Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ACM SERVICES LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ACM SERVICES LLC in 3443 ED BLUESTEIN BLVD., AUSTIN, TX 78721 (NAICS 238210). OSHA activity number 343433173.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ACM Services LLC — free Get an email when a new federal OSHA severe-injury report for ACM Services LLC is published. One employer, no account, unsubscribe in one click.
Establishment
ACM SERVICES LLC
Site address
3443 ED BLUESTEIN BLVD.
City
AUSTIN
State
TX
ZIP
78721
Mailing
3280 FM 112, TAYLOR, TX 76574
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
42
Ownership type
A

1 citation on file for this inspection.

1926.416 A03

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 12, 2018
Abate by
Sep 18, 2018
Penalty
Initial $6,467 · Current $3,234 Reduced
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into physical or electrical contact with the electric power circuit.    On or about August 24, 2018, the main disconnect for the building undergoing renovation was de-energized and a dead front was installed.  The load side of the switch was tested, but not the line side that was energized exposing electricians to 7200 volts AC and the hazard of electrical burns. The transfer switches were located next to the building being renovated.
Recent events (2)
  • — I (S) $3233.5
  • — Z (S) $6467

View ACM Services LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343433173.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.