, PA 18610 (NAICS 238210). OSHA activity number 343399242.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tekrins, INC. — free Get an email when a new federal OSHA severe-injury report for Tekrins, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
TEKRINS, INC.
Site address
291 COMMERCE BLVD
City
BLAKESLEE
State
PA
ZIP
18610
Mailing
11 E TROUT RUN ROAD, EPHRATA, PA 17522
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
6
Ownership type
A

3 citations on file for this inspection.

1926.152 C04 I

Other-than-serious 1 instance 6 exposed
Issued
Sep 20, 2018
Abate by
Nov 7, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.152(c)(4)(i): Portable outdoor storage tanks for flammable or combustible liquids were nearer than 20 feet from the building(s):  a) Blakeslee, PA: A 500-gallon diesel fuel storage tank was placed about 2 feet from a structure used as a workplace for employees, on or about August 16, 2018.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (O) $0

1926.152 D02

Other-than-serious 1 instance 6 exposed
Issued
Sep 20, 2018
Abate by
Nov 7, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.152(d)(2): A portable fire extinguisher having a rating of not less than 20-B was not located between 25 feet and 75 feet from flammable liquid storage area(s) located outside:  a) Blakeslee, PA: A portable fire extinguisher was not available in the area where a 500-gallon diesel storage tank was used for refueling equipment, on or about August 16, 2018.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (O) $0

1926.152 G09

Other-than-serious 1 instance 6 exposed
Issued
Sep 20, 2018
Abate by
Nov 7, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.152(g)(9): Conspicuous and legible signs prohibiting smoking were not posted in service and refueling areas:  a) Blakeslee, PA: A sign prohibiting smoking was not posted where a 500-gallon diesel storage tank was used for refueling equipment, on or about August 16, 2018.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (O) $0

View Tekrins, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343399242.