Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: ASARCO LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ASARCO LLC in HAYDEN OPERATIONS 6094 N. ASARCO RD., HAYDEN, AZ 85135 (NAICS 331411). OSHA activity number 343642765.

Watch Asarco LLC — free Get an email when a new federal OSHA severe-injury report for Asarco LLC is published. One employer, no account, unsubscribe in one click.
Establishment
ASARCO LLC
Site address
HAYDEN OPERATIONS 6094 N. ASARCO RD.
City
HAYDEN
State
AZ
ZIP
85135
Mailing
P.O. BOX 8, HAYDEN, AZ 85135
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331411
Employees
607
Ownership type
A

3 citations on file for this inspection.

1910.269 C01 II

Serious Gravity 10 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $13260.00 · Current $13260.00
29 CFR 1910.269(c)(1)(ii): The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (c)(2) though (c)(4) of this section with the employees involved before they start each job:    a)   MCC ROOM: A job briefing including the required subjects under 29 CFR 1910.269 (c)(2) was not conducted to inform workers of the hazards associated with racking and rolling in the switchgear for the main air compressor, exposing employees to hazards from arc flashes including burns and heat inhalation. On December 5, 2018, three employee sustained burns resulting from an arc flash.
Recent events (3)
  • — F (S) $13260
  • — C (S) $13260
  • — Z (S) $13260

1910.269 L08 V

Willful Gravity 10 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $132598.00 · Current $106740.00 Reduced
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2:     (a) MCC ROOM:  Employees working on equipment with an arc rating estimate above 2.0 cal/cm2 were not wearing adequate protective clothing or provided with other protective equipment exposing employees to hazards from arc flashes including burns and heat inhalation.  On December 5, 2018, three employee sustained burns resulting from an arc flash.
Recent events (3)
  • — F (W) $106740
  • — C (W) $132598
  • — Z (W) $132598

1910.269 U02

Deleted Willful Gravity 10 1 instance 8 exposed
Issued
Abate by
Penalty
Initial $132598.00 · Current $0.00 Reduced
29 CFR 1910.269(u)(2): The employer didn't ensure that, when employees removed or insert draw-out-type circuit breakers, the breaker was in the open position. The employer did not also render the control circuit inoperable where the design of the equipment permitted.   a)   MCC ROOM: The employer did not ensure that the circuit would remain open and inoperable for the duration of the task when employees were inserting a 4160V breaker into switchgear, exposing employees to hazards from arc flashes including burns and heat inhalation. On December 5, 2018, three employee sustained burns resulting from an arc flash.
Recent events (3)
  • — F (W) $0
  • — C (W) $132598
  • — Z (W) $132598

View ASARCO LLC's full OSHA safety record →