Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,892Inspections Most recent open 2026-09-03 Last loaded 2026-09-07

OSHA Inspection: KIEWIT POWER CONSTRUCTORS CO.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of KIEWIT POWER CONSTRUCTORS CO. in 1 ARMORCAST ROAD, BIRDSBORO, PA 19508 (NAICS 237130). OSHA activity number 343662359.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Kiewit Power Constructors CO. for free Get an email when a new federal OSHA severe-injury report for Kiewit Power Constructors CO. is published. One employer, no account, unsubscribe in one click.
Site address
1 ARMORCAST ROAD
City
BIRDSBORO
State
PA
ZIP
19508
Mailing
3555 FARNAM ST., SUITE 1000, OMAHA, NE 68131
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
400
Ownership type
Private (A)

4 citations on file for this inspection.

1926.416 A01

Other-than-serious 1 instance 2 exposed
Issued
Apr 29, 2019
Abate by
Apr 6, 2020
Penalty
Initial $11,934 · Current $11,934
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:    a) Birdsboro Power Plant - isophase generator circuit breaker system: On or about December 13, 2018, employees assigned to work within the circuit breaker were exposed to electric shock due to uncontrolled voltage that originated and backfed from the switchyard.     Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (3)
  • · F (O) $11934
  • · C (S) $11934
  • · Z (S) $11934

1926.417 A

Other-than-serious 1 instance 2 exposed
Issued
Apr 29, 2019
Abate by
Apr 6, 2020
Penalty
Initial $11,934 · Current $11,934
29 CFR 1926.417(a): Controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were not tagged:    (a) Birdsboro Power Plant - isophase generator circuit breaker system: On or about December 13, 2018, backfed voltage entering the circuit breaker from the switchyard was neither deactivated or tagged out prior to employees working within the circuit breaker.     Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (3)
  • · F (O) $11934
  • · C (S) $11934
  • · Z (S) $11934

1926.1051 A

Other-than-serious 1 instance 2 exposed
Issued
Apr 29, 2019
Abate by
May 16, 2019
Penalty
Initial $3,836 · Current $3,836
29 CFR 1926.1051(a): Stairway(s) or ladder(s) were not provided at all personnel points of access where there was a break in elevation of 19 inches (48 cm) or more, or no ramp, runway, sloped embankment, or personnel hoist was provided:    a) Birdsboro Power Plant: On or about December 13, 2018, the employer did not provide a ladder or other safe means of access for an employee accessing the isophase generating circuit breaker. The lid of the isophase is located approximately 11 feet above the lower expanded metal platform.    Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date, and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (3)
  • · F (O) $3836
  • · C (S) $3836
  • · Z (S) $3836

1926.1203 A

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Apr 29, 2019
Abate by
May 16, 2019
Penalty
Initial $11,934 · Current $0 Reduced
29 CFR 1926.1203(a): Before it began work at a worksite, the employer did not ensure that a competent person identified all confined spaces in which one or more of the employees it directed may have worked, and/or did not identify each space that was a permit space, through consideration and evaluation of the elements of that space, including testing as necessary:  a) Birdsboro Power Plant: On or about December 13, 2018, the employer did not identify the isophase generating circuit breaker as a confined space prior to assigning employee work activities within the space.   Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (3)
  • · F (S) $0
  • · C (S) $11934
  • · Z (S) $11934

View Kiewit Power Constructors CO.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343662359.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.