OSHA Inspection: U.S. FISH & WILDLIFE SERVICE/ CABEZA PRIETA NATIONAL WILDLIFE REFUGE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. FISH & WILDLIFE SERVICE/ CABEZA PRIETA NATIONAL WILDLIFE REFUGE in 1611 N. 2ND AVE, AJO, AZ 85321 (NAICS 924120). OSHA activity number 343437711.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Fish & Wildlife Service/ Cabeza Prieta National Wildlife Refuge — free Get an email when a new federal OSHA severe-injury report for U.S. Fish & Wildlife Service/ Cabeza Prieta National Wildlife Refuge is published. One employer, no account, unsubscribe in one click.
Site address
1611 N. 2ND AVE
City
AJO
State
AZ
ZIP
85321
Mailing
1611 N. 2ND AVE ATTEN: SID SLONE, AJO, AZ 85321
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
15
Ownership type
D

2 citations on file for this inspection.

1910.157 E04

Serious Gravity 1 3 instances 13 exposed
Issued
Sep 28, 2018
Abate by
Oct 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(4): Stored pressure dry chemical portable fire extinguishers that require a 12 year hydrostatic test were not emptied and subjected to applicable maintenance procedures every 6 years:  a) Oil Conex Box - A portable fire extinguisher was overdue the 6-year maintenance checks.   b) Law Enforcement Office (House)  - A portable fire extinguisher was overdue the 6-year maintenance checks.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 5 exposed
Issued
Sep 28, 2018
Abate by
Oct 11, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Vistor Center Employee Break Area - a "UL" listed relocatable power tap (RPT) was not used in accordance with instructions to power a refrigerator and a microwave oven.