FORT WAINWRIGHT, AK —
OSHA Inspection: ARMY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ARMY in CHENA BEND GOLF COURSE, FORT WAINWRIGHT, AK 99703 (NAICS 713910). OSHA activity number 343648887.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ARMY
- Site address
- CHENA BEND GOLF COURSE
- City
- FORT WAINWRIGHT
- State
- AK
- ZIP
- 99703
- Mailing
- 1060 GAFFNEY ROAD BUILDING 1555, FORT WAINWRIGHT, AK 99703
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 713910
- Employees
- 302
- Ownership type
- D
Citations
13 citations on file for this inspection.
1910.22 A03
- Issued
- Feb 1, 2019
- Abate by
- Mar 7, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(3): Walking-working surfaces were not maintained and kept free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice. DMWR Building 1185, Birch Hill Ski and Snowboard Area, west egress: on or about 28 November 2018, a loose sheet of plywood board measuring approximately 80x40 inches was used as a regular walking surface covering a construction trench. This condition exposed employees to a fall hazard.
Recent events (1)
- — Z (S) $0
1910.28 B01 I
- Issued
- Feb 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the following: Guardrail systems, safety net systems, or personal fall arrest systems. DMWR Building 1185, Birch Hill Ski and Snowboard Area, compressor room, valve pit: on or about 28 November 2018, the entry point to the rail compressor pit was not guarded, exposing employees to fall hazards of approximately 4 feet. This condition exposed employees to fall hazards.
Recent events (1)
- — Z (S) $0
1910.37 A03
- Issued
- Feb 1, 2019
- Abate by
- Mar 7, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit routes were not kept free and unobstructed. DFMWR Building 1185, Birch Hill Ski and Snowboard Area, west egress: on or about 28 November 2018, the employer did not ensure that the exit paths were clear. A construction pit running parallel to the building existed within the exit path impeding a timely egress. This condition exposed employees to a fire hazard.
Recent events (1)
- — Z (S) $0
1910.37 B01
- Issued
- Feb 1, 2019
- Abate by
- Apr 8, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that an employee with normal vision can see along the exit route. Building 3702, Nugget Lanes Bowling Center, pin setter maintenance shop: on or about 28 November 2018, the employer did not provide emergency exit lighting. Maintenance shop has no ambient lighting. This condition exposed employees to delays in exiting the building, smoke inhalation, fire, and tripping hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 B02
- Issued
- Feb 1, 2019
- Abate by
- Apr 8, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit". Building 3702, Nugget Lanes Bowling Center, pin setter maintenance shop: on or about 28 November 2018, Two instances were noted where the employer did not ensure that exit signs were posted along the exit route: a) The door way leading to the pin access area was not marked. This exit is designated as the primary exit. No emergency exit lighting available along this route. b) The door way leading to the outdoor exit route was not marked. This exit is designated as the alternate exit route. No emergency exit lighting available along this route. This condition exposed employees to delays in exiting the building causing smoke inhalation and fire hazards.
Recent events (1)
- — Z (S) $0
1910.37 B05
- Issued
- Feb 1, 2019
- Abate by
- Mar 7, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet). Building 3702, Nugget Lanes Bowling Center, pin setter maintenance shop: on or about 28 November 2018, the doorway to the storage area was not marked "Not an Exit" or identified by signage marking its actual use. Door way leads to a dead-end storage area. This condition exposed employees to delays in exiting the building causing smoke inhalation and fire hazards.
Recent events (1)
- — Z (S) $0
1910.212 B
- Issued
- Feb 1, 2019
- Abate by
- Mar 7, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving. Golf Course, Building 2096, shop bay: on or about 28 November 2018, the employer did not ensure that the Mark 1 Drill Press, model C114, serial number 15878, was securely mounted to prevent movement. This condition exposed employees to a struck by hazard.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Feb 1, 2019
- Abate by
- Mar 7, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Outdoor Recreation, Building 4050, workshop bench: on or about 28 November 2018, an energized 25 foot extension power cord was affixed along the wall and mounted in and through the workbench frame. This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
- — Z (S) $0
1910.305 G02 III
- Issued
- Feb 1, 2019
- Abate by
- Feb 21, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws. Outdoor Recreation, Building 4050, south-east corner workshop, electrical closet: on or about 28 November 2018, strain relief for a black 600 volt 8/3 heavy-duty portable flex-cord was damaged. This condition exposed employees to an electrical shock hazard.
Recent events (1)
- — Z (S) $0
1910.334 A02 I
- Issued
- Feb 1, 2019
- Abate by
- Mar 7, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): a) Golf Course, Building 2096, work bay: on or about 28 November 2018, an energized spring driven retractable incandescent utility shop light had visible damage to the outer protective jacket. This condition exposed employees to an electrical shock hazard. b) Building 3702, Nugget Lanes Bowling Center, center lane access area: on or about 28 November 2018, an energized ProNautic digital charging platform, model 2420P had visible damage to the outer protective jack adjacent to the cord plug. This condition exposed employees to an electrical shock and electrical burn hazard. c) Ski Area, DMWR Building 1185, west-side building exterior: on or about 28 November 2018, an energized 25 foot orange extension power cord used to heat snow groomers had visible damage to the outer protective jacket in the form of cracks and strain relief. This condition exposed employees to an electrical shock hazard. d) Outdoor Recreation, Building 4050, workshop bench: on or about 28 November 2018, an energized 25 foot extension power cord had visible burn damage to the outer protective jacket. This condition exposed employees to an electrical shock hazard.
Recent events (1)
- — Z (S) $0
1960.8 A
- Issued
- Feb 1, 2019
- Abate by
- Mar 7, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.8(a): The Agency head did not furnish employment and a place of employment to each employee that were free from recognized hazards that caused or were likely to cause death or serious physical harm. Chena Bend Golf Course, Building 2095, bay area: on or about 28 November 2018, a metal warehouse pallet storage rack was not secure to the wall or floor. Pallet rack is located in a seismically active zone. This condition exposed employees to a struck by hazard.
Recent events (1)
- — Z (S) $0
1910.157 E02
- Issued
- Feb 1, 2019
- Abate by
- Mar 7, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly. Golf Course, Building 2096: on or about 28 November 2018, Amerex ABC portable, multi-purpose stored pressure dry chemical fire extinguishers were not inspected at least monthly. Fire extinguishers indicated test was last conducted in August 2017. This condition exposed employees to a fire hazard.
Recent events (1)
- — Z (O) $0
1910.165 E
- Issued
- Feb 1, 2019
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.165(e): Manually operated actuation devices for use in conjunction with employee alarms were not unobstructed, conspicuous and readily accessible. Golf Course, Building 2095, adjacent to the western exit door: on or about 28 November 2018, the employer did not ensure that Honeywell manual operated fire pull station was clear of obstructions. Fire pull station had miscellaneous items stored in front of the pull station impeding immediate access. This condition exposed employees to smoke inhalation and fire hazards.
Recent events (1)
- — Z (O) $0
More inspections at Army
View Army's full OSHA safety record →
More inspections in this industry (NAICS 713910)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343648887.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.