MONTGOMERY, TX —
OSHA Inspection: VOLT POWER, LLC
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of VOLT POWER, LLC in 600 MARGARITAVILLE PARKWAY, MONTGOMERY, TX 77356 (NAICS 221122). OSHA activity number 345422620.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VOLT POWER, LLC
- Site address
- 600 MARGARITAVILLE PARKWAY
- City
- MONTGOMERY
- State
- TX
- ZIP
- 77356
- Mailing
- 3100 INTERSTATE NORTH CIRCLE SUITE 300, ATLANTA, GA 30339
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 8
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.952 C02
- Issued
- Dec 2, 2021
- Abate by
- Dec 21, 2021
- Penalty
- Initial $10,728 · Current $0 Reduced
General-duty citation text
29 CFR 1926.952(c)(2): Additional briefings. Additional job briefings were not held when significant changes, which might affect the safety of the employees, occurred during the course of the work: On or about July 15, 2021, at a site located on a lakeside resort in Montgomery, TX, employees were exposed to electrical hazards while replacing underground power transmission lines without conducting an additional job briefing when significant changes, which might affect the safety of the employees, occurred during the course of the work.
Recent events (3)
- — F (S) $0
- — C (S) $10728
- — Z (S) $10728
1926.961 C06
- Issued
- Dec 2, 2021
- Abate by
- Dec 21, 2021
- Penalty
- Initial $13,653 · Current $10,000 Reduced
General-duty citation text
29 CFR 1926.961(c)(6): The employer did not verify that lines and equipment were deenergized by testing the lines and equipment to be worked with a device designed to detect voltage: On or about July 15, 2021, at a site located on a lakeside resort in Montgomery, TX, employees were exposed to electrical hazards while replacing underground power transmission lines without testing the lines with a device designed to detect voltage before cutting the intact lines.
Recent events (3)
- — F (S) $10000
- — C (S) $13653
- — Z (S) $13653
More inspections at Volt Power, LLC
View Volt Power, LLC's full OSHA safety record →
More inspections in this industry (NAICS 221122)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345422620.