Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,892Inspections Most recent open 2026-09-03 Last loaded 2026-09-07

OSHA Inspection: OWAN, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of OWAN, LLC in 6745 W SUNDUST ROAD, CHANDLER, AZ 85226 (NAICS 441229). OSHA activity number 343561551.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Owan, LLC for free Get an email when a new federal OSHA severe-injury report for Owan, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
OWAN, LLC
Site address
6745 W SUNDUST ROAD
City
CHANDLER
State
AZ
ZIP
85226
Mailing
6745 W SUNDUST ROAD, CHANDLER, AZ 85226
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
441229
Employees
10
Ownership type
Private (A)

4 citations on file for this inspection.

1910.157 C04

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 28, 2018
Abate by
Dec 4, 2018
Penalty
Initial $3,142 · Current $1,000 Reduced
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition:    Maintenance Area - Portable fire extinguisher gauge indicating it was discharged. Arrow was on the left side of the green serviceable area with no safety pin installed.
Recent events (2)
  • · I (S) $1000
  • · Z (S) $3142

1910.305 G01 IV A

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 28, 2018
Abate by
Dec 10, 2018
Penalty
Initial $3,769 · Current $1,000 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    Outdoor maintenance area - Two flexible cords connected together, approximately 100 foot each, were being used as a substitute for fixed wiring.
Recent events (2)
  • · I (S) $1000
  • · Z (S) $3769

1910.157 C01

Other-than-serious 1 instance 2 exposed
Issued
Nov 28, 2018
Abate by
Dec 10, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  Maintenance Area - A portable fire extinguisher in the outside maintenance area was not mounted, located and identified so that it was readily available when needed.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.305 G02 III

Other-than-serious 1 instance 2 exposed
Issued
Nov 28, 2018
Abate by
Dec 10, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that the strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.  Outside Maintenance Area - The flexible cord connected to a battery charger and light was not connected to a device and fitting so that strain relief was provided.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Owan, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343561551.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.