CAMP LEJEUNE, NC ·
OSHA Inspection: U.S. DEPARTMENT OF DEFENSE
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of U.S. DEPARTMENT OF DEFENSE in 1230 HOLCOMB BLVD, CAMP LEJEUNE, NC 28547 (NAICS 424410). OSHA activity number 343634275.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. DEPARTMENT OF DEFENSE
- Site address
- 1230 HOLCOMB BLVD
- City
- CAMP LEJEUNE
- State
- NC
- ZIP
- 28547
- Mailing
- 1230 HOLCOMB BLVD, CAMP LEJEUNE, NC 28547
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424410
- Employees
- 100
- Ownership type
- Federal government (D)
Citations
5 citations on file for this inspection.
1910.303 B02
- Issued
- Feb 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) On or before November 27, 2018, Series of extension cords were daisy chained and were being used in lieu of fixed wiring to power an industrial coffee pot. b) On or before November 27, 2018, A re-locatable power tap, designed and listed being used with high concentrations of low powered loads was instead used with high powered loads such as a mini fridge and Sharp microwave.
Recent events (1)
- · Z (S) $0
1910.303 F02
- Issued
- Feb 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or before 27 November, 2018, 120/240 amps, electrical service panel was not marked to show which breakers operated which circuit or piece of equipment.
Recent events (1)
- · Z (S) $0
1910.304 G05
- Issued
- Feb 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: On or before November 27, 2018, employees were using industrial fans which did not have a grounding path. In two instances, the path to ground was not permanent, continuous, and effective.
Recent events (1)
- · Z (S) $0
1910.305 B01
- Issued
- Feb 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1): Openings through which conductors enter boxes, cabinets, or fittings were not effectively closed: a) On or about November 27, 2018, A 208v electrical panel had a 1/2 inch opening and was not effectively closed. b) On or about November 27, 2018, multiple electrical junction boxes were not equipped with a knockout cover which exposed employees to live parts.
Recent events (1)
- · Z (S) $0
1960.59 A
- Issued
- Feb 25, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.59(a): 29 CFR 1960.59(a): The Agency did not provide appropriate safety and health training for employees: The employer did not ensure employees charged with overseeing the Hobart Scale periodic maintenance schedule and enforcing safety rules and regulations were properly trained to ensure that the path to ground was permanent, continuous, and effective.
Recent events (1)
- · Z (S) $0
More inspections at U.S. Department of Defense
View U.S. Department of Defense's full OSHA safety record →
More inspections in this industry (NAICS 424410)
More inspections in NC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343634275.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.