FLORA, IL —
OSHA Inspection: QCIRCUITS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of QCIRCUITS, INC. in 1 INDUSTRIAL PARK, FLORA, IL 62839 (NAICS 334416). OSHA activity number 343476545.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- QCIRCUITS, INC.
- Site address
- 1 INDUSTRIAL PARK
- City
- FLORA
- State
- IL
- ZIP
- 62839
- Mailing
- 1 INDUSTRIAL PARK, FLORA, IL 62839
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 334416
- Employees
- 12
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.305 G01 IV A
- Issued
- Dec 28, 2018
- Abate by
- Jan 25, 2019
- Penalty
- Initial $1,885 · Current $1,885
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) East side of facility in the Surface Mount Department, a 110 volt flexible cord was taped to the floor across the aisle, hard wired into a 4 plex electrical receptacle as permanent wiring. b) In the Stockroom area, several flexible 110 volt power extension cords were supplying electrical power to the overhead lights. c) In the north central section of the facility, a flexible 110 volt power extension cord was supplying electrical power to the overhead light.
Recent events (1)
- — Z (S) $1885
1910.305 G01 IV D
- Issued
- Dec 28, 2018
- Abate by
- Jan 25, 2019
- Penalty
- Initial $1,885 · Current $1,885
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces: a) In the Stockroom area, several flexible 110 volt power cords were wrapped around ceiling structural steel. b) In the north central section of the facility, a flexible 110 volt power cord was wrapped around ceiling structural steel.
Recent events (1)
- — Z (S) $1885
1910.22 A03
- Issued
- Dec 28, 2018
- Abate by
- Jan 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(3): Walking-working surfaces were not maintained free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice: East side of facility in the Surface Mount Department, a 110 volt flexible cord was taped to the floor across the aisle creating a tripping hazard.
Recent events (1)
- — Z (O) $0
1910.303 G01 II
- Issued
- Dec 28, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space about electric equipment rated 600 volts, nominal, or less was used for storage: At the north wall, the two electrical panels had material stored in the space below them.
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 334416)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343476545.