HOLLIDAYSBURG, PA —
OSHA Inspection: WALKER LUMBER COMPANY, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of WALKER LUMBER COMPANY, INC. in 780 RESERVOIR ROAD, HOLLIDAYSBURG, PA 16648 (NAICS 321113). OSHA activity number 343546883.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WALKER LUMBER COMPANY, INC.
- Site address
- 780 RESERVOIR ROAD
- City
- HOLLIDAYSBURG
- State
- PA
- ZIP
- 16648
- Mailing
- 148 TIPPLE LANE P.O. BOX 60, WOODLAND, PA 16881
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321113
- Employees
- 6
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.147 C07 I C
- Issued
- Nov 7, 2018
- Abate by
- Dec 5, 2018
- Penalty
- Initial $5,174 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(7)(i)(C): Employees whose work operations are in an area where energy control procedures are utilized, were not instructed about the procedure: a) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: On or about October 16, 2018, the employer did not ensure that employees who operate the unscrambler machine or who work in areas of the facility where energy control procedures are utilized were instructed about the procedures.
Recent events (2)
- — I (S) $0
- — Z (S) $5174
1910.147 C07 IV
- Issued
- Nov 7, 2018
- Abate by
- Dec 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(iv): The employer did not certify that employee training had been accomplished and kept up to date: a) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: On or about October 16, 2018, the employer did not certify that employee training had been accomplished and kept up to date for each employee working in areas of the plant where energy control procedures are utilized including those employees who operate the unscrambler machine.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B01
- Issued
- Nov 7, 2018
- Abate by
- Nov 20, 2018
- Penalty
- Initial $6,467 · Current $6,400 Reduced
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: a) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, employees were exposed to electrical hazards created by conduit that was broken off and disconnected from an electrical box located on the floor of the building near the unscrambler machine. Conductors (220 volt) running through the conduit were exposed. b) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, employees were exposed to electrical hazards created by conduit that was broken off and disconnected from an electrical box located on the floor of the building near the unscrambler machine. A conduit leading into a junction box with five missing knockouts was broken off and separated from the junction box. c) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, employees were exposed to electrical hazards created by an electrical panel that was missing screws to secure the front cover to the frame of the panel. An orange flexible cord ran through a gap between the front cover and the frame of the electrical panel.
Recent events (2)
- — I (S) $6400
- — Z (S) $6467
1910.303 G02 I
- Issued
- Nov 7, 2018
- Abate by
- Nov 20, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures: a) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, the door on a green electrical panel that was located on the side of the unscrambler machine was left open. The electrical panel housed equipment that was energized to 220 volts.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Nov 7, 2018
- Abate by
- Nov 20, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, a orange flexible cord used to supply power (110 volt) to a DeWalt brand air compressor was draped over nails and through an electrical panel.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Nov 7, 2018
- Abate by
- Nov 20, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed: a) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, unused openings existed inside of an electrical panel that was located on the wall near the unscrambler machine. Unused openings existed to the left of a switch that was labeled 'Deck' and near the bottom of the panel. b) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, unused openings on a junction box were not effectively closed. Multiple knockouts on a junction box located on the floor of the shop near the unscrambler machine were missing and filled with debris.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.22 A01
- Issued
- Nov 7, 2018
- Abate by
- Dec 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, service rooms, and walking-working surfaces were not kept in a clean, orderly, and sanitary condition: a) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, stones, wood, dust and debris accumulated on the floor of the facility on the sides of and beneath of the unscrambler machine. b) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, dust accumulated on top of wooden beams along the wall of the building near the unscrambler machine. c) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, stones, wood, dust and debris accumulated on top of and inside of a green electrical panel located on the side of the unscambler machine.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.178 L06
- Issued
- Nov 7, 2018
- Abate by
- Dec 5, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l). The certification shall include the name of the operator, the date of the training, the date of the evaluation, and the identity of the person(s) performing the training or evaluation: a) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: On or about October 16, 2018, the employer did not certify that each employee who operated a Sellick SD-100 forklift or a Hyster P80A forklift had been trained and trained and evaluated as required by this paragraph (l).
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 E01 II
- Issued
- Nov 7, 2018
- Abate by
- Nov 20, 2018
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Markings were not provided on electrical equipment giving voltage, current, wattage, and other ratings as necessary: a) Jobsite, 780 Reservoir Road, Hollidaysburg, PA 16648: Observed on or about October 16, 2018, an electrical cabinet located on the wall near the unscrambler machine was not equipped with labels or markings showing the voltage, current, wattage, and other ratings as necessary.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Walker Lumber Company, INC.
View Walker Lumber Company, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 321113)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343546883.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.