OSHA Inspection: U.S. DEPARTMENT OF DEFENSE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of U.S. DEPARTMENT OF DEFENSE in 1230 HOLCOMB BLVD, CAMP LEJEUNE, NC 28547 (NAICS 424410). OSHA activity number 343634275.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of Defense for free Get an email when a new federal OSHA severe-injury report for U.S. Department of Defense is published. One employer, no account, unsubscribe in one click.
Site address
1230 HOLCOMB BLVD
City
CAMP LEJEUNE
State
NC
ZIP
28547
Mailing
1230 HOLCOMB BLVD, CAMP LEJEUNE, NC 28547
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424410
Employees
100
Ownership type
Federal government (D)

5 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a)  On or before November 27, 2018, Series of extension cords were daisy chained and were being used in lieu of fixed wiring to power an industrial coffee pot.   b)  On or before November 27, 2018, A re-locatable power tap, designed and listed being used with high concentrations of low powered loads was instead used with high powered loads such as a mini fridge and Sharp microwave.
Recent events (1)
  • · Z (S) $0

1910.303 F02

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:   On or before 27 November, 2018, 120/240 amps, electrical service panel was not marked to show which breakers operated which circuit or piece of equipment.
Recent events (1)
  • · Z (S) $0

1910.304 G05

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:   On or before November 27, 2018, employees were using industrial fans which did not have a grounding path.  In two instances, the path to ground was not permanent, continuous, and effective.
Recent events (1)
  • · Z (S) $0

1910.305 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1): Openings through which conductors enter boxes, cabinets, or fittings were not effectively closed:   a)  On or about November 27, 2018, A 208v electrical panel had a 1/2 inch opening and was not effectively closed.   b)  On or about November 27, 2018, multiple electrical junction boxes were not equipped with a knockout cover which exposed employees to live parts.
Recent events (1)
  • · Z (S) $0

1960.59 A

Serious Gravity 1 1 instance 1 exposed
Issued
Feb 25, 2019
Penalty
Initial $0 · Current $0
29 CFR 1960.59(a): 29 CFR 1960.59(a):  The Agency did not provide appropriate safety and health training for employees:    The employer did not ensure employees charged with overseeing the Hobart Scale periodic maintenance schedule and enforcing safety rules and regulations were properly trained to ensure that the path to ground was permanent, continuous, and effective.