Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: VOLT POWER, LLC

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of VOLT POWER, LLC in 1054 N. ST. AUGUSTINE, DALLAS, TX 75217 (NAICS 221122). OSHA activity number 343630026.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Volt Power, LLC — free Get an email when a new federal OSHA severe-injury report for Volt Power, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
VOLT POWER, LLC
Site address
1054 N. ST. AUGUSTINE
City
DALLAS
State
TX
ZIP
75217
Mailing
8588 KATY FREEWAY, HOUSTON, TX 77024
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
5
Ownership type
A

5 citations on file for this inspection.

1910.269 Q01 III

Serious Gravity 10 1 instance 4 exposed
Issued
May 22, 2019
Abate by
Apr 18, 2022
Penalty
Initial $13,260 · Current $13,260
29 CFR 1910.269(q)(1)(iii): When a pole is set, moved, or removed near an exposed energized overhead conductor, the employer did not ensure that each employee wears electrical protective equipment or uses insulated devices when handling the pole and that no employee contacts the pole with uninsulated parts of his or her body.  On or about November 27, 2018, at a worksite located on St. Augustine Street, Dallas, Texas, employees working on replacing a pole near exposed energized electrical power lines were exposed to electrical shock and burn hazards.
Recent events (3)
  • — F (S) $13260
  • — C (S) $13260
  • — Z (S) $13260

1910.137 C02 VIII

Serious Gravity 10 1 instance 4 exposed
Issued
May 22, 2019
Abate by
Apr 18, 2022
Penalty
Initial $13,260 · Current $13,260
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment shall be subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-4 and Table I-5.  On or about November 27, 2018, at a worksite located on St. Augustine Street, Dallas, Texas, employees working on replacing a pole near exposed energized electrical power lines were exposed to electrical shock and burn hazards.
Recent events (3)
  • — F (S) $13260
  • — C (S) $13260
  • — Z (S) $13260

1910.269 A02 I A

Serious Gravity 10 1 instance 2 exposed
Issued
May 22, 2019
Abate by
Apr 18, 2022
Penalty
Initial $132,598 · Current $132,598
29 CFR 1910.269(a)(2)(i)(A): The employer did not ensure that each employee was trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments.  On or about November 27, 2018, at a worksite located on St. Augustine Street, Dallas, Texas, untrained employees  replacing a pole near exposed energized electrical power lines were exposed to electrical shock and burn hazards.
Recent events (3)
  • — F (S) $132598
  • — C (W) $132598
  • — Z (W) $132598

1910.269 P04 I

Serious Gravity 10 1 instance 4 exposed
Issued
May 22, 2019
Abate by
Apr 18, 2022
Penalty
Initial $132,598 · Current $132,598
29 CFR 1910.269(p)(4)(i): The employer did not ensure that mechanical equipment was operated so that the minimum approach distances, established by the employer under paragraph (l)(3)(i) of this section, were maintained from exposed energized lines and equipment.   On or about November 27, 2018, at a worksite located on St. Augustine Street, Dallas, Texas, employees working on replacing a pole near exposed energized electrical power lines were exposed to electrical shock and burn hazards.
Recent events (3)
  • — F (S) $132598
  • — C (W) $132598
  • — Z (W) $132598

1910.269 P04 III A

Serious Gravity 10 1 instance 4 exposed
Issued
May 22, 2019
Abate by
Apr 18, 2022
Penalty
Initial $132,598 · Current $132,598
29 CFR 1910.269(p)(4)(iii)(A): The employer did not ensure that energized lines or equipment exposed to contact are covered with insulating protective material that will withstand the type of contact that could be made during the operation.   On or about November 27, 2018, at a worksite located on St. Augustine Street, Dallas, Texas, employees working on replacing a pole near exposed energized electrical power lines were exposed to electrical shock and burn hazards.
Recent events (3)
  • — F (S) $132598
  • — C (W) $132598
  • — Z (W) $132598

View Volt Power, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343630026.