OSHA Inspection: VOLT POWER, LLC

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of VOLT POWER, LLC in 600 MARGARITAVILLE PARKWAY, MONTGOMERY, TX 77356 (NAICS 221122). OSHA activity number 345422620.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Volt Power, LLC — free Get an email when a new federal OSHA severe-injury report for Volt Power, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
VOLT POWER, LLC
Site address
600 MARGARITAVILLE PARKWAY
City
MONTGOMERY
State
TX
ZIP
77356
Mailing
3100 INTERSTATE NORTH CIRCLE SUITE 300, ATLANTA, GA 30339
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
8
Ownership type
A

2 citations on file for this inspection.

1926.952 C02

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Dec 2, 2021
Abate by
Dec 21, 2021
Penalty
Initial $10,728 · Current $0 Reduced
29 CFR 1926.952(c)(2): Additional briefings. Additional job briefings were not held when significant changes, which might affect the safety of the employees, occurred during the course of the work:  On or about July 15, 2021, at a site located on a lakeside resort in Montgomery, TX, employees were exposed to electrical hazards while replacing underground power transmission lines without conducting an additional job briefing when significant changes, which might affect the safety of the employees, occurred during the course of the work.
Recent events (3)
  • — F (S) $0
  • — C (S) $10728
  • — Z (S) $10728

1926.961 C06

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 2, 2021
Abate by
Dec 21, 2021
Penalty
Initial $13,653 · Current $10,000 Reduced
29 CFR 1926.961(c)(6): The employer did not verify that lines and equipment were deenergized by testing the lines and equipment to be worked with a device designed to detect voltage:    On or about July 15, 2021, at a site located on a lakeside resort in Montgomery, TX, employees were exposed to electrical hazards while replacing underground power transmission lines without testing the lines with a device designed to detect voltage before cutting the intact lines.